TEZ8 Self-Flush Procedure

Тәжірибелік нұсқаулар және стиль

Thanks to a unique oil system, it’s easy to clean the Appion TEZ8 Vacuum Pump after use on unusually dirty or contaminated systems. This simple oil flush procedure is the same used at the factory to restore performance due to dirty oil and/or insufficient oil changes. It’s recommended to perform this procedure after evacuating burnout systems, very wet systems, Ammonia or Lithium Bromide systems, or just as a part of regular maintenance.
1. Install a clean TEZOM Cartridge
2. Turn on the machine
3. Throttle the input with a Valve Core Removal Tool on the 1/4" input (part# MGAVCT)
4. Run the machine for at least 5 minutes
5. Repeat the process until the oil is clear
If your TEZ8 is having difficulty evacuating systems, try this flushing procedure before attempting any repairs. Be sure to test the pump before and after with a vacuum gauge connected directly to the pump so you can measure the results.
Questions? Contact our support team: support@AppionTools.com or 303-937-1580
----
About Us:
Appion is Applied Innovation. We never stop challenging ourselves to develop smaller, lighter, and more innovative tools for HVAC/R technicians. Appion’s solutions for fast Refrigerant Recovery, Evacuation and Measurement include: G5Twin Recovery Machine, TEZ8 Vacuum Pump, appION Wireless Digital Gauges, and MegaFlow Vacuum-Rated Tools.
Visit us at AppionTools.com!