100A SWITCH FUSE ISOLATOR INSTALL

hope you lot enjoyed the video.
remember to check out the socials
insta / rdaviselectrical
TikTok / rdaviselectrical

Пікірлер: 107

  • @abdoaiman
    @abdoaiman Жыл бұрын

    Leaving extra length of the armoured would make the job easier i believe .. Well done sparky 👍

  • @daveenglish2031
    @daveenglish20314 ай бұрын

    great vid. Ive got to do one this week. what's the general thoughts on running the swa up the cavity?? If i cant get it up the cavity then I'm going to have to chase it into the block behind the dot and dab :/

  • @fire_stick
    @fire_stick5 ай бұрын

    DNO fuse is to protect the installation as a whole metering etc, the additional fuse is required to protect the cabling to the CU. Not required if CU is closer.

  • @therealdojj
    @therealdojj Жыл бұрын

    So is it purely because of the distance then? I think a saw another video about the same thing earlier today

  • @ru8y1987
    @ru8y1987 Жыл бұрын

    Assuming the DNO puts a 100a in... your fuse needs to be max 80a. Selectivity and all that 👍

  • @Emin3m1986

    @Emin3m1986

    Жыл бұрын

    No, you don`t... because there is no need for selectivity there.

  • @ru8y1987

    @ru8y1987

    Жыл бұрын

    @@Emin3m1986 who says?

  • @Danny-npgbp

    @Danny-npgbp

    6 ай бұрын

    DNO will only fit 80a fuse in cutout. Your 100a fuse pointless. Really needs to be 63a to allow for discrimination between household circuit and DNO supply.

  • @robtmcL12

    @robtmcL12

    4 ай бұрын

    I'm DNO and can confirm we have recently had instruction to fit an 80 amp in the 100 amp cutout. The reason being it will allow 120 amp + for a few hours. The time/current curve for the BS88 will confirm this. As for discrimination, you don't need to bother. It's 50/50 which one will fail first and if it's the DNO one that gives up first, they will respond within 2 hours anyway. In some instances ( flats with submains ) we use a red fuse link in the flat as there's already fuse protection in the Distribution board ( eg Bemco/Rapell/Schnieder boards ).

  • @aclarke0100
    @aclarke0100 Жыл бұрын

    What grips did you use please

  • @connormelia2926
    @connormelia292610 ай бұрын

    Top stuff

  • @sergiofernandez3725
    @sergiofernandez3725 Жыл бұрын

    Why was it not an 80amp fuse upstream of the 100amp main cutout? Descrimination/ Selectivity and what not

  • @kittsdiy

    @kittsdiy

    Жыл бұрын

    +1 .. now it's the strongest fuse who will not pop :p 50/50 chance the DNO one will trip :p

  • @ljtr2112
    @ljtr2112 Жыл бұрын

    Great work mate… the guy from the DNO will appreciate the work too. Not understanding the ball ache you had leaving plenty of room for the meter 👍

  • @RDavisElectrical

    @RDavisElectrical

    Жыл бұрын

    Cheers mate. He better appreciate it 😂😂

  • @benYMSB

    @benYMSB

    5 ай бұрын

    The meter provider won’t touch it. They don’t connect to a de-energised supply and on the basis there’s no room for an isolator, they’d walk away.

  • @shiamjad
    @shiamjad11 ай бұрын

    very helpful video....

  • @abcd-by6rw
    @abcd-by6rw Жыл бұрын

    Curious if its recommended putting some kind of terminal on the bare conductor? or if this does not matter, cheers!

  • @abcd-by6rw

    @abcd-by6rw

    Жыл бұрын

    i.e. crimp or other

  • @tomlloyd9372
    @tomlloyd9372 Жыл бұрын

    Nice. FYI, its the meter operator (eon, british gas etc) who will install the meter. DNO own up to the cutout before the meter, so will not install that

  • @0liver0verson9

    @0liver0verson9

    6 ай бұрын

    Yep.

  • @chrischris3551
    @chrischris35518 ай бұрын

    Great job,quick question, what’s the point of using a 100A isolator when the mains got a 100A alright supporting it?

  • @mcoys1029

    @mcoys1029

    Ай бұрын

    If the tails are longer than 3 metres away from the consumer unit you have to put in a fused mains switch due to regs

  • @chandreshvarsani2190
    @chandreshvarsani2190 Жыл бұрын

    I've done a couple of these, it's easier to curl the wires at both lod and supply side. I always leave length on cables just in case and it looks just as tidy. Not sure why earth nut or banjo wasn installed from source side as less likely to get tampered or disconnected 🤔

  • @sebastiannielsen

    @sebastiannielsen

    10 ай бұрын

    Tampering with Earth or Neutral won't in any way get you free electricity, it will just make the life more dangerous. So putting them on "consumer side" is actually preferred, since then if the consumer or any electrician needs to make a measurement on for example earth or neutral, you usually need to separate these (NOTE: Very dangerous, should be done with isolated supply) and then you can measure, for example, track down cheater earths (cheater earths are when you make a fake earth out of the neutral on a socket - super dangerous!) - this by connecting a beeper transmitter on the now disconnected earth, and then making sure every socket beeps. If a socket doesn't beep, its a sign that the earth in that socket is fake. Disconnected neutrals and earths also have other usages, measuring resistance to find out cable lengths and impedance, tracing broken earths and neutrals and lots of other uses, and it would be a pity to have to call DNO or meter company just to do some troubleshooting on earth or neutral. So always leave earth and neutral easily accessible on consumer side.

  • @JJ-lf4er
    @JJ-lf4er Жыл бұрын

    Do you not usually use the grey for the earth and black for neutral or doesn’t it matter as long as it’s sleeved?

  • @RDavisElectrical

    @RDavisElectrical

    Жыл бұрын

    No mate, black for CPC always 👍🏻

  • @NickGirnius

    @NickGirnius

    Жыл бұрын

    Deneutralization of black means it will always be CPC and grey will be the neutral mate

  • @mikethemask1525

    @mikethemask1525

    Жыл бұрын

    Denuetralize the black always grey is neutral and should be sleeved blue.

  • @_eusty

    @_eusty

    Жыл бұрын

    I do the same, but really there are no regs, as long as they are identified correctly.

  • @Riggersa

    @Riggersa

    Жыл бұрын

    @@_eusty there are regs for it, if you look in the regs book where it lists the colours, now black should never be used as as a neutral with new colours

  • @ElectricianTV
    @ElectricianTV Жыл бұрын

    Nice one Ryan that is always a bitch of a job. Even if you do armours every day.its still shit. You made it look easy keep up the good work. The only thing I do different is I take the grommet out of the gland and put it back in, so the 2 25 mm holes are at the back.

  • @RDavisElectrical

    @RDavisElectrical

    Жыл бұрын

    Cheers Andrew, appreciate it, yeah it’s a git of a job.

  • @ELECTRICLIFE4U
    @ELECTRICLIFE4U Жыл бұрын

    👍👍👍👍👍

  • @tim4182
    @tim4182 Жыл бұрын

    22/58 100a fuse is an European style industrial fuse NOT a domestic 22/57 house service type. Any short circuit fault would blow the DNO fuse and not the one in the switch fuse,I've seen this happen before,these fuses have a much higher watts loss and pre arcing values are higher

  • @supersparks9466
    @supersparks9466 Жыл бұрын

    Those switch fuses are pants, just no room in there. I always buy the Wylex ones ,plenty of room in them.

  • @corbs07
    @corbs07 Жыл бұрын

    Any reason why you didn’t use a stuffer instead of a swa gland as it’s earth distro end ?

  • @RDavisElectrical

    @RDavisElectrical

    Жыл бұрын

    Nah no reason mate

  • @mikethemask1525

    @mikethemask1525

    Жыл бұрын

    I've used these once, personally I prefer the metal swa glands feels better even if it's just my excuse to get grips out and show off 😂

  • @lisabarton22
    @lisabarton227 ай бұрын

    Is it possible for the switch to go off but not blow fuse?

  • @olegbirfon-ss3fs
    @olegbirfon-ss3fs2 ай бұрын

    hi, anybody could explain when we could place 63amp, or 80amp or 100amp? after installed smart meter it increased the bill cost, burn off extractor, washing machine, hair drier, thank you have a nice day

  • @mrutubeuk
    @mrutubeuk Жыл бұрын

    Did you run the swa through the cavity if so how much of it?

  • @JonNelson90WBN

    @JonNelson90WBN

    Жыл бұрын

    Didn’t he say the consumer unit was roughly 12mtr away?

  • @henrytwigger2245
    @henrytwigger2245 Жыл бұрын

    The supply companies use to insist that no consumer apparatus be installed in meter cabinets, has that changed ?

  • @kobirelf97

    @kobirelf97

    9 ай бұрын

    This is technically not true in this case when a consumer unit is more than 3 m away from the main head there has to be an isolator of some kind

  • @johnwaby4321
    @johnwaby4321 Жыл бұрын

    I would have put the tails gland above the main switch they would have gone straight in .. And fit an earthing nut on the swa gland .

  • @marcwilliams3921
    @marcwilliams3921 Жыл бұрын

    That neutral on the load side must of been a right pig

  • @RDavisElectrical

    @RDavisElectrical

    Жыл бұрын

    Yep, it was 👍🏻😂

  • @philbennett806
    @philbennett806 Жыл бұрын

    I installed one for a meter move, wrestled with the 25mm 3core only for the DNO to put in cable that was no bigger than my thumb! What’s that all about?!

  • @RDavisElectrical

    @RDavisElectrical

    Жыл бұрын

    😂😂ffs

  • @darrenplant1428

    @darrenplant1428

    Жыл бұрын

    Possibly try rated?

  • @joehamilton2999

    @joehamilton2999

    Жыл бұрын

    Would’ve been Concentric cable mate if TNCS

  • @Emin3m1986
    @Emin3m1986 Жыл бұрын

    Mate, I`m curious how did you manage to put back the front of the Fused Switch Panel... I guess that you know what I mean.

  • @temp06j723-pmeighttq

    @temp06j723-pmeighttq

    11 ай бұрын

    The packaging is provided with extra stickers

  • @michaeltye8853
    @michaeltye8853 Жыл бұрын

    Pay slightly more and you can have colour coded SWA ….BROWN..BLUE …GREEN/YELLOW ..worth the extra .

  • @RDavisElectrical

    @RDavisElectrical

    Жыл бұрын

    It’s really no time at all to put the heat shrink on, plus the heat gun kept my hands warm 😂

  • @kittsdiy

    @kittsdiy

    Жыл бұрын

    +1 i really don't get this .. seems every UK elektrician buys the SWA for industrial 3 phase use with black/brown/grey . And changes the colors . Here in Belgium this is not really allowed as it is confusing . Using a black conductor for PE etc .. just buy the correct cable for domestic .. and it seemes UK is 99% single fase in houses .. should be no problem to find correct cable .( in Belgium we call this 3G16 / 3G25 . The G tells there is a ground wire( CPC yellow green in ) and 2 wires for current blue and brown(or black ) .

  • @_eusty

    @_eusty

    Жыл бұрын

    @@kittsdiy That's because 3 core SWA is generally used on 3 phase systems....

  • @kittsdiy

    @kittsdiy

    Жыл бұрын

    @@_eusty yep for 3x400V industrial use the colors are correct .. and NO neutral wire . And CPC is run seperate .. So domestic elektricians just buy the wrong cable and relabel it .. Would not pass inspection here official . the color has to be the same for whole cable ( so recoloring black to green/yellow is not ok here ) . But i think in UK after installation no external company needs to inspect the electricians work and aprove .. i have seen many do it on youube .. so i guess it's allowed in UK ..

  • @seano452

    @seano452

    Жыл бұрын

    Hence the sleeving…. If the sleeving is blue or green or brown, then that states what the conductor is. 👍🏻

  • @BK-jc7ik
    @BK-jc7ik Жыл бұрын

    😁✋✋

  • @tomcollinson5433
    @tomcollinson5433 Жыл бұрын

    Bet getting the cover on was a nightmare😂

  • @gavinnoname1424

    @gavinnoname1424

    Жыл бұрын

    Pretty sure the each connection for the lid is on the right hand side too

  • @Lordmarkstuckey4161
    @Lordmarkstuckey41613 күн бұрын

    Why are Meters now fitted on the outside of the house?

  • @23lnp

    @23lnp

    2 күн бұрын

    So the powers that be can gain access to it without you needing to be home. They cant enter your home by law unless you let them in. If you build a metal cage around your outdoor meter then they cant gain access and if they break it to get to the meter its classed as criminal damage.

  • @andrewjames3908
    @andrewjames39087 ай бұрын

    Whats the limit on how long the cable run can be in this situation?

  • @peterigrenyi9176

    @peterigrenyi9176

    6 ай бұрын

    No limit really. But you have to size cable correctly for voltage drop. (And i do not mean limitless as in 1 million miles... )

  • @ascorpio1
    @ascorpio111 ай бұрын

    Why 25mm SWA and not 16mm?

  • @temp06j723-pmeighttq

    @temp06j723-pmeighttq

    11 ай бұрын

    Why not 25mm² ? Why not 35mm² ??

  • @ascorpio1

    @ascorpio1

    11 ай бұрын

    @@temp06j723-pmeighttq Because my understanding is that the cable size and fuse should match the setup. The DNO fuse is 100 amps. The tails are 25mm which support amps of over that size of use or thereabouts. If you then are going to build a distribution network then the DNO then expects you to go lower in cable size and fuse to protect their fuse. A 25mm cable matches the tails which isn’t the correct way to build a distribution network hence the question. I think the distribution network needs to be lower cable and fuse so that if there was an issue on it then it would protect the DNOs fuse and setup but I’m not qualified and learning so if you know the answer I’d be glad to hear it.

  • @temp06j723-pmeighttq

    @temp06j723-pmeighttq

    11 ай бұрын

    DNO's cabling protection is another complex story. CutOut is to protect Meter Tails etc. When given a 100A service Cut Out, you wouldn't be fitting a 16mm² Tails unless you Downsize the Switch-fused Isolator + fuse to a 80A then it will be fine. But then it will be a waste, considering the ability the DNO to Service up to 100A yet we downgrade our PERMANENT Cabling(meter tails) to a lower size that Forever is Binded/capped to 80A in the future (with using of 16mm²). Hope it makes sense.

  • @stevenredmond7455
    @stevenredmond7455 Жыл бұрын

    The meter box isn’t your’s so how do you get away with using it for your sw fuse. I’ve always had to put it either inside property of 2nd box.

  • @RDavisElectrical

    @RDavisElectrical

    Жыл бұрын

    You can’t be serious?

  • @stevenredmond7455

    @stevenredmond7455

    Жыл бұрын

    @@RDavisElectrical Yes i am serious. Maybe you require more experience. Different area’s i suppose have different rules. In Cambridgeshire we had to use a separate meter box for sw fuse. We were not allowed to fit anything in with the head & meter.

  • @persona250

    @persona250

    Жыл бұрын

    The meter box is property of the homeowner.

  • @stevenredmond7455

    @stevenredmond7455

    Жыл бұрын

    @@persona250 The box is but not what goes in it.

  • @karlfleming7182

    @karlfleming7182

    10 ай бұрын

    @@stevenredmond7455 Nah steve sw fuse can go in meter box!

  • @whitey4909
    @whitey4909 Жыл бұрын

    Should you be fitting a 100a switch fuse?

  • @kittsdiy

    @kittsdiy

    Жыл бұрын

    that would probably trip faster then DNO (melt) fuse. I would go for this approach i think.

  • @tomturner4590
    @tomturner4590 Жыл бұрын

    Just curious as to what is the need for another fuse next to the main fuse?

  • @RDavisElectrical

    @RDavisElectrical

    Жыл бұрын

    We aren’t allowed to touch the main fuse 😅

  • @RDavisElectrical

    @RDavisElectrical

    Жыл бұрын

    Without ringing the DNO anyway

  • @kittsdiy

    @kittsdiy

    Жыл бұрын

    Also i hope the extra one is faster then the one from the DNO 🙂 Seems a bit useless 2 100A melt fuses after eachother .. if the new one trips first your lucky .. you can replace it . If the DNO ones trips you have to call DNO or break the seal . ( kinda funny in uk they do'nt have automatic fuses from the DNO .. proably because melt fuses are cheaper )

  • @neil6438

    @neil6438

    Жыл бұрын

    @@kittsdiy I thought that....

  • @darrenplant1428

    @darrenplant1428

    Жыл бұрын

    It’s because the cable is over the recommended distance. And runs in the fabric of the building.

  • @GRANTY960
    @GRANTY960 Жыл бұрын

    Don’t suppose you had to move the new enclosure about 3mm to the left to get the cover on did you 👀🤣

  • @RDavisElectrical

    @RDavisElectrical

    Жыл бұрын

    Nope, went on, just 😬😅😂

  • @GRANTY960

    @GRANTY960

    Жыл бұрын

    @@RDavisElectrical the squeaky bum when you remember the cover over laps 😂

  • @philtaylor3184

    @philtaylor3184

    8 ай бұрын

    ​@@GRANTY960and the bonding strap for the front cover isn't fitted

  • @JC-sd3vh
    @JC-sd3vh8 ай бұрын

    Fuse switch

  • @jonte7582
    @jonte7582 Жыл бұрын

    how come the cables dont come with the right colour? Brown, Blue, Earth

  • @StuartJ

    @StuartJ

    10 ай бұрын

    Because the cable used was 3 phase + armoured (earth). Not sure why you wouldn't use 2 core, plus armoured.

  • @karlfleming7182

    @karlfleming7182

    10 ай бұрын

    @@StuartJ Having Earth as a wire in the cable from meter to the unit is more reliable than relying on the armour

  • @StuartJ

    @StuartJ

    10 ай бұрын

    @@karlfleming7182 I don't see how. So long as the armour is correctly terminated.

  • @rossdavis6837
    @rossdavis6837 Жыл бұрын

    Looks like agg bro😂

  • @RDavisElectrical

    @RDavisElectrical

    Жыл бұрын

    It really was 😩😂😂

  • @stevedebbiemoore
    @stevedebbiemoore Жыл бұрын

    Is there room for a smart meter🤔

  • @RDavisElectrical

    @RDavisElectrical

    Жыл бұрын

    Plenty

  • @avreclaim6469
    @avreclaim6469 Жыл бұрын

    Bin the banjo, Use Earth Nuts - It is 2022!! 🙂 Also you have left that WRONG, the Isolator should kill the fuse, not a slick mod! Probably a job for CW, NOT a BW Gland as well....

  • @karlfleming7182

    @karlfleming7182

    10 ай бұрын

    yeah have to say this wasn't a great job on this video

  • @BlackDragonSP
    @BlackDragonSP Жыл бұрын

    Хм, запасика у нуля нету

  • @aclarke0100
    @aclarke0100 Жыл бұрын

    What grips did you use please

  • @RDavisElectrical

    @RDavisElectrical

    Жыл бұрын

    Knipex pliers wrench