Return to Troubleshoot AC Compressor with Open Windings

Ғылым және технология

I was doing an AC maintenance and ran into this packaged AC not cooling. Found the compressor not running and windings open. The air conditioners compressor was extremely hot. I return the following day to see if windings closed. Also troubleshoot the faulty compressor.
When I approached the air conditioner, first thing I did was turn on the power at disconnect. I heard the compressor start up and run. I noticed the suction line was warm. I checked pressures and they were about equal. The compressor didn’t sound good. I changed the power/ phase into the units contactor, to see if the compressor was running out of phase. After this the compressor started pumping correctly. The compressor was out of phase. After the video I cleaned the condenser coil.

Пікірлер: 17

  • @WillPlaysGames1993
    @WillPlaysGames19934 күн бұрын

    glad to see your back uploading again i missed your videos since you always made them seem fun but educational at the same time

  • @thehvachacker

    @thehvachacker

    4 күн бұрын

    glad you enjoy my experiences at work

  • @tedcatino5593
    @tedcatino55934 күн бұрын

    glad your back

  • @MoellerEngineeringCo.
    @MoellerEngineeringCo.4 күн бұрын

    Good fix Bill. Most tech's would not think of switching one of the 3 phases. There are probably more problems in this building.

  • @thehvachacker

    @thehvachacker

    4 күн бұрын

    I ran into a compressor in past doing this, even have a vid kzread.info/dash/bejne/h4qi0cWPftGth6Q.htmlsi=1bi66P42d0lmE32h. around the 15:15 time. this was first time I ran into a compressor doin this. all other units are from a different panel. this unit 8s from a panel in a part of building that got renovated.

  • @MoellerEngineeringCo.

    @MoellerEngineeringCo.

    4 күн бұрын

    @@thehvachacker That makes perfect sense. When they did the remodel, the electrician unknowingly switched the phases in the panel.

  • @edbonjovi9133
    @edbonjovi91334 күн бұрын

    Hello from leak master plumbing Great. To see u. Bill

  • @andrewredmon4197
    @andrewredmon41974 күн бұрын

    He's back!

  • @sungkim7579
    @sungkim75794 күн бұрын

    Welcome back good

  • @thehvachacker

    @thehvachacker

    4 күн бұрын

    thanks

  • @SixTwoHemi
    @SixTwoHemi4 күн бұрын

    Nice work

  • @thehvachacker

    @thehvachacker

    4 күн бұрын

    thanks

  • @commenter5469
    @commenter54694 күн бұрын

    Just the sound of the compressor let you know it’s running backwards. Scrolls usually not really noisy

  • @peckerpeter2078
    @peckerpeter20784 күн бұрын

    What’s the oil level at?

  • @mikev.1034
    @mikev.10344 күн бұрын

    👍🤙🤘😯

  • @Ivansgarage
    @Ivansgarage4 күн бұрын

    Should of been switched in the disconnect, not the contactor

  • @thehvachacker

    @thehvachacker

    4 күн бұрын

    Next time I’m up there I will. It runs and I’m the only one to work on it.