Pull Box Sizing. The "U-Pull"

Автокөліктер мен көлік құралдары

Using the 2018 Canadian Electrical Code I size a pull box specifically with conductors entering and exiting on the same wall, otherwise known as the "U-Pull"
I reference 12-3036 as the rule for this.
This video is intended as an instructional aid and further clarification should be obtained through your local jurisdictional electrical authority. Thanks for watching.

Пікірлер: 14

  • @erick.5103
    @erick.51034 жыл бұрын

    YOUR THE MAN! thanks for CEC content

  • @larryteslaspacexboringlawr739
    @larryteslaspacexboringlawr7394 жыл бұрын

    thank you for fixing sound, great video

  • @butters742
    @butters7424 жыл бұрын

    Keep the videos coming. I love all the videos people make on Electrical but not many are using the Canadian code since there state side. Still appreciate any video but nice to see a video on the Canadian Electrical codes

  • @johnshahin1377
    @johnshahin13772 жыл бұрын

    Thanks alot for your tutorial in these KZread videos it's really helpful for me, I managed to get 309a license, best wishes ever for you, forward ever

  • @schulerruler

    @schulerruler

    2 жыл бұрын

    Thanks for watching and congratulations!

  • @johnshahin1377

    @johnshahin1377

    2 жыл бұрын

    @@schulerruler thanks again

  • @__________f9433
    @__________f9433Ай бұрын

    Thank you

  • @H.A..
    @H.A..2 жыл бұрын

    excellent, thank you.

  • @thetimelords911
    @thetimelords9113 жыл бұрын

    How exactly do you calculate the length of the other side of the box? You would need to know the distance between the conduit entry points and the outside walls of the box right? How do you find that?

  • @schulerruler

    @schulerruler

    3 жыл бұрын

    The width of the box would be determined from the minimum space required between the connectors of the conduits containing the same conductors. 12-3036 2) c) ii) says six times the diameter of the largest Raceway containing the same conductors. So that, plus the necessary room for the connectors and their locknuts would be the minimum dimension of the other side.

  • @jagdeep324
    @jagdeep3244 жыл бұрын

    Great

  • @712anup1
    @712anup1 Жыл бұрын

    May i please ask, how did you have 53 TSC?

  • @InServiceForTheGoodofAll
    @InServiceForTheGoodofAll3 жыл бұрын

    They’ve deleted table 6. It’s 6A now

  • @schulerruler

    @schulerruler

    3 жыл бұрын

    And it's even more different now in the 2021!