Do Pancakes Violate Code? How Many Conductors can ACTUALLY Fit?

Do Pancakes Violate Code? Absolutely not!! They are delicious! Oh. Not that kind of delicious, syrupy goodness, but rather pancake electrical boxes!! If you have ever had the pleasure to install or perform service with one of these boxes, you know exactly what we are talking about!! On this episode of Electrician U, Dustin takes an adventure to find out if in fact the round pancake boxes we see, as electricians, are code compliant. I know, I know, I was hoping for a road trip for pancakes too!! 😊
🤘⚡️MEMBERSHIP⚡️🤘
JOIN ELECTRICIAN U - become a member and get:
FREE Continuing Education every year
FREE Practice Exams
FREE Monthly Video Courses
FREE Weekly Live Instructor-Led Classes
FREE Monthly Educational Newsletter
Premium Members-Only Content
Private Discord Channel
Monthly Members-Only Discord Chats
Sign up here --- www.electricianu.com/electric...
🎧🎹MUSIC AND VIDEO:🎹🎧
/ descantmv
🎬✍️ART AND ILLUSTRATION:✍️🎬
www.daverussoart.com
First, what would we use a pancake box for? These boxes can be rather handy if you have to install a box for a light fixture with very little clearance behind them. Biggest item that comes to mind is if the fixture needs to be installed directly where a stud is, and we don’t have a void in the wall for a box. You simply install the box to the stud, install your wires and the drywall covers up the depth of the box (as there is no plaster/tile ring) to install. You then would mount your fixture over the box, terminate your wires, and move on to the next task. While this application is handy for placement of the box, it can cause other issues such as not enough wire bending space, pinched wires (due to the shallow depth of the box), and other items.
Article 314.16 of the NEC (and I am paraphrasing here!) that a box shall be sized to provide enough free space for all the conductors in it. Within the article, there are a few areas that provide us with some guidance. B1 covers conductors; so, the wires themselves. B2 covers clamp fill; this is for any INTERNAL connectors (some metallic boxes have these built in and must be accounted for). B3 covers support fittings; some luminaires have a stud that holds the fixture to the box). B4 covers device/equipment; things like switches or receptacles themselves. B5 covers equipment grounding conductors; these are counted separately from the phase and neutral conductors as there can be more of them than any other conductor in certain situations.
Table 314.16(A) and 314.16 (B) are two tables that are used to size some standard boxes as well as some standard conductors. To use Table 314.16(B), simply find the corresponding wire size you are using, multiply by how many conductors you have in the box of that size and deduct for the equipment grounds (we only count them all as 1 conductor until you get to 4, then .25 of an allowance for every other equipment ground over 4). Once that number is generated, compare it to Table 314.16(A) with the box that you are attempting to use. Remember, you must account for devices, internal cable clamps and studs as well! If the number you came up with is larger than the amount for the box you are trying to use, you will have to select a larger box that will fit the number of conductors you need.
The boxes should have their volume stamped in them. 4” pancake boxes have a volume of about 6 CI and 3” pancake boxes have a volume of around 4 CI. Considering that a piece of #12 wire takes up 2.25 inches, that means you could not get a piece of 12-2 Romex into a 3" box. A piece of #14 wire takes up 2 inches so one piece of that cable WOULD be acceptable to put in there, but not if you had a device, a fixture stud, or an internal connector.
So, we can see that for most applications, a pancake box is too small to use for either 12-2 OR 14-2 especially if they have internal cable clamps in the box. So, what are our options? We could select a box without internal clamps, make sure and use 14-gauge wire (provided it worked with the ampacity of our fixture), and place the box at the end of the run and only had the one piece of cable entering it. It is simply a numbers game!
We hope this demystified the pancake box size issue! Please continue to follow Electrician U and Dustin as we are constantly adding new content to help our followers on their careers as electricians!
#electrician #electrical #electricity

Пікірлер: 305

  • @williamsnyder6514
    @williamsnyder65142 жыл бұрын

    Keep in mind bro 410.20 allows us to use the canopy of a luminaire. I really like your material and we need to make sure the guys learning from us know the true code for the exam.

  • @bananainacup

    @bananainacup

    2 жыл бұрын

    314.16 which is referred to in 410.20 days that the volume needs to be marked and most canopies on fixtures are not marked

  • @williamsnyder6514

    @williamsnyder6514

    2 жыл бұрын

    @@bananainacup typically the AHJ will allow us one 12/2 or one 14/2 for vanity fixtures with large canopies regardless of the box fill calculation

  • @bananainacup

    @bananainacup

    2 жыл бұрын

    @@williamsnyder6514 yeah I mean I’ve never had it fail But it is kinda up to the ahj interpretation

  • @darksaint36

    @darksaint36

    2 жыл бұрын

    I doubt many inspectors do fill calculations or check if the light will have enough room.

  • @Satchmoeddie

    @Satchmoeddie

    2 жыл бұрын

    @@darksaint36 Some do, but very rarely on any residential jobs. The workload is crazy and the doper roper inspectors are never the most experienced inspectors on staff.

  • @jsimanella
    @jsimanella2 жыл бұрын

    As others have stated, you really should mention canopy space. No inspector has ever flagged me for a single 12/3 to a pan. We do it when there's no other reasonable option.

  • @cameronforbes2649

    @cameronforbes2649

    8 ай бұрын

    yeah he's overthinkging something that's already been addressed. as stated elsewhere (Williamsnyder's comment) UL1598 allows luminaires to have less volume than 314.16. Further, 314.16 apples more to junction boxes and conduit bodies where you can actually determine what goes in. bcuz as you know, you wind up having to put a light dead nutz on a truss.

  • @JohnThomas-lq5qp

    @JohnThomas-lq5qp

    5 ай бұрын

    Problem that I read was when a 4" what 1/2" deep pancake is surface mounted a majority.of the cubic inch volume of shallow canopies are taken up by the pancake box. They way it was presented it said that a 4" pancake box counting the connector does not have enough volume for even illegal 14/2 type NM cable to feed a wall mounted luminares. In my area one inspector now only accepts UF cable to feed any outdoor luminares. Said NM cable is not rated for damp locations .

  • @shanesmith8420
    @shanesmith84202 жыл бұрын

    Some light fixtures have a canopy so there's more space therefore legal. However with a blank plate on the box you would be in violation of code

  • @littlehuey5679
    @littlehuey56792 жыл бұрын

    Most inspectors that I have met use the device’s housing as part of the fill calculation because there is almost no situation where you have a flat cover on a pancake box !

  • @cipher1167

    @cipher1167

    2 жыл бұрын

    Yes, that is why they allow them. All light fixtures I’ve installed have space for the wires.

  • @cgschow1971

    @cgschow1971

    3 ай бұрын

    Except for a keyless lampholder.

  • @davidkahler9390
    @davidkahler93902 жыл бұрын

    It's worth mentioning the existence of saddle boxes. I didn't know they existed until recently, and boy are they so much better for this situation.

  • @FishFind3000

    @FishFind3000

    2 жыл бұрын

    Never heard of them but from one quick Google search there pretty sweet.

  • @heronimousbrapson863
    @heronimousbrapson8632 жыл бұрын

    I used pancake boxes on the exterior of my garage, mounting them directly on the surface before the siding was put up. In order to more adequately accomodate the wires of a motion detector controlled light fixture, I was able to use a pancake box extender which screws on to the main pancake box. They are available in many hardware stores.

  • @goodolsparky9386
    @goodolsparky93862 жыл бұрын

    Love this channel! Keep up the great work Dustin!

  • @esl4058
    @esl40582 жыл бұрын

    A stack of pancakes briefly flashed right at the beginning of the video and I appreciated that.

  • @bobfarnum199
    @bobfarnum1992 жыл бұрын

    Thank you for sharing your knowledge, Dustin . Appreciate your channel .

  • @brianc3481

    @brianc3481

    2 жыл бұрын

    He is definitely a great resource that I use to further my understanding and knowledge of the national electoral code and I have no idea where I'd be without him.

  • @chevlinpodhorodeski9814
    @chevlinpodhorodeski98142 жыл бұрын

    Up in Canada 12/2 the bond is only #14 (not that it changes a whole lot) plus the bond doesn't count for box fill either

  • @danielmcdougle6925

    @danielmcdougle6925

    2 жыл бұрын

    Does in USA

  • @jeffhagen4202
    @jeffhagen42022 жыл бұрын

    There are 5/8 pancakes, which have something like 8 cu in. Since most ceilings are 5/8" drywall, they work well there and would allow a 14/3 or 12/2.

  • @chuckjim5921
    @chuckjim59212 жыл бұрын

    Awesome vid as always. Just got done dealing with some of these last week. For 14/2 garage coach lights, they can work fine cause the wire is supported, in most cases, by brick work. Knock the clamps out and realistically you can still get away with 2 cables through the back. My biggest beef with these is seeing them used in stud spaces. Primarily bathrooms for sink fixtures. Been seeing them used due to a vent pipe that is right in the way. No reason to ever have to be forced to use a pancake in a cavity where you can easily fit a bar hanger or cut in box. Wish the plumbing code would reflect this and make plumbers reroute their vent pipes to accommodate electricians.

  • @2point..0
    @2point..02 жыл бұрын

    Appreciate you Dustin, thanks for the teaching!!!

  • @nickesposito3497
    @nickesposito34972 жыл бұрын

    This channel is one of the best electrical education resources next to Mike Holt, keep up the great work

  • @willschultz5452
    @willschultz54522 жыл бұрын

    A electrician friend of mine said " why do they sell them then" he uses them all the time 😂. I only use them if there is no other way.

  • @comingtofull-ageinchrist6736
    @comingtofull-ageinchrist67362 жыл бұрын

    actually, I was thinking about this when I watched you try to stuff the wires into you switch box when you were doing the wireless switches, and a lot of the older boxes that were used were 18 cubit inches. Well, before the 2020, you could fit 3 12/2 Romex cables into a 18 cu in. box. Now, in the 2020, when you have more than 4 equipment grounds, you have to add 1/4 volume allowance for each equipment ground over that, based on the largest equipment ground for that group or circuit. That's where you have to think if you use split a 2 gang box to use for 2 circuits as well. see 314.16 (B)(5) for equipment grounding conductor fill. If you are using a metal box with clamps, it changes the game a little. because a 18 cu. in. box can not receive 3 12/3 in a metal box because of that. There's two clamps and you have to count one based on the largest conductor entering the box. that means you can use 2 12/2 Romex cables or 1 12/2 and 1 12/3. You know, Journeymen I worked with as an apprentice in Oklahoma didn't teach what the code says. I think they were more interested in having someone to crawl in the attic or dig a ditch or drive the ground rod when it had to be done, than to teach them the code, so they could go take the exam and pass it! They would get mad and say I was arguing if I wanted to know why I was doing something a certain way, or I didn't want to do something their way because I had just learned the way that you're supposed to do it according to the NEC. I just wanted to learn, so I could get my license, and it wasn't something I received any help from the Journeymen or contractors on the job. Because they got their license and never cracked the code book after that! For anyone reading this that doesn't have their license, don't wait until you're eligible to take the exam to study. There is so much to learn, so much information in that code book. The most important thing I can think of is to learn how to identify a the main topic of a question and where to locate it in the NEC. Learning calculation and all that is great, but being able to quickly find something. If you're taking the Unlimited Journeyman exam, it's 100 questions, and you have 4.5 hours to complete it, so learning where to find things is important. You have a little over 2 minutes for each question. Your first pass should be to answer what you know and mark the ones you don't know or aren't sure of. second pass should be looking up the questions you didn't know and not taking more than a minute to find them; the ones that take more than a minute, leave marked and come back to it. Save the ones you had a hard time looking up till last; chances are you may see the answer when you are looking up something else, and save your calculations for last. never hit the done button. Sit in front of that computer and go over everything one last time and beware of changing an answer unless the correct answer is on the pages of the code book and you are looking at it. I don't know how many times I've changed an answer that was right Start Early!!!!!!! Don't wait till you are eligible for the exam to study for the exam. That is a pain you will regret! lol

  • @actionjksn
    @actionjksn2 жыл бұрын

    I've used plenty of these, the lights pretty much always have a cavity that will accommodate the wire and connectors. I never see lights that are completely flat at the mounting surface where the wires come out of the back side of the light. I'm sure something like that exists but most lights will work with these boxes. Boxes like this get installed and used safely for decades with no problems. Install a regular box that sticks out until the inspector signs off on it and then switch them out with the pancakes.

  • @Satchmoeddie
    @Satchmoeddie2 жыл бұрын

    How about the domed cover on the fixture? Yeah, that adds volume.

  • @tommycho9068
    @tommycho9068 Жыл бұрын

    Thank you for the very good information about electric codes. Many thanks.

  • @David0lyle
    @David0lyle2 жыл бұрын

    Hmm 🤔 are you allowed to consider the space in the back of the fixture? Most ceiling fans have a pretty generous escutcheon and typically a good size down rod? How about the typical Florence fixture where the termination is in the fixture rather than the box?

  • @Hitman.13.

    @Hitman.13.

    2 жыл бұрын

    I agree with you, except with the ceiling fans portion, those are not rated for ceiling fans.

  • @hunterlobdell1042

    @hunterlobdell1042

    2 жыл бұрын

    Yes

  • @bananainacup

    @bananainacup

    2 жыл бұрын

    @@Hitman.13. they do have fan rated pancakes tho but yes regular pancakes are not fan rated

  • @Hitman.13.

    @Hitman.13.

    2 жыл бұрын

    @@bananainacup Yes sir, funnily enough we call em "Fan cakes" around here lol

  • @xylexut2589

    @xylexut2589

    2 жыл бұрын

    @@Hitman.13. I didn't even pay attention to the rating when I was changing a light fixture to a fan at my mom's house. I just put extra drywall screws where the fan bracket screws would be so that the fan was being held from along the stud instead of the sides so there was no chance for the box to bend or wobble.

  • @BillyD
    @BillyD2 жыл бұрын

    The editing is so good!

  • @jorlando6108
    @jorlando61082 жыл бұрын

    I usually use these when i have to put an exit sign right in the middle above a door and there is a stud there.When you screw it to the stud the sheet rockers cut around it and I haven’t had any issues with inspectors.also the exit sign provides enough space inside to make joints.the pancake box is just there so you have something to attach the machine screws to to hold the sign.That’s why pancake boxes are the same thickness of the sheetrock.

  • @obsoleteprofessor2034
    @obsoleteprofessor20342 жыл бұрын

    I've been using these is my plaster house. I sheetrocked over the plaster which gave me 1/2" depth. I pulled out the old knob and tube and dug out the plaster enough for the romex connector to clear. Fish the romex through enlarged existing holes and screw it over the plaster.

  • @dennywires
    @dennywires2 жыл бұрын

    Great video and content!

  • @heroknaderi
    @heroknaderi Жыл бұрын

    Cool Never noticed that. I see builders use them occatinally for ights and fans.

  • @comingtofull-ageinchrist6736
    @comingtofull-ageinchrist67362 жыл бұрын

    let me say this about the volume fill for equipment grounds separately: 314.16(B)(5) equipment grounds up to 4 can be counted as 1, then a 1/4 volume allowance for each additional not a whole. and 314.16 (B)(2) for clamps if there is one or more, only one volume allowance is required based on the largest conductor entering the box. and you're wrong on the pancake boxes, because the volume of the light fixture or ceiling fan canopy is also added to the volume, and many of the light fixtures and ceiling fans have a volume fill space in them. Vanity lights have volume space etc.

  • @swaterman08
    @swaterman082 жыл бұрын

    The code is assuming we are going to put a flat cover on it? Most light fixtures the cover is a dome, does that add to cubic inches?

  • @cdecoro
    @cdecoro2 жыл бұрын

    Isn’t this missing the point that a typical light fixture has substantial additional volume below the box itself? Effectively that becomes a box extension.

  • @BrentFreyEsq

    @BrentFreyEsq

    2 жыл бұрын

    314.16(A): “The volume of a wiring enclosure (box) shall be the total volume of the assembled sections and, where used, the space provided by plaster rings, domed covers, extension rings, and so forth, **that are marked with their volume** or are made from [standard sized boxes]” Key point, the luminaire has to be **marked** with a volume to add that space. In the real world, they're never marked.

  • @forgetaboutitwillya5702

    @forgetaboutitwillya5702

    2 жыл бұрын

    @@BrentFreyEsq True but at the same time the volume in the fixture can be used even if it's not marked. Just use common sense. You got plenty of room in most fixtures. This guy is completely going overboard.

  • @mojopare8954

    @mojopare8954

    2 жыл бұрын

    @@forgetaboutitwillya5702 Not overboard but precise. The marked box is another refinement that eliminates old stock and promotes new stock. Also increases the demand for licensed and knowledgeable professionals.

  • @forgetaboutitwillya5702

    @forgetaboutitwillya5702

    2 жыл бұрын

    @@mojopare8954 So you're going base your calculate of wires completely on the cubic inch space of a pancake and ignore the fact that most light fixtures have canopies that in most cases have 3 or 4 times the volume of a pancake. Just cause the fixture doesn't have a cubic inch measurement. I guess common sense eludes people now a days. SMH.

  • @dougfoster445

    @dougfoster445

    2 жыл бұрын

    @@forgetaboutitwillya5702 Well, code is king. What's common sense to one person is uncommon sense for the next. Each canopy is a different size.

  • @chrisathomas1
    @chrisathomas12 жыл бұрын

    remember most pancake box's are used to hold a fixture and the wiring. The volume is increased in the fixture mounting area. If you use the pancake box only for a j box with a blank cover then it becomes a code violation.

  • @allenandtammyterwilliger1201
    @allenandtammyterwilliger12012 жыл бұрын

    I really appreciate your channel. As some folks mentioned that you can use the canopy as fill, but it is my understanding that you cannot technically use it because the fill isn't stamped on the canopy. I have also never had an inspector fail it

  • @timh2870
    @timh28702 жыл бұрын

    14 AWG switch leg when the rest of the circuit is 12 AWG? See 240.4(D)(3). The only place I'll use 14 AWG on a 20 amp circuit (and AFAIK the only place they're allowed) is small jumpers that stay within a single box.

  • @TylerSmith-kt8rk
    @TylerSmith-kt8rk2 жыл бұрын

    Great! Now I want pancakes lol

  • @SeekingTheLoveThatGodMeans7648
    @SeekingTheLoveThatGodMeans76482 жыл бұрын

    I once had a house where I DIY'ed a lot of stuff needing county permits/inspections. I never got grief over pancake boxes, whose use expects a canopy, not a flat cover. So how much space is in the canopy? Even if the canopy is not explicitly marked, if a marked extension ring attached to the pancake can be covered by that canopy with the edge of the canopy being flush to the surface, then the canopy has at least as much space as the ring and the ring ought to satisfy a finicky inspector. For a rough-in inspection I don't know why the inspector should care about the canopy for it hasn't been installed! At worst it should be worth a note "Luminaire canopy must/will be rated at X cubic inches or more." But again I'm talking about reasonable people. Pancakes aren't used out of the sheer joy of them (if there's space, a deeper box is better, for one day one may want to wire more into the system) but because they can be attached directly to a surface such as a beam above the ceiling.

  • @th-bk2qs
    @th-bk2qs2 жыл бұрын

    We use them for sconce lights. Run one 14/2 per sconce and send them to the J. I'm almost a year in so it's nice to see another view of why.

  • @renedelpech214
    @renedelpech2142 жыл бұрын

    Dustin you are a top master. You should be teaching at technical school. I am much confident when I am working on electric devices

  • @codycurry91
    @codycurry912 жыл бұрын

    I’ve had inspectors ok pancakes and fan rated pancakes because the canopies give your conductors more room.

  • @pya102
    @pya1022 жыл бұрын

    Do you also have to account for the fixture wires in those calculations?

  • @davidicousgregorian
    @davidicousgregorian2 жыл бұрын

    Does the depth of attached wire fill area of fixture(1/2 in depth or more as example) connected to pancake box count as adding wire fill cu in area space if wire splice area of metal area of fixture is protected from exterior sources if i add a metal wire area of fixture is enclosed and directly attached to pancake essentially adding wire fill area to the pancake box ?

  • @ballisticbuddha
    @ballisticbuddha2 жыл бұрын

    This is why saddle boxes are superior to pancakes. The extra volume you get by wrapping the box around the joist makes them actually usable to code and can even allow for a junction on the circuit if you need it. I just replaced a pancake in my kitchen ceiling yesterday for a saddle box with a 12.5 in³ volume. Even with the integrated clamps it's still pretty roomy with 2 Romex coming into the box, especially since they're non metallic and don't need a ground screw taking up precious space.

  • @phi5head

    @phi5head

    2 жыл бұрын

    Saddle boxes only work if you need your box exactly centered on the joist. That's usually not the case.

  • @aaronlee9651

    @aaronlee9651

    2 жыл бұрын

    For commercial won't always work like that

  • @markxx90
    @markxx902 жыл бұрын

    I’m surprised you didn’t mention about available canopy space of the light

  • @jfromtn7410
    @jfromtn7410 Жыл бұрын

    so say from a junction box with 12 /2 wire on a 20 amp circuit could I run 14 /2 off the 12/2 to a light fixture if I step down to a 15 amp breaker in 1 of these pancake and be up to code?

  • @martinserena9314
    @martinserena93142 жыл бұрын

    I noticed that fan support pancake boxes are identified as 1/2" deep, but their overall depth is closer to 5/8" deep. When installing the box on a centered joist with 1/2" drywall at the ceiling, the box sits outside of the drywall by about 1/8". I have been creating a 1/8" deep notch in the joist to flush the pancake box to meet the code section on flush mounting boxes. Is this the best method for a workmanlike install?

  • @ericstocker6902
    @ericstocker69022 жыл бұрын

    At 10:50 in video, you talked about using 12 ga combined with 14 ga switch leg. Is that to code? The 14 ga wire would not be protected with a 20a breaker.

  • @zacharybob4336

    @zacharybob4336

    2 жыл бұрын

    Tap conductor rules, check out 210.19. It's a more difficult set of codes to understand so most resi guys just stick with the small conductor rule 240.4(D).

  • @ericstocker6902

    @ericstocker6902

    2 жыл бұрын

    @@zacharybob4336 I don't have a code book to look it up.

  • @billhandymanbill2775

    @billhandymanbill2775

    2 жыл бұрын

    I agree with Eric about not using 14 gauge switch leg on a a 12 gauge/20 amp circuit.

  • @cameroncrider6970
    @cameroncrider69702 жыл бұрын

    I work for a new build residential company. If we use a pancake, we do our best so it only has one run of wire in it. So many instances of the dry wallers cutting our wire. Then we loop it to pull extra if needed.

  • @davidicousgregorian

    @davidicousgregorian

    2 жыл бұрын

    fixture still needs 2 wires tho a hot and nuetral so 1 wire is not possible since nuetral can be energized on return it counts as wire 2 and fixture needs nuetral

  • @cameroncrider6970

    @cameroncrider6970

    2 жыл бұрын

    @@davidicousgregorian one run of wire being a 14/2 leg from the switch for example.

  • @codegmaster2610
    @codegmaster2610 Жыл бұрын

    I'm a new apprentice in canada, so I may be wrong or nec may handel this differently, but I was taught to not count the bonding wire since it doesn't always carry current as the hot and natural do. Is there a reason you count 3 conductors for 14/2 or 12/2

  • @danieldryden542
    @danieldryden5422 жыл бұрын

    I was thinking most times the light canopy adds room to the over all space in the enclosure. We almost never put a round flat plate on a pancake box.

  • @Chris_In_Texas
    @Chris_In_Texas2 жыл бұрын

    However throw out cable loading, just thing ok 314.27(c) states that all boxes used in habitable rooms in ceilings shall be rated for ceiling fans with that stamped into the box. Also goes on to state that you have to use #10 screws. Also 314.27(a)(1) states that for vertical wall use all boxes must identified on what weight is supports if less than 50 lbs. They can be used if marked accordingly.

  • @cashisgreen6383
    @cashisgreen63832 жыл бұрын

    Can you please do a video why you don’t like being a electrician and then a video why you like being a electrician. Thanks, great work and video.

  • @charliefarrell4888
    @charliefarrell488810 ай бұрын

    I’ve chosen a pancake box for a ceiling fixture, in order to hang a vanity light, centered. To do so, I have to attach to a stud, that’s why I’m choosing this box option. Is that typically within code for a single vanity light fixture ?

  • @johnfilce9236
    @johnfilce92362 жыл бұрын

    These calcs assume a flat cover on the box, right?

  • @Valeij221
    @Valeij2212 жыл бұрын

    I had a water loss underneath a kitchen sink. Basically a flood from a broken pipe under the sink. Went in the house and opened up the cabinet doors… the fridge, range, garbage disposal, and a light socket for the “microwave” we’re all hard wired with 1 wire nut to each line, and there was no lid to the pancake. I hit the main breaker and still wanted to cry the whole time I unwired that shit.

  • @deepinthought469
    @deepinthought4692 жыл бұрын

    Great video. Suggest a video on voltage drop. A footnote (NEC 210-19 FPN No. 4) in the National Electrical Code states that a voltage drop of 5% at the furthest receptacle in a branch wiring circuit is acceptable for normal efficiency. The Fine Print Notes to 210.19(A), 215.2(A)(4), 230.31(C), and 310.15(A)(1) that you adjust for voltage drop when sizing conductors. It's important for you to remember that Fine Print Notes are recommendations, not requirements [90.5(C)]. Do you (over)size your "home runs"? Do you use the limits of 32ft 14-2 for 1500W 15A breaker, 47ft 12-2 for 2KW 20A breaker on 12-2, etc.? Would love to see your response video.

  • @mannymota2871
    @mannymota28712 жыл бұрын

    I was using those today, for pendant lights

  • @phi5head

    @phi5head

    2 жыл бұрын

    Same. Exact center of the island countertop fell directly on a joist and I had no choice. I use them all the time. There's plenty of room for wire when the additional space from the luminaire's canopy is taken into consideration.

  • @theabandonedpeople1961
    @theabandonedpeople19612 жыл бұрын

    Anything over 4 grounds you add them as a half I believe now for every one after

  • @martinhumerickhouse8319
    @martinhumerickhouse83192 жыл бұрын

    This is one code that has had me always thinking about everyone saying canopy counts as “space”. I think I even commented somewhere that it does and now stand corrected. 410.20 states that canopies and boxes shall supply enough space for LUMINARIES CONDUCTORS! Not branch circuit conductors. Second it gives reference to 314.16. So 314.16(B)(1) exception states. That fixture wires or conductors enter from a domed luminaire or similar canopy shall be omitted ( short version) both times talking about the fixture wires and not the branch circuit Point is canopy does not add on to box fill simply takes into an account for fixture/conductor fill adding to an outlet

  • @markchidester6239
    @markchidester62392 жыл бұрын

    Logically, total inches of wire within the box is what should be used for the calculation.

  • @nogoa42
    @nogoa422 жыл бұрын

    "Boxes and conduit bodies shall be of sufficient size to provide free space for all enclosed conductors." there is no expectation that all conductors in a luminaire mounting box will be enclosed in the box. These boxes are not outlet, junction, or device boxes and are not expected to be covered in a way that all conductors will be encased within the confines of it.

  • @RB-xv4si

    @RB-xv4si

    2 жыл бұрын

    I’m curious how you convinced yourself that a pancake box does not fit within the definition of an outlet. It certainly does. Sounds to me like a massive copout for someone who realizes they’ve been Fing this up for years.

  • @michaelmassetti4068
    @michaelmassetti40682 жыл бұрын

    Ok. Great video. I think most pancakes are only good for eating anyway. Gonna watch your video on conduit fill.

  • @aaronlee9651
    @aaronlee96512 жыл бұрын

    A fix...j box above and do pigtails coming in to pancake. Instead of having two 12 2 in these box. Had to solve this yesterday at my job

  • @ddelano7408
    @ddelano74082 жыл бұрын

    Is there some kind of a bushing that goes into the knockout hole so the cable won't chafe on the box? If so doesn't that have to be counted also?

  • @harveylong5878

    @harveylong5878

    2 жыл бұрын

    some come with a plastic bushing that acts as a clamp or just use a regular romex connector

  • @stevenpeck5949
    @stevenpeck59492 жыл бұрын

    What if the pancake is used for structural support and the fixture wires, 18/3, run through the box, though the beam and into a larger box for connection to power, 14/3?

  • @drewc3651
    @drewc36512 жыл бұрын

    I'm licensed in Va. They don't allow any metal boxes in ceilings any more in residential??

  • @nhzxboi
    @nhzxboi2 жыл бұрын

    Made for 14/2AWG(W/G, of course) connected to 18AWG stranded connection. Yet, the 'box' is not a closed box by itself. Perhaps there is some volume added by the cover?...the fixture? I'm not sure I'm going to buy this hook, line and sinker. I don't refute. But, I question tossing in the multiple 12AWG connections. Of course, the thing isn't meant for a multiple connection box of 12 AWG. Assuming a flat cover? If so, sure that would be lame.

  • @TheSolo727
    @TheSolo7272 жыл бұрын

    Does adding a box extension make a difference?

  • @shanesmith8420
    @shanesmith84202 жыл бұрын

    Again it may also end up being up to the authority having jurisdiction. In my experience let's say vanity lights with a vent pipe dead center of the sink. So a Hollywood light would have space for the conductor. I actually had a service call on a new house in Austin where there was water coming out of the powder room light downstairs. When I got there with the homeowner and plumber and superintendent . I took down the fixture . viola some bozo screwed the fixture to the three inch vent pipe thus the leak. The plumber cuts out the damaged section of pipe and there are dozens of condoms caught on the screws that went into the pipe. So the plumber drops the pipe out in the garage and we all had a laugh. That was until the homeowner came in and asked what are those. The plumber says those are weenie boots prophylactics..The homeowner then says I don't use those things. Uh ohh!! Guy got physically ill. Because it was only his wife and his 13 yr old daughter living with him. Really don't know what happened after that but the guy was immediately on his phone to his wife and his daughters school. True story

  • @knighthonor44

    @knighthonor44

    2 жыл бұрын

    Damn

  • @bananainacup

    @bananainacup

    2 жыл бұрын

    This was a wild fucking ride that I did not expect to go on when I started reading your comment

  • @HBSuccess

    @HBSuccess

    2 жыл бұрын

    Ok you just beat any story I can tell after 50 yrs in the feild 😂😂

  • @inecronomicsi4285
    @inecronomicsi428511 ай бұрын

    BRO My builder LOVES pancake boxes with "slim fit" canopy pendant lights 😅 Obviously the pancake boxes are a result of the beams but typically we have 3x pendants for the eating bars and often 2/3 will be pancake boxes. I have said to my boss so many times that theres no way pancake box with a slim canopy is legal 🤷‍♂️🙃

  • @oldtimefarmboy617
    @oldtimefarmboy6172 жыл бұрын

    Can you use the pancake just to mount the light and then run its wires from the pancake to a proper size junction box to connect all the wires together? Maybe they can make a larger diameter pancake box so there is more internal volume. Maybe they can make a pancake that "saddles" the joist so that the extra volume going up each side of the joist can be used to push connectors into.

  • @vince6829
    @vince6829 Жыл бұрын

    Based on the comments, it sounds like the canopy of a fixture increases the total box fill making it ok in the end to use a pancake in wiring a fixture with 14-2. Correct? Thanks for sharing your knowledge.

  • @feyrband
    @feyrband2 жыл бұрын

    Does my pancake violate code if there's an extension cord hanging out of it with a lamp socket on the end? How far back would we have to go? (I have cloth wrapped wiring)

  • @rupe53

    @rupe53

    2 жыл бұрын

    your whole system predates code so making changes will be an issue, unless it's all redone back to the panel, which will not meet today's code anyway.

  • @donphillips5957

    @donphillips5957

    2 жыл бұрын

    Residential code generally allows that work inside the wall met code when installed, so it's ok(ish). The extension cord out of the box raises questions, pancakes are almost exclusively for mounting luminaries.

  • @rupe53

    @rupe53

    2 жыл бұрын

    @@donphillips5957 ... back in the day that cord hanging out of a box was usually called a laundry drop. They were used for both lights and a place to plug in appliances. (washing machines) They were code at the time, although pretty shaky by todays standards, even without being 100 years old and having worn insulation.

  • @jonesconrad1
    @jonesconrad12 жыл бұрын

    I'm in the UK so I don't know is this a federal or state code you are referring to ?

  • @waiting4aliens
    @waiting4aliens2 жыл бұрын

    How can you use a metal box without a cable clamp of some sort? Interior or exterior?

  • @sterlingferguson7234
    @sterlingferguson72342 жыл бұрын

    Interesting

  • @justinmanship5431
    @justinmanship5431 Жыл бұрын

    Would the manufacturer of the pancake with the clamps not be calculating for the volume used by the clamps already?

  • @colinstu
    @colinstu2 жыл бұрын

    314.15(B)(1) Exception and 314.15(B)(5)... But yeah, 6cu is really minimum usable...

  • @blh3741
    @blh37412 жыл бұрын

    I was nailed for this once and the fixture's canopy wouldn't fly. So... out comes a saddle box and she really wanted to not allow it just due to the shallow depth in the center. My only comeback was "why would they allow these to be sold for 2 circuit ceiling fans? She then wouldn't allow me to install it before she signed off, making me call for a re-inspection...grrrrr. The next inspector just shook his head and muttered something under his breath.

  • @hiseminencetheholymacdiarmada
    @hiseminencetheholymacdiarmada3 күн бұрын

    I want to use a 4” x 1/2” deep pancake to mount a ring floodlight camera. I want to surface mount the pancake on a stucco wall.

  • @yeroca
    @yeroca2 жыл бұрын

    If you're trying to use one of these as a junction box, wouldn't that be a minimum of five conductors going in? (2 hots, 2 neutrals, and 2 equipment grounding conductors that count as 1)

  • @mr.g937

    @mr.g937

    2 жыл бұрын

    Yes...and it's not to code, although many people do it (and I've done it).

  • @wdkofc6989
    @wdkofc69892 жыл бұрын

    I'm confused. You were correct on what you said about these boxes but where I'm fuzzy is don't you have to count the wires you are connecting to? I don't see a lot of lights with terminals on them.

  • @boulderboy245

    @boulderboy245

    2 жыл бұрын

    Check the exception in 314.16 B 1 conductor fill.

  • @shoelessone
    @shoelessone Жыл бұрын

    Question: don't you need a clamp in there always? Wouldn't you need to de-rate the 6"?

  • @joelboutier1736
    @joelboutier17362 жыл бұрын

    My understanding or box fill was to count CURRENT CARRYING CONDUCTORS. The ground is not carrying current thus would not be counted towards box fill. Line & neutral conductors would count only so for 12/2 Romex, the box fill calculation would only be 2.25 + 2.25 which is still too much for the 3" pancake. BUT 14/2 Romex is only 2 + 2 so it would be acceptable to run 14/2 Romex to a 3" pancake. Am I wrong about current carrying conductors? It's been a while since my apprenticeship program.

  • @josephknapick5307

    @josephknapick5307

    2 жыл бұрын

    314.16.(B)(5) of the 2020 code requires counting of EGCs as described in the video...1 thru 4 EGCs = 1 volume allowance in total... EGCs 5 and above each count as an additonal 1/4 volume allowance.

  • @mr.g937

    @mr.g937

    2 жыл бұрын

    Even before 2020 you still had 1 conductor allowance for the ground. 2020 just stepped it up for >4

  • @maximostov5823
    @maximostov58232 жыл бұрын

    Pancake boxes will work with cables that does not have wire-type EGC like BX cable or EMT

  • @SkaggsFamily
    @SkaggsFamily2 жыл бұрын

    Well, you've helped me uncover YET ANOTHER code violation in my house (2x 14/2 plus fixture wires and wirenuts stuffed into a shallow fiberglass pancake). I have no idea how this place passed inspection 22 years ago (very basic stuff too). I'm finding these things during repair of what always turn out to be sloppy installation (multiple arcing/crackling switches because of long conductor strips/shorts, several flickering light fixtures with bad wirenut technique, mis-wired smoke detector travellers left unconnected, multiple GFCI outlets on one circuit, and more...).

  • @RB-xv4si

    @RB-xv4si

    2 жыл бұрын

    I’ve been trying to understand the pervasive shit dick work constantly done in our industry since I started 7 years ago. The only thing I can come up with is (because I see it all the time) that as soon as someone is good/competent enough to do really good work, they often have opportunities to make better money running other guys (the ones that don’t know much, of course) and so that’s what they end up doing. And we end up with this continuous mega shit dick work because of it. The foremen, don’t have time to baby and check on their workers and the inspectors don’t care enough or have time to check everything with the time they have allotted for the inspection. It’s such a problem that my company have an entire QC department (I work as QC in the field).

  • @wim0104

    @wim0104

    2 жыл бұрын

    remodeling companies (kitchen & bathroom) get away with scary "electrical" work.

  • @justink7269

    @justink7269

    2 жыл бұрын

    If you're using metal rather than plastic, allow yourself a little more because of course its much safer

  • @scotttribout1150
    @scotttribout11502 жыл бұрын

    Let let pose this quandary. You are using a pancake in a surface mount application for a wall mount exterior light. Or a ceiling mount fan. (Yes there are fan pans). The room allotted with the fixture should also play into the fill calculations. A lot of wall fixtures and some fans have a "shroud" that provides more than enough space to comfortably make connections. In theory it would work. What's everyones opinions?

  • @rupe53

    @rupe53

    2 жыл бұрын

    these boxes are not rated for exterior use.

  • @mccarterjg
    @mccarterjg2 жыл бұрын

    I don't know I just calculated out this volume of a 3-in cylinder that's half inch thick is 14 cubic inches, subtract the wall diameters and then the clamps is probably where that 4 cubic inch came from, I would think that you only have to subtract from that size classification when you add extra clamps not something from the factory

  • @jeffreyrossman1083
    @jeffreyrossman10832 жыл бұрын

    What about conduit grounded circuits? Couldn’t a 3” pancake work if you’re only running hot and neutral in 14 awg with the conduit as your ground?

  • @rupe53

    @rupe53

    2 жыл бұрын

    are you talking about a light fixture with a pull-chain from 1950? Let's get real. A half inch box doesn't have enough room to connect a half inch conduit.

  • @nsmith0723
    @nsmith07232 жыл бұрын

    I hate metal junction boxes, every time I've come across a serious issue they are involved. One time the aluminium siding ended up getting electrified through one and you'd get a little shock off of it. Now each time it was wired improperly, but it wouldnt have anywhere to short with a plastic box

  • @benpedolsky9214
    @benpedolsky92142 жыл бұрын

    Notch the framing 1” and use octagon boxes. Unless it’s in the ceiling I suppose

  • @dougfoster445

    @dougfoster445

    2 жыл бұрын

    You're not always putting them in framing. often times you are mounting them on exterior walls with stucco surface.

  • @barryomahony4983

    @barryomahony4983

    2 жыл бұрын

    Code doesn't allow notching in the middle third of a joist

  • @mr.g937

    @mr.g937

    2 жыл бұрын

    Notching the framing is a good way to destroy the structural integrity of your roofing system. Never notch!

  • @ndowroccus4168
    @ndowroccus41682 жыл бұрын

    Pancakes, the electricians paradox…I’m sure this will be addressed in the future code books (ya know, once the pancake manufacturers pay-off the board of code monkeys, much like arc-faults).

  • @daleatkin8927
    @daleatkin89272 жыл бұрын

    So I see a lot of comments re: is this really a code violation, can we count the space in the light fixture itself etc, etc. I have a better question for all of you: given that the majority of code exists for a reason, sometimes to save dumb people from themselves, sometimes for serious safety issues, what would you do if you found, in your own home, that the guy before you had used one in a code breaking way, but had been passed by an inspector. What about a client home?

  • @johnchristmas7522
    @johnchristmas75222 жыл бұрын

    In the UK you cant buy "pancakes"! First time I've heard of these-what are they used for? We would be required by code to fit a deep box, recessed into what ever. if its Plaster board, we have special plastic boxes made with rear fixing. That is achieved by sprung loaded 'ears' fixed to the box, which are squeezed inwards inside the box and then expand once past the plaster board thickness. The box is held in place by the slightly larger lid, or face of the switch or receptacle. Light fittings that hang by flex are accommodated by a circular surface plastic box, which has a base with a lid. The lid has deep sides(approx 5/8") with an internal thread that screws onto the base side. The base has a fixed ground terminal and an array of recessed terminals giving connections for the feed/switch line and neutral cable together with terminals for the flex. The flex is wired through the lids centre hole (just the size of the flex) then screwed up to the base. all connections hidden!

  • @wmcomprev
    @wmcomprev2 жыл бұрын

    Question: Most boxes have outlets or switches put in them. With a pancake, you're attaching a device that doesn't go into the box. In fact, in most cases, you're attaching a device with a dome on it, giving extra space for the wires. Are there any allowances for any of that?

  • @remodz6385

    @remodz6385

    2 жыл бұрын

    Yes and no. During the inspection phase, you usually don’t have any fixture, it’s just the box with the wires coming in. So that is all the inspector has to go off. But when installing the fixture, you CAN take into account the fixture space itself as well. But you can’t pass inspection to get to that point lol. It’s a catch 22.

  • @hankkline7300

    @hankkline7300

    2 жыл бұрын

    @@remodz6385 They do make blank covers for pancakes that have a built in dome in them. that would allow the extra volume to make the inspector happy.

  • @FishFind3000
    @FishFind30002 жыл бұрын

    The different thickness pancakes are for different drywall thickness

  • @GS-lh2nx
    @GS-lh2nx2 жыл бұрын

    2 things. I thought the grounding conductor counted as less? And if you run a switch leg of 14 off of a 12 do you have to derate the circuit to a 15 amp circuit then? Just trying to learn and I don't have a code book to cite. Thx for the videos and info, they are always well done.

  • @ranger178

    @ranger178

    2 жыл бұрын

    I believe it follows same logic as 15 amp outlets on a 20 amp circuit you can't put more than 15 amps through that particular piece of wire because its going to 1 dedicated fixture

  • @donphillips5957

    @donphillips5957

    2 жыл бұрын

    Older code allowed 14g for a 20A circuit (my apartment), but the wires had to go through the walls, you would derate the wire ampacity if it went through the attic because of heat. Complicated, so they have just made it 12 for 20A.

  • @rogerholland98
    @rogerholland982 жыл бұрын

    Must of the time I have seen pancakes used is to mount a light fixture. Can we not add the volume of the fixture enclosure in our calculation?

  • @barryomahony4983

    @barryomahony4983

    2 жыл бұрын

    If the fixture has a volume marked on it, yes.

  • @krich106
    @krich1062 жыл бұрын

    Man my last boss, would use nothing but pancakes... Only time I'd use something else, if the light was midpsan between joists. He even made me use plastic pancakes for ceiling fans. Such a pain the rear! Easier for rough-in, blows at trim-out. Let alone Id rather do metal for fans.

  • @peterohmart5954
    @peterohmart59542 жыл бұрын

    Do you have to add a percentage for a rolex connector for that pancake?

  • @aaronlee9651

    @aaronlee9651

    2 жыл бұрын

    Good ol Rolex connect kinda pricey

  • @Justanotherwhiteguyyabish
    @Justanotherwhiteguyyabish2 жыл бұрын

    We run all our lighting and outlets in 14/2 unless it’s code to be on 20 amp circuit

  • @punkboyblue
    @punkboyblue2 жыл бұрын

    3:00 I'm a little confused at this grounds thing, would it mean 5=2, or 5=5? 6=3, or 6=6? etc

  • @Tojso09

    @Tojso09

    2 жыл бұрын

    According to the 2020 NEC code, 4 grounds or fewer total is 1 volume allowance (based on the size of the largest conductor in the box). Each ground greater than 4 is counted as 1/4 of a volume allowance. so, 5 grounds total is 1.25 volume allowances. 6 grounds total is 1.5 volume allowances.

  • @Bremend
    @Bremend2 жыл бұрын

    Why are you running 12/2 to lights?

  • @MagneticPerturbation
    @MagneticPerturbation2 жыл бұрын

    Alright. This is all technically accurate which is the point. All the comments noting the inclusion of canopy space as a factor are relying on the authority having jurisdiction and their acceptance of that interpretation/exception. The NFPA panel creating NFPA 70 should take this up for the 2023 code or asap just to codify the exception or otherwise clarify.