  • @keithharrington8715
    @keithharrington8715 Жыл бұрын

    All, please remember that there are several reasons to "derate" or lower the ampacity or current carrying ability of wires. Ambient temperature is listed in section 310 of the NEC. Yes, your attic or just laying in insulation may put you into this section. It might be smart to oversize your feeder wires to be safe.

  • @vaughnmanagan2740
    @vaughnmanagan2740 Жыл бұрын

    Awesome video. Brevity is the sole of wit! Exactly what I was looking for.

  • @jonbraddock5545
    @jonbraddock5545 Жыл бұрын

    Have a link to that upcoming video? Cant seem to find it on your channel.

  • @victornaja7927
    @victornaja7927 Жыл бұрын

    for the 100 amp box what size copper would i use. thank you fyi from main panel to shop its about 60 feet.

  • @mcurtis13
    @mcurtis133 жыл бұрын

    Nice not 30mins for some basic info. Awesome!

  • @heroknaderi
    @heroknaderi3 жыл бұрын

    Sir thank you so much for sharing these tips I’m installing a few in my house and now I can use your tips to get them cheaper than you would at homedeapot

  • @electricianhub86

    @electricianhub86

    3 жыл бұрын

    You got it bro! Thank you for your support! Let's get to it!!!

  • @mikeymiranda859
    @mikeymiranda8597 ай бұрын

    Aye pro-tip, what gauge was your SEC Cabel for your 100amp? Thanks

  • @throughoureyes5160
    @throughoureyes51602 жыл бұрын

    So heres what we have going on. We have a main pole that has 200 amp service to it. We have a shed that is about 350 to 400 feet away and we'd like to install a sub panel to feed an A.C. and a fridge. I think I need a 50 amp breaker at the main box then run #6 UF wire to the sub panel which will have two 15 amp breakers, one to feed an outlet for the A.C. and one to feed the outlet for the fridge. Does this sound like the right set up? Also would I need to worry about voltage drop or would this set up enable The A.C. and fridge to run without fault even with voltage drop. I have literally just started to learn about all this in the last week. Treat me like a toddler when answering please. haha

  • @kurthaueter7653
    @kurthaueter76532 жыл бұрын

    I wish I could buy at those prices today!

  • @eliaschico7781
    @eliaschico7781 Жыл бұрын

    Helo , I want to put a 100amp sub panel, 100 feet away, what size cable should I use?

  • @randellentz836
    @randellentz836 Жыл бұрын

    SER cable is not Direct burial, and cannot be run underground in conduit.

  • @101realtor
    @101realtor2 жыл бұрын

    Reading a bit around the net. This cable is rated at 90 degrees to get that amp rating correct? From what I’m reading, most terminals are rated at 75 degrees which brings the max amp rating down allowed down. Is that correct?

  • @keithharrington8715

    @keithharrington8715

    Жыл бұрын

    Actually, nec not in front of me but section 110.14, I think, talks about terminal connections..... PS. Please no grief if the 100 Amp limit is inside 60 degrees or 75 degrees.

  • @edwincastaneyra2220
    @edwincastaneyra22202 жыл бұрын

    Do we have to install ground rods for the subpanel if we install it in the basement in the same house...?

  • @electricianhub86

    @electricianhub86

    2 жыл бұрын

    Great question, you'll never install more ground rods at sub panels in the same structure according to the NEC definitely work with your electrical inspector.

  • @wildwoodtop
    @wildwoodtop2 жыл бұрын

    Can I run a 60 amp sub panel off a 100 amp main panel (How big of a subpanel can I install off a 100 amp service)

  • @electricianhub86

    @electricianhub86

    2 жыл бұрын

    kzread.info/dash/bejne/Z5il0qaqgcyqmqg.html You will have to do a load calculation

  • @SquirrelsForAll
    @SquirrelsForAll3 жыл бұрын

    Man, wish you were in Orange County, CA!

  • @electricianhub86

    @electricianhub86

    3 жыл бұрын

    Me too brother

  • @jacksonwarner4604
    @jacksonwarner46043 жыл бұрын

    Unless you buy it from me....I can move some numbers around on the computer haha. Sick info tip on the 90 amp breaker.

  • @electricianhub86

    @electricianhub86

    3 жыл бұрын

    Great question! Yes it's going to be sized based off of table 250. 122 (C)(1) and just classified as a bonding jumper. Page 119 of the 2017 NEC!

  • @electricianhub86

    @electricianhub86

    3 жыл бұрын

    Love it!!

  • @danielb2060
    @danielb20602 жыл бұрын

    Can that cable be buried in conduit for a out building as it is in your hand?

  • @SquirrelsForAll

    @SquirrelsForAll

    2 жыл бұрын

    No, this wire cannot be buried as-is and cannot be buried even in conduit. However, it can be placed within conduit above ground.

  • @stanleykania7184
    @stanleykania7184 Жыл бұрын

    Still grinding here..

  • @JonoFinley
    @JonoFinley2 жыл бұрын

    Doesn’t a feeder to a sub panel get the 83% 310.15(B)(7)(2) thing? I’m trying to get 100a out of a feeder that’s AL #2 SER. Isn’t it good for 100a?

  • @electricianhub86

    @electricianhub86

    2 жыл бұрын

    Great question, has to serve the entire main structure

  • @constantinstartun4688
    @constantinstartun46883 жыл бұрын

    Gret tip! What's the actual size of the wire?

  • @electricianhub86

    @electricianhub86

    3 жыл бұрын

    2 awg aluminum

  • @beckyschwantes5287

    @beckyschwantes5287

    3 жыл бұрын

    @@electricianhub86 could you land a 1/1/1/3 ser on a 100amp breaker safely?

  • @SquirrelsForAll

    @SquirrelsForAll

    2 жыл бұрын

    @@beckyschwantes5287 1/0-1/0-1/0-2 Gray Stranded AL SER Cable ia good for 100 amp but watch the length of the install.

  • @spindctr1
    @spindctr13 жыл бұрын

    Go Vols

  • @electricianhub86

    @electricianhub86

    3 жыл бұрын

    Let's get to it!

  • @davidkettell5726
    @davidkettell57263 жыл бұрын

    its a buck fifty at home depot ?

  • @electricianhub86

    @electricianhub86

    3 жыл бұрын

    Not sure haven't checked recently

  • @keving1774
    @keving17742 жыл бұрын

    That's gotta be aluminum

  • @fredastaire6156
    @fredastaire61562 жыл бұрын

    What gauge wire is that? Can somebody help me out?

  • @electricianhub86

    @electricianhub86

    2 жыл бұрын

    Typically 2-2-2-4

  • @DryUrEyesM8

    @DryUrEyesM8

    Жыл бұрын

    @@electricianhub86 Is 1-1-1-3 fine to land on a 100 amp feeder?

  • @Emma-ol7kf
    @Emma-ol7kf4 ай бұрын

    3 years of inflation

  • @Jack.of.all.learning
    @Jack.of.all.learning2 жыл бұрын

    Efficient communicator

  • @electricianhub86

    @electricianhub86

    2 жыл бұрын

    thank you!!