Sub Panels Explained - Why are neutral and ground separated?

Sub Panels Explained Get an exclusive Surfshark deal! Enter promo code ENGINEERINGMINDSET for an extra 3 months free at ➡️ surfshark.deals/engineeringmi...
How do sub panels work, how are sub panels wired, why are neutral and ground separated, what happens during a ground fault, what happens when we lose a neutral wire, what happens if the sub panels is incorrectly wired. All this and so much more covered in this video.
👉 👉👉 Electronics design software I use ➡️ www.altium.com/asp/the-engine...
Learn more here: theengineeringmindset.com/sub...
⚡🛠️ TOOLS YOU NEED 🛠️⚡
*******************************
Get this electronics book ➡️ amzn.to/41cCJPk
Professional Multimeter -➡️ amzn.to/3xu2Vaw
Good multimeter -➡️ amzn.to/3xrbuTd
Professional clamp meter ➡️ amzn.to/4140FnK
Good Clamp meter ➡️ amzn.to/3xqt2is
Outlet tester ➡️- amzn.to/3kavg2l
Energy monitoring plug ➡️ amzn.to/3SkfPl7
Battery tester -➡️ amzn.to/3S3fHWI
Basic electronics ➡️ kit amzn.to/3xuLiqS
👋 SOCIALISE WITH US 👋
*******************************
👉FACEBOOK: / theengineeringmindset
👉TWITTER: / theengmindset
👉INSTAGRAM: / engineeringmindset
👉WEBSITE: Http://TheEngineeringMindset.com
👀 Links - MUST WATCH!! 👀
*******************************
⚡ELECTRICAL ENGINEERING⚡
👉How electricity works: • How ELECTRICITY works ...
👉Three Phase Electricity: • How Three Phase Electr...
👉How Inverters work: • How Inverters Work - W...
👉How TRANSFORMER works: • How does a Transformer...
👉How 3 Phase electricity works: • How Three Phase Electr...
👉How Induction motor works: • How does an Induction ...
👉What is a KWH: • What is a kWh - kilowa...
👉How induction motor works: • How does an Induction ...
❄️ CHILLER ENGINEERING ❄️
👉Chiller Efficiency improvements: • Chiller Efficiency Imp...
👉Chilled water schematics: • Chilled Water Schemati...
👉Chiller crash course: • Essential Chiller Term...
👉Chiller types: • Chiller Types and Appl...
👉Chillers/AHU/RTU: • How Chiller, AHU, RTU ...
👉Water cooled chiller Part1: • Chiller Basics - How t...
👉Water cooled chiller Part2: • Chiller Basics - How t...
👉Water cooled chiller advanced: • How Chiller works - De...
👉Air cooled chiller: • Absorption Chiller, Ho...
👉Absorption Chiller : • Air Cooled Chiller - ...
👉Chiller/Cooling tower/AHU: • How a Chiller, Cooling...
👉Chiller flow rate: • Chiller flow rate meas...
👉Chiller fault troubleshooting: • Chiller faults - troub...
👉Chiller COP calculation: • Chiller Efficiency CAL...
👉Chiller cooling capacity calcs: • CALCULATE Chiller cool...
👉Chiller compressors: • 🔧 Chiller - Compressor...
👉Chiller expansion valve: • Chiller - Expansion Va...
👉Chiller surge: • Chiller - Surge
👉Chiller condenser: • 🔧Chillers - Condensers
👉Chiller evaporator: • 🔧Chiller - Evaporators
👉Chiller compressor centrifugal: • Centrifugal Compressor...
👉Chiller cooling capacity: • Chiller - Cooling Capa...
🌡️ HVAC ENGINEERING 🌡️
👉HVAC Basics: • Fundamentals of HVAC -...
👉Boilers/AHU/FCU: • How a boiler, fan coil...
👉How Heat Pump works: • How A Heat Pump Works ...
👉Heat pumps advanced: • How A Heat Pump Works ...
👉Fan Coil Units: • Fan Coil Unit - FCU HVAC
👉VAV Systems: • Variable Air Volume - ...
👉CAV Systems: • Constant Air Volume - ...
👉VRF Units: • Video
👉Cooling load calculations: • Cooling Load Calculati...
👉Pulley belt calculations: • Pulley Belt CALCULATIO...
👉Pump calculations: • Pump CALCULATIONS, Flo...
👉Fan and motor calculations: • Fan & motor CALCULATIO...
👉HVAC Cooling coils: • HVAC - Cooling coil + ...
👉Cooling towers: • How Cooling Towers Work
⚗️ REFRIGERATION SYSTEMS 🌡️
👉How refrigerants work: • Refrigerants How they ...
👉Thermal expansion valves: • How TXV works - Thermo...
👉Refrigeration design software: • Refrigeration Design S...
👉Design refrigeration system: • How to DESIGN and ANAL...
👉Reversing valve: • Reversing valve - Heat...
👉How A/C units work: • Basic Refrigeration cy...
⚗️ REFRIGERANTS ⚗️
👉Refrierant retrofit guide: • Refrigerant Retrofit G...
👉Refrigerant types, future: • Refrigerant Types, Iss...
👉How refrigerants work: • Refrigerants How they ...
🌊 HYDRONICS 🌊
👉Primary & Secondary system: • HVAC Primary & seconda...
👉Pumps: • Centrifugal Pump How D...
👉Pump calculations: • Pump CALCULATIONS, Flo...
wireman, electrical contractor, national electrical code, electrican, electrical exam prep

Пікірлер: 652

  • @EngineeringMindset
    @EngineeringMindset11 ай бұрын

    *Get an exclusive Surfshark deal!* Enter promo code *ENGINEERINGMINDSET* for an *extra 3 months free* at surfshark.deals/engineeringmindset

  • @manickn6819

    @manickn6819

    11 ай бұрын

    Good video. Can you do one on UK electrical systems? TNCS

  • @MTZ_Tractors

    @MTZ_Tractors

    10 ай бұрын

    Kindly make a detailed video on the Electronic Speed Controller and Servo tester controlling the BLDC 2212 Motor.

  • @Aktharindia7869

    @Aktharindia7869

    10 ай бұрын

    What about your videos are Copyrighted or free??

  • @EngineeringMindset

    @EngineeringMindset

    10 ай бұрын

    Copyrighted

  • @mrafoboy5908

    @mrafoboy5908

    10 ай бұрын

    Can u guys do a video on comparator 🙏

  • @Mark-eu4di
    @Mark-eu4di11 ай бұрын

    As an electrician of 36 years I enjoy your videos very much as it reminds me of why we do what we do everyday without thought. It helps to refresh my memory thank you!

  • @melainewhite6409

    @melainewhite6409

    11 ай бұрын

    Help me out here, main and sub panels connected by non-metallic raceway and way too far apart to ever be jointly touched. I'm not following how an absent neutral fault in a (wrongly) bonded sub panel is somehow worse than an absent neutral fault in a main panel with a (properly) unbonded sub panel. It seems in both cases current returns to the buried ground rod of the panel in which the absent neutral fault exists, energizing that panel's housing, and perhaps not tripping the breaker. So is it just the issue with current getting on a metallic raceway between the panels or an alternate path between the panels via a person contacting both that is not present with my scenario.

  • @Mark-eu4di

    @Mark-eu4di

    11 ай бұрын

    @@melainewhite6409 Because when you don’t isolate the neutral buss in a sub panel regardless of the distance the ground buss and the neutral buss are bonded together through the panel frame. Now the ground buss and the neutral buss become one through the metal frame of the panel. This is dangerous because both busses are going to carry current back to source (Which is your main panel, then your utility). The ground buss should NEVER carry current unless you have a fault to ground which then it will cause the circuit breaker to trip. In the main panel it is not an issue because the only thing between the main panel and the outside pole is your neutral/ground where they now join as one conductor. 😎

  • @melainewhite6409

    @melainewhite6409

    11 ай бұрын

    @@Mark-eu4di Thanks

  • @CensoredByYouTube.

    @CensoredByYouTube.

    10 ай бұрын

    I'm not a pro, but I'll never forget a quote that I read on Tom Henry's website nearly two decades ago: _"An electrician is educated to the fact that there are times when we _*_don't_*_ want electricity to work."_

  • @thardyryll

    @thardyryll

    10 ай бұрын

    @@CensoredByKZread.You get my thumb’s up for that! I just copied that quote into my iPhone. Priceless. I am 68 and also no pro, but I did my first electrical work - everything, including a full SEP replacement - on my first house nearly 45 years ago. And it’s still standing. Cost me $37,500, and it’s worth $700,000 today.

  • @shazam6274
    @shazam627411 ай бұрын

    Excellent! The details and explanations of US Home wiring in a concise 16 minute video are quite an achievement. The illustrations, animations and well paced narration essentially make this equivalent to a thick textbook and many hours of lectures in a classroom setting. Additional kudos for the on screen reference foot notes to to the Electric Code and the bonus GFCI explanation at the end! Thank you for these great videos.

  • @EngineeringMindset

    @EngineeringMindset

    11 ай бұрын

    Glad you enjoyed. The NEC codes were added in for extra info as the last electrical panel video descended into a war zone in the comments section, this should clarify things

  • @w1swh1

    @w1swh1

    9 ай бұрын

    Yes good job, very clear now. @@EngineeringMindset

  • @cityguyusa

    @cityguyusa

    8 ай бұрын

    Funny that we seem to learn better from video yet classrooms are still book centric. If we had a movie a couple times during the school year when I went to school it was a miracle. Maybe 3 or 4 a year. Maybe the classroom of the future is KZread. We just need to organize the content.

  • @w1swh1

    @w1swh1

    8 ай бұрын

    @@cityguyusa Yes I agree!! A video is worth a thousand books lol😊

  • @-_.._._--_.-.-_-_-_-...-.-

    @-_.._._--_.-.-_-_-_-...-.-

    5 ай бұрын

    ​@@w1swh1but the video keeps referring to the books, so..... I'm confused now!

  • @synctothegid
    @synctothegid11 ай бұрын

    This is absolutely the best presentation I have ever seen concerning this subject. I have been in the power business for over 40 years and my personal observation is that most people in this business, including myself, are hard pressed to really explain this adequately or have a true understanding of the "why" of this very important subject. Really great job. Thanks

  • @erintyres3609

    @erintyres3609

    8 ай бұрын

    The diagrams at 1:44 and at 11:04 really help to make things clear.

  • @robertbolzicco9995
    @robertbolzicco99953 ай бұрын

    I have been doing this for 20+ years and "just knew" what do do and why. This explained it so much better than anyone has in my 20 year service.

  • @frnks3020

    @frnks3020

    Ай бұрын

    Same

  • @williamrose7818
    @williamrose781811 ай бұрын

    We do not bond sub panels because a ground cannot be a current carrying conductor. If you were to lose the neutral in a sub panel, and it was bonded, everything would work through the ground. And as I just mentioned the ground can not be a current carrying conductor. Thank you.

  • @skatedoof

    @skatedoof

    7 ай бұрын

    Thanks for putting it simply

  • @user-vb4em4vm5h

    @user-vb4em4vm5h

    6 ай бұрын

    Should your ground wires be run to separate bars in the box?

  • @user-vb4em4vm5h

    @user-vb4em4vm5h

    6 ай бұрын

    As in the ground being separate from the neutral?

  • @djkingpersia

    @djkingpersia

    6 ай бұрын

    ​@@user-vb4em4vm5hyes you should add a ground bar to your sub panel and keep the grounds in neutral separate not put the ground in neutrals together on 1 bar

  • @odavis1364

    @odavis1364

    6 ай бұрын

    Correct

  • @gauthamtaube
    @gauthamtaube10 ай бұрын

    I know it takes a great deal of effort and attention to detail to explain something in a simple way. The more you try to explain something simply, the more illustrations and flow you need to construct, in order to get across the information without leaving your audience feel like they've already lost you. You have done exactly that - put all your knowledge together without a ton of effort to transfer that to your audience in a short manner. In the field of electrical engineering, not a lot of channels or content creators do that, like we see in the field of computers and IT/programming. You are one of those few content creators who is also hands-on and detailed, and we see your level of effort and really, really appreciate you!

  • @zeddpilsner4
    @zeddpilsner411 ай бұрын

    You have the best explanations on the platform. Please keep doing what you do!

  • @DanielMcNaughton91
    @DanielMcNaughton9111 ай бұрын

    Always wanted to understand why you don't bond ground and neutral in a sub panel. Thanks for the great content!

  • @EngineeringMindset

    @EngineeringMindset

    11 ай бұрын

    Glad to help!

  • @buentaste

    @buentaste

    11 ай бұрын

    I still don't understand. Cau you explain please 🙏 to me? Thanks...

  • @buentaste

    @buentaste

    11 ай бұрын

    @@spotscorner6040 I really appreciate you kindness for answering. I do understand that the ground wire needs to be bonded to the white (neutral) wire in the box panel. What fo not understand is why the su panel is not. Thanks....

  • @williamrose7818

    @williamrose7818

    11 ай бұрын

    Because the ground cannot be a current carrying conductor, and if you were to lose the neutral in a sub panel, everything would still work through the ground. And like I just said the ground cannot be a current carrying conductor, so that is why we do not bond sub panels.

  • @DanielMcNaughton91

    @DanielMcNaughton91

    11 ай бұрын

    @@williamrose7818 that explanation was the missing piece for me. Thank you!

  • @frostbite1991
    @frostbite19916 ай бұрын

    After years of asking why you don't bond neutral and ground anywhere outside the main panel and getting the response "because you just don't", I finally understand why. It's all about getting the breaker to trip when it needs to. I can also see why other countries requires GFCI breakers, as you're SOL if you lose service neutral in the majority of US homes. Thanks for making this extremely easy to understand!

  • @garycornelisse9228
    @garycornelisse922811 ай бұрын

    This is the best explanation I have ever seen on the installation of sub panels and grounding and I have done electrical work for over 50 years.

  • @veteranveteran9915
    @veteranveteran99159 ай бұрын

    Finally somebody has a proper video with no crazy loud music dancing clowns shaky cameras or weird stuff going on. Just excellent illustration perfect explanation and detailed video work thank you so much I just subscribed❤❤❤

  • @jimdean7335
    @jimdean733511 ай бұрын

    Nicely done. Many people don’t understand the ground/ neutral scenerios and you explained it very well.

  • @EngineeringMindset

    @EngineeringMindset

    11 ай бұрын

    Thank you

  • @itchitrigger8185
    @itchitrigger818511 ай бұрын

    Thank you for this, very informative. 22 ish years ago when I was a wee young apprentice plumber, I was cutting in an ice maker tee off the main and got whacked off my ladder. I found out latter that they 'lost the neutral'. I was so unsure about what actually happened, that for many years after, I would use jumper cables to jump any main cuts. To this day I keep an ncv wiggy in my tool bag for the occasional 'shocking shower valve'. Thank you again for this great presentation.

  • @benchociej2435
    @benchociej243511 ай бұрын

    11:48 this is a ground fault and short circuit. Another possible ground fault is neutral to ground, which is not a short circuit and won't generally trip the overcurrent device. Just another reason why GFCI is important!

  • @BryanSeigneur0
    @BryanSeigneur010 ай бұрын

    As an American, thank you very much, clearly British Engineering Mindset engineer, for explaining North American residential electricity. I appreciate it continuously as your accent's clear timbre narrates.

  • @jessemilligan
    @jessemilligan10 ай бұрын

    This has been explained to me 3-4 times and this is the first time I’ve understood it. Thank you!

  • @allentaylor9073
    @allentaylor907310 ай бұрын

    This is I will say the best video I've seen explaining sub panel wiring and faults that could occur if miswired. Good job!

  • @nolanharriott4574
    @nolanharriott457410 ай бұрын

    Excellent video. Properly explained and I appreciate the correct terminology. I’m an electrician in Canada and we do it the same. The only difference where I am is a grounding electrode is not required for a sub panel if your bonding conductor is sized correctly. Of coarse you always have to check with your local municipality for amendments and technical interpretations to the national code. Every area is different due to things like climate and weather.

  • @jimsubtle886
    @jimsubtle88611 ай бұрын

    Nicely done mate! I wish you could have included some "in-the-field" multi-meter readings of this going wrong in the wild on bad installations. Great job Mr Mindset

  • @michaelbeckerman7532
    @michaelbeckerman753210 ай бұрын

    Easily the single BEST video I have EVER seen on this subject! Really, really well done!

  • @privacyvalued4134
    @privacyvalued413411 ай бұрын

    The Engineering Mindset drinking game: "Bus bar."

  • @EngineeringMindset

    @EngineeringMindset

    11 ай бұрын

    Sounds like a good excuse to drink

  • @DavidLewisJedi
    @DavidLewisJedi7 ай бұрын

    There are a lot of great electrical basics videos on YT, but by far, you've explained these concepts so well, and along with the fantastic graphics, made these concepts very well articulated. Thank you for producing these amazing videos and keep up the good work!!

  • @BlaiserAid
    @BlaiserAid4 ай бұрын

    I am just a DYI dude. OK, I'm an engineer and fairly well educated about electricity, but I'm no electrician. I've rewired my house, replacing old wires and balancing circuits (with guidance from a licensed an electrician), installed new circuits, etc. I've never understood why sub-panel ground and neutral are not bonded. I've watched a number of KZread videos and asked pros, and they just never really made sense to me. This video has made it very clear, and it was done really well. Thank you!

  • @user-vk3sf2qp4d
    @user-vk3sf2qp4d11 ай бұрын

    The best and most illustrative explanation I have seen!. Wow! The detail, the graphics, the NEC references, the accent! Great video.

  • @misugijun
    @misugijun11 ай бұрын

    omg this is a gold level video on this topic. there are few things i couldn't get but i'll watch again to try to understand them. Thank you very much for this much detailed and easy to understand step by step telling

  • @gruntpup8152
    @gruntpup815211 ай бұрын

    Fantastic breakdown! I really you appreciate citing the NEC so I could follow along. I understand grounding and bonding but know I feel that I can explain it. Thank you.

  • @kencarp57
    @kencarp5711 ай бұрын

    EXCELLENT VIDEO! 👍👍I knew that sub-panels should never be bonded because a fault could cause all metal parts to become electrified. But I didn't know exactly WHY. After I watch this video a DOZEN more times, maybe I will finally understand how it REALLY works...

  • @wfrencher80
    @wfrencher8011 ай бұрын

    Very good video, and as an electrician myself I appreciate the NEC code references. A couple of things. 1) At time 13:00 where you talk about "double bonded ground fault condition", NEC reference 250.6 talks about "objectionable current" which is essentially what you're explaining when the installer mistakenly bonds the neutral and grounds in both the main and sub panels. It would be helpful to add that reference. 2) At time 10:50, you're code reference is incorrect. Im assuming this was just a typo on your end. You meant to reference 250.24(A)(5) which prohibits the grounded (neutral) conductor to be bonded to the equipment grounding conductor(s). But awesome video. Thank you for making it.

  • @EngineeringMindset

    @EngineeringMindset

    11 ай бұрын

    Thank you. Good points too. For the NEC codes I have just written the article number and the section number rather than the sub points within that section simply because I think it's important the viewer reads that entire section and not just the sub point else they will miss vital information.

  • @wfrencher80

    @wfrencher80

    11 ай бұрын

    Yes that makes sense, and I do agree it's more important the audience doesn't get lost in the weeds. Whenever I have to explain electrical concepts to my customers I try to keep my explanation simple and easy to understand.

  • @user-wp3ho7dd3p
    @user-wp3ho7dd3p11 ай бұрын

    Excellent video,man.Thanks for your time.Looking forward to the next one.. You did a phenomenal job explaining trunk/branch electrical. Cheers! .

  • @slateslavens
    @slateslavens11 ай бұрын

    Thanks for this video! I need to revisit the 110 "Shore" service panel in my bus conversion motorhome. The "Main" panels in RVs are technically sub panels and I need to make sure mine is right. I knew this when I wired it and knew about the special considerations for the neutral and ground bus bars, but I didn't know _why._ Now that I do, it all makes sense.

  • @patterrr
    @patterrr6 ай бұрын

    This video is so incredibly clear and the animations do a great job of further describing the dialog. Excellent resource, thank you for creating!

  • @player101snoop
    @player101snoop3 ай бұрын

    Wow, what a great video. I have read through dozens of explanations of setting up panels and have felt like I was getting conflicting explanations. Your video put it all together and it now makes complete sense. Thank you!

  • @jurgenskrause
    @jurgenskrause10 ай бұрын

    These videos are an amazing training resource. I would love to see similar ones for European standars!

  • @rhtcguru
    @rhtcguru10 ай бұрын

    This is by far the best explanation I have ever seen. Great job

  • @donaldp9259
    @donaldp92599 ай бұрын

    Finally. A clear and coherent explanation delivered in a way that even I can understand it!

  • @imprezagtr
    @imprezagtr11 ай бұрын

    The explanation + animation really helps! Thank you!

  • @Z901Z
    @Z901Z11 ай бұрын

    The King of Building services videos!!!

  • @BoilersRock
    @BoilersRock10 ай бұрын

    Very helpful video, and the segue into your sponsor's ad starting around 7:35 was about as smooth a placement as I've ever seen :)

  • @phenry5083
    @phenry508310 ай бұрын

    Transformers almost always connect to 2 of the 3 phases of primary, other than that this is one of the best and most accurately explained videos I've seen.

  • @Mentaculus42

    @Mentaculus42

    10 ай бұрын

    Is that not how it is always done, I think the video is definitely wrong with regard to the SERVICE HIGH VOLTAGE LINE CONNECTION. Don’t you need to have the high side of the transformer connected BETWEEN two phases so that ALL of the current loops through them and not a transformer ground. Some rural high voltage lines have two lines and not three but I don’t think that one is a neutral but just the other phase!

  • @EngineeringMindset

    @EngineeringMindset

    10 ай бұрын

    There are a number of ways the transformer might be connected. It's going to vary by region. The one show is the simplest version just a single phase pole mounted type, it will work just fine. This isn't the point of the video so I have not discussed two and three phase connection transformers, just a basic understanding of how it's all connected to the grid so we understand the fault paths.

  • @phenry5083

    @phenry5083

    10 ай бұрын

    @@EngineeringMindset I was going based off your statement that it typically only connects to one phase. That is incorrect. Although single phase connecting transformers do exist, they aren’t typical. They are the rarest type. They typically connect to 2-3 phases, even for residential.

  • @Mentaculus42

    @Mentaculus42

    10 ай бұрын

    A single phase delta transformer has two bushings connected to two of the three primary wires, so the primary winding sees the phase-to-phase voltage. This avoids returning primary current through a neutral that must be solidly grounded to keep its voltage near earth potential. Since the neutral is also provided to customers, this is a big safety advantage in a dry area like California where soil conductivity is low. The main disadvantage is higher cost, e.g., from needing at least two insulated 'hot' phase wires even on a branch circuit. Other areas that have ground conductivity that is higher can be wired as per video but require a neural return path to the substation. This appears to require a 4 wire system on the primary side (or 2 wire system on 1 phase system) unless the video author suggests that the return current from the line transformer to substation can travel through the “actual ground”! So it is suggested that the provided video diagram is the simplest or a 4 wire system is simpler than a 3 wire primary system. Not too sure that a 4 wire system makes more sense than a 3 wire primary system particularly from an educational perspective. If the suggestion is that the return current can flow through the actual physical ground then that brings up some other safety concerns. The only high voltage distribution system system that I am aware of that has current flowing through the actual physical ground is in HVDC long distance transmission lines. So maybe the youtube author could do a video on the “economic considerations” of why a 4 wire system is preferred over a 3 wire primary system.

  • @Mentaculus42

    @Mentaculus42

    10 ай бұрын

    @@phenry5083 At least what I have seen in California it is typical to connect the primary between 2 phases for a residential “split-phase” service. The other possibility that I have seen in PGE areas is the use of multiple pole transformers feeding a 240v split-phase circuit that is placed below the high voltage lines. This is done to provide redundancy to the lower voltage service circuit but I have seen this cause significant low voltage problems if one of the transformers is nonfunctional.

  • @T.E.P..
    @T.E.P..6 ай бұрын

    It's been a huge delight and learning experience being subbed .... one of the few channels I ring the bell for notifications .... Hope 2023 has been a perfect year for you and those you love.

  • @DarnieeW
    @DarnieeW5 ай бұрын

    Thanks! the visualization with the audio commentary really helped me understand this a lot more.

  • @garza1367
    @garza136711 ай бұрын

    Wow! The detail, the graphics, the NEC references, the accent! Great video

  • @0blivioniox864
    @0blivioniox86411 ай бұрын

    Thank you man... This is the best-explained answer to this question I've ever found since this question began plaguing my mind.

  • @brianedwards231
    @brianedwards23111 ай бұрын

    A great explanation that I have shared with my son who is new home owner as he tries to understand basic electricity.

  • @LonersGuide
    @LonersGuide11 ай бұрын

    The best and most illustrative explanation I have seen!

  • @RezaJones
    @RezaJones3 ай бұрын

    This is a very clear and thorough explanation of this question. Well done!

  • @metrotechguru5863
    @metrotechguru58636 ай бұрын

    This was an excellent explanation of the subject. This is the most detailed and understandable presentation on U.S. electrical systems I have come across.

  • @YooTooobJeff
    @YooTooobJeff9 ай бұрын

    Excellence in presentation in all aspects, learning isn’t any easier than this!

  • @hugoluna9949
    @hugoluna994911 ай бұрын

    As an individual learning with minimal (non existent) guidance from the company I work for. Thank you sir for your concise explanation.

  • @cookinwithchris86
    @cookinwithchris86Ай бұрын

    What a great video you went all the way to the nitty gritty... This will automatically go on my electrical playlist for KZread

  • @austinmarius850
    @austinmarius850Ай бұрын

    While I know much if not all of this from watching so so many other videos and studying on my own, this ONE video explains everything so so so so well.. Amazingly well done. The flow of electricity with the dotted lines is critical in helping people understand how this all works. SO much great info in one single place. WOW!

  • @LLL2382
    @LLL238211 ай бұрын

    Am going to watch this video over and over until I understand every scenario. Thanks TEM

  • @Pharmer_Mike
    @Pharmer_MikeАй бұрын

    Phenomenal video! Have done a bit of electrical work with my father on our Farm in the past and now do a little here and there and this video succinctly gives a great overview of concepts important for working knowledge!

  • @kevinluna8411
    @kevinluna841111 ай бұрын

    Would like to see a video of yours explaining the differences between the American and European electrical systems in detail. Great video as always!

  • @EngineeringMindset

    @EngineeringMindset

    11 ай бұрын

    Great suggestion!

  • @jesserawson898

    @jesserawson898

    9 ай бұрын

    @@EngineeringMindset As would making it clear at the beginning of the video the region of the world being discussed. I assume your discussion applies to the Americas and not Europe.

  • @chrisr897
    @chrisr89710 ай бұрын

    The greatest video to explain the basics in one place. Great work. 😊😊😊😊

  • @TedTedness-wu4vb
    @TedTedness-wu4vb5 ай бұрын

    BEST explanation I have ever seen or heard. Bar none!!!! Well done Sir.

  • @kyzor-sosay6087
    @kyzor-sosay608711 ай бұрын

    Excellent video,man.Thanks for your time.Looking forward to the next one.

  • @jamess1787
    @jamess178711 ай бұрын

    You did a phenomenal job explaining trunk/branch electrical. Cheers! 🍻

  • @EngineeringMindset

    @EngineeringMindset

    11 ай бұрын

    Glad you enjoyed it!

  • @pochuanhsing2466
    @pochuanhsing246610 ай бұрын

    Thanks It's a great explanation to this topic. The best one i have seen. I wish i had seen it early then I would have saved some money on installing a sub panel by myself. We ended up hiring one electrician for 1K.

  • @rvscootin3457
    @rvscootin34574 ай бұрын

    Excellent in depth explanation!

  • @turboflush
    @turboflush10 ай бұрын

    Very well explained. Along with problem situations explained.

  • @williamferguson395
    @williamferguson3953 ай бұрын

    Great Video! Love the animated explanations!

  • @richardaristegui8930
    @richardaristegui89306 ай бұрын

    I really loved you video and how you broke everything down into simple terms. I Just wanted to let you know though. At lease in my area, the power companies and inspectors require the grounded wire coming from the grounding electrode to go straight the the primary connections in the meter located in the sealed power company compartment in the case of a meter disconnect or meter panel combo. not to the electrical panels shown on multiple occasions in your video. Sorry to bring this up but it is an important distinction. Hope this helps. I know it will definitely help someone pass inspection if they are installing a new service or repairing an existing service.

  • @dougthornton6884
    @dougthornton68848 ай бұрын

    Spot on !!! Licensed master electrician of 40 years in NY Thanx for excellent vids....

  • @Cudagirl1970
    @Cudagirl19708 ай бұрын

    Just OUTSTANDING! What an incredible resource. Thank you!

  • @MrNoobed
    @MrNoobed11 ай бұрын

    I did buried wire locating for awhile and it really made me figure out grounding. I was always disappointed when no one else understood...

  • @PhuongTran-ty8vm
    @PhuongTran-ty8vm11 ай бұрын

    Perfect demonstration! Thanks alot

  • @electriclott
    @electriclott10 ай бұрын

    In Florida where I live, the grounding electrode conductor is bonded to neutral in the meter can rather than the Neutral/Ground bus bars in the main panel.

  • @marcfruchtman9473
    @marcfruchtman947311 ай бұрын

    Amazing! This is the best explanation with animations that I have ever seen. Not only that, you provided the perfect explanation of why an EGC (proper bonding) is required and also how a grounding electrode by itself is not adequate! Additionally the explanation for the GFCI was great! Thank you very much for making this video.

  • @EngineeringMindset

    @EngineeringMindset

    11 ай бұрын

    Glad you liked it!

  • @sushantm9475
    @sushantm947511 ай бұрын

    Brilliant video sirr..long awaited.. beautifully and thoroughly explained 😊🎉.. though couldnt grasp somethings ..will again surely go through that

  • @mikehouston6851
    @mikehouston68516 ай бұрын

    This is an excellent presentation. I finally understand this issue.

  • @mesachen
    @mesachen2 ай бұрын

    Great video, watch it 20 times!

  • @localone1597
    @localone15974 ай бұрын

    Great video. You are so clear in your explanation. The best illustrations I've seen. I will definitely be watching more.

  • @omasback
    @omasback11 ай бұрын

    I think there's an error here: 13:24 the ground fault current will travel on the metal raceway even if you don't bond the ground and neutral in the subpanel, because the subpanel ground bus bar is bonded to the panel chassis via the screws that attach it to the chassis. The reason that you don't bond ground and neutral in the subpanel is to prevent the ground wire from carrying return current from the subpanel to the main panel during normal operation.

  • @EngineeringMindset

    @EngineeringMindset

    11 ай бұрын

    Notice at 13:07 it states "equivalent path shown for simplicity" as it's difficult to animate current through the case.

  • @omasback

    @omasback

    11 ай бұрын

    @@EngineeringMindset Yeah I get that. I just don't understand why you said "if there's a metal raceway between panels, the current will flow on this also" as a result of ground and neutral being bonded in the sub panel. Current will flow on the raceway whether or not ground and neutral are bonded, because the ground bus bars are bonded to the frames of both panels. And the thing about a human carrying current between panels is also possible even without bonding ground and neutral in the subpanel, for the same reason. See @rustediron4062 and @cornpop7805 comments for basically the same objection, worded differently.

  • @MateiFM
    @MateiFM5 ай бұрын

    Excellent illustrations. Thank you.

  • @WelcmeTo1984
    @WelcmeTo19844 ай бұрын

    Kudos! Brilliant illustrations!

  • @SuperVstech
    @SuperVstech11 ай бұрын

    With the number of times I have had customers with a broken neutral feeder drop, I would hint all main breakers should be GFCI, to prevent issues…

  • @evilcraig359
    @evilcraig3592 ай бұрын

    Our inspector does not allow a ground rod on a sub panel, he said all grounds must run thru the main disconnect. I argued about it, but HE is the man.

  • @ericharrelson2045
    @ericharrelson204511 ай бұрын

    This is one of the best videos I've seen on the topic; very good.

  • @EngineeringMindset

    @EngineeringMindset

    11 ай бұрын

    Glad to hear that!

  • @lrayvick
    @lrayvickАй бұрын

    Exception! I am going to go out on a limb and say there is one exception to the rule - you should bond the neutral and ground in a subpanel where there is a gounding system at the subpanel and there is none at the main panel.

  • @dennissalisbury496
    @dennissalisbury49610 ай бұрын

    The best explanation of house wiring ever.

  • @tytyguy1able
    @tytyguy1able8 ай бұрын

    Literally it was this video that provided the lightbulb moment I needed to finish my solar installation. Thanks g!

  • @EngineeringMindset

    @EngineeringMindset

    8 ай бұрын

    Glad I could help!

  • @vincentzacks9584
    @vincentzacks95847 ай бұрын

    Excellent explanation!

  • @gerrymaecarino3695
    @gerrymaecarino36952 ай бұрын

    Thankyou , your explanation makes it easier to uncderstand.

  • @mikechiodetti4482
    @mikechiodetti448211 ай бұрын

    Thank you for this explanation.

  • @BuffaloBilliam
    @BuffaloBilliam11 ай бұрын

    Thanks for directing me here :)

  • @samueljoseph2676
    @samueljoseph26769 ай бұрын

    Hello, Been enjoying your channel for years, thanks for everything. Video topic suggestion: MRI cooling. Using liquid helium at -452F to cool giant magnet flying around someone’s head is pretty sweet. Would love a video about all the components of the cooling system! Thanks!

  • @janj5786
    @janj57865 ай бұрын

    Awesome video... would love to see same video on generator transfer panels with bonded/unbonded generators.

  • @mattjulian8153
    @mattjulian81533 ай бұрын

    👏 👏 👏👏👏 bravo!!! A most excellent presentation…well done sir! This is a ‘must watch’ for anyone in the electrical trade, from manufacturer tech support, the supply chain staff to installation apprentices ….well done indeed 👏👏👏👏

  • @rustediron4062
    @rustediron406211 ай бұрын

    12:58 - 13:47 I need further explanation. The ground bus on the sub panel is already connected to the sub pannel box right? so wouldn't current from a fault flow through that metal raceway and potentially through you if you bridged the two boxes regardless of the neutral bus being connected in the sub pannel? If the ground bus is not connected to the sub pannel box, then how would a fault on that box trip the breaker? I can understand why you wouldn't want them connected during regular operation; (no fault) because in that case the ground wires and the pannel boxes would act as an exposed neutral line but I don't understand why it matters durring a fault.

  • @GeronimoChannel

    @GeronimoChannel

    Ай бұрын

    @rustediron4062 That’s been driving me crazy but reading your comment I think that’s the answer. I think in regular operation you would be safe by touching the two panels (when properly connected). At ground fault it wouldn’t matter how they’re connected you’d still may get some current. At least that’s what I think. Did you find any answers?

  • @Hoaxiin

    @Hoaxiin

    Ай бұрын

    ⁠@@GeronimoChannel so if everything is connected properly the breaker will trip almost instantly from a ground fault which essentially makes the risk of touching both during a fault negligible. If bonded in both places it makes it so during normal operation the ground wire has a path for current to travel which is not supposed to have current for any other reason than during a fault.

  • @GeronimoChannel

    @GeronimoChannel

    Ай бұрын

    @@Hoaxiin i see. Thanks!

  • @kismofer1
    @kismofer15 ай бұрын

    very informative just what I was looking 👍🏼

  • @jefffree6990
    @jefffree69908 ай бұрын

    Great animations really help!

  • @Hoochiemamawrangler
    @HoochiemamawranglerАй бұрын

    Good information. Thankfully I have never needed a sub panel.

  • @neema12345
    @neema1234511 ай бұрын

    I'm glad to see that you're now able to make new videos

  • @EngineeringMindset

    @EngineeringMindset

    11 ай бұрын

    Have for months now

  • @neema12345

    @neema12345

    11 ай бұрын

    Nice 👍👍👏👏😊😊

  • @ninjapancakes9435
    @ninjapancakes943510 ай бұрын

    This video explains the question I've had for a long time, thank you so much for explaining that. I still have a couple questions but I now understand the reason ground and neutral are connected is to trip the breaker. I can't help but think that there has to be a better way but can't comment on that at the moment. I'll rewatch and think on it a bit more before I ask any other questions.

  • @carultch

    @carultch

    3 ай бұрын

    The neutral-to-ground bond really belongs in the transformer, rather than in the disconnect or panelboard. But, due to the fact that most service transformers are utility-owned, rather than customer-owned, the NEC makes a compromise to require it in the service disconnect instead, since it's the first piece of equipment that the customer controls. This becomes a big problem when there are service disconnects (plural) which the NEC allows, as it forces you to undermine the entire purpose of restricting this bond to one location, and requires you to do it in all of the service disconnects. It's also very common that multiple customers share a transformer, which ends up requiring redundant neutral-to-ground bonds. A much better solution would be for the NEC to only require it in the dominant service disconnect, when there are service disconnects (plural), and base its sizing on the sum of the service disconnects. Then, all smaller service disconnects would be built as subpanels with separate grounds and neutrals. And if there are customer-owned transformers, put it in the transformer instead of the secondary disconnect.

  • @quagmyer7230
    @quagmyer72309 ай бұрын

    Excellent explanation, I,wired a sub panel for a solar system to run some of the circuits like, well, sewer lift station, refrigerators and a few outlets for back up and had a hard time finding the answer to my questions, this video did it with ease.

  • @EngineeringMindset

    @EngineeringMindset

    8 ай бұрын

    Seen our new video on HOW SOLAR PANELS WORK in detail kzread.info/dash/bejne/i6yomZSadM2sl7w.html

  • @robertdale001
    @robertdale0013 ай бұрын

    Excellent explaination

  • @kattoman7548
    @kattoman75486 ай бұрын

    superb explanation!

  • @bryanfuentes1452
    @bryanfuentes145210 ай бұрын

    @12:57 When bonding the subpanel, it is true that parallel paths occur during ground fault but its not a big deal since it is shorted and therefore will happen only momentarily. The real problem is during a normal condition. The current will still flow in the two paths and also through the enclosure.

  • @chrisbolin2478

    @chrisbolin2478

    5 ай бұрын

    Yes, I agree what he said was incorrect and that the breaker would do its job. After I posted my comment I scrolled through the comments to see if anybody caught it.