Power Transformer Testing - Automatically measuring ratio and winding resistance of all taps/phases

Ғылым және технология

When manufacturers perform ratio and winding resistance tests at the end of the production process or during factory acceptance testing, time is costly and performing such tests efficiently is crucial. When performing diagnostic tests on site, there's also a limited window of time. The CPC 100 and the CP SB1 switchbox make ratio and winding resistance measurements efficient by avoiding climbing up and down the transformer repeatedly and reducing connection errors.
Interested in power transformer testing? - Watch all of our videos: • Power Transformer Testing
Interested in testing primary assets? - Watch all of our videos: • CPC 100 | Testing prim...
Get more Information about CPC 100: www.omicronenergy.com/en/prod...

Пікірлер: 52

  • @berniebernhardt1898
    @berniebernhardt1898 Жыл бұрын

    This is honestly one of the best channels on KZread. Not only do they provide useful information on a novel topic, they engage with the KZread community. Love it!

  • @omicronenergy

    @omicronenergy

    Жыл бұрын

    Thank you so much for this nice comment. We are happy that you like our channel and videos.

  • @HKPawar-eu2uj
    @HKPawar-eu2uj10 жыл бұрын

    Mr. H. K. PAWAR. Mumbai India. It is very useful for every electrical engineer. VERY GOOD.

  • @heathers2706
    @heathers27062 жыл бұрын

    I love the transformer remember you Matt hausladen miss you

  • @franciscoalvarez5215
    @franciscoalvarez52159 жыл бұрын

    Amazingly useful.

  • @thulasiram5156
    @thulasiram51563 жыл бұрын

    CPC 100 ultimate device.

  • @omicronenergy
    @omicronenergy11 жыл бұрын

    Dear Said Bourbab, We appreciate your feedback - it's very valuable for us. You are correct, the rules say that people have to wear safety gear when climbing large transformers. We missed that when the video was originally made. Meanwhile, we have a strict Personal Protective Equipment Program in place at OMICRON and will ensure that current safety practices and safety rules are followed for all future video shootings. Again, thank for your feedback. Best Regards, Our OMICRON team

  • @omicronenergy
    @omicronenergy11 жыл бұрын

    Dear Jahn Erik, The 2-winding transformer, which is shown in the video, was tested in cooperation with a local Austrian energy utility. However, the OMICRON accessory CP SB1 is not restricted to any specific 2-winding transformers, thus all explained measurements such as transformer ratio, excitation current measurements, static winding resistance as well as dynamic winding resistance measurements can be carried out on almost all types of power transformers. Best regards, Your OMICRON team

  • @vincentmansal8493

    @vincentmansal8493

    6 жыл бұрын

    France

  • @dr.nadhimrasool2959
    @dr.nadhimrasool29599 жыл бұрын

    very useful informations

  • @shahidmallik1119
    @shahidmallik11196 жыл бұрын

    Thanks for this information

  • @maniikanta3592
    @maniikanta35927 жыл бұрын

    I liked it very useful

  • @Engineer9736
    @Engineer97368 жыл бұрын

    Nice bit of automation. Unfortunately i don't have such a transformer to test.

  • @omicronenergy
    @omicronenergy11 жыл бұрын

    Dear vivekelec85, The tests can only be performed when the transformer is offline. The Tan delta/Power factor test is an additional diagnostic test for testing the insulation condition of the power transformer. It can be performed using the CPC 100 combined with the CP TD1 accessory. Best regards, Your OMICRON team

  • @ajayyadav-xq7yv

    @ajayyadav-xq7yv

    5 жыл бұрын

    OMICRONenergy will you please to share more details with us...as I am working in refinery & We have 84 transformer.. please mail me catalogue or any manual related to testing at ajayyadav9042@gmail.com

  • @omicronenergy

    @omicronenergy

    5 жыл бұрын

    Dear ajay yadav , thank you for your interest. You can find detailed information about the CPC 100 (such as brochures, articles and videos) on our website: www.omicronenergy.com/en/products/cpc-100/. Have you already heard about our dedicated power transformer test system TESTRANO 600? As you work in refinery and have 84 transformers, this test solution might be interesting for you as well: www.omicronenergy.com/en/products/testrano-600/ If you have any further questions please feel free to contact us. Best regards, Your OMICRON team

  • @lamarkap3339

    @lamarkap3339

    3 жыл бұрын

    Hello can i get à help ?

  • @omicronenergy

    @omicronenergy

    3 жыл бұрын

    Cher Lamar Kap, Merci pour ton intérêt! Veuillez contacter votre interlocuteur OMICRON local. Vous pouvez les trouver ici: www.omicronenergy.com/en/contact/addresses Meilleures salutations Votre équipe OMICRON

  • @SergioTusen
    @SergioTusen6 жыл бұрын

    Thanks

  • @ManojSingh-zq9ux
    @ManojSingh-zq9ux6 жыл бұрын

    useful information.

  • @omicronenergy
    @omicronenergy11 жыл бұрын

    Dear iClueYuin, We’re happy to hear that you like our system. As you mentioned, the system is designed to simplify the testing workflow on a 3-phase transformer for the construction crew. The transformer has to be climbed only once, and no rewiring is required, as ratio and exiting current, static and dynamic winding resistance are determined with one measurement. The risk of wiring errors is also minimized as the wiring plausibility is checked automatically prior to the measurement.

  • @mksharma4523
    @mksharma45238 жыл бұрын

    Use full for engineer

  • @teamh7pro935
    @teamh7pro9357 жыл бұрын

    Very nice

  • @satyarout9377
    @satyarout93777 жыл бұрын

    thanks omicron

  • @user-ri6jz5si3o
    @user-ri6jz5si3o6 жыл бұрын

    good job

  • @muralikrishnankrishn
    @muralikrishnankrishn11 жыл бұрын

    it's very valuable eee engineering power transformer ss / production

  • @soloogirl8372
    @soloogirl83725 жыл бұрын

    very useful

  • @hiendo8973
    @hiendo89738 жыл бұрын

    Thanks!

  • @polokelophenyo7548

    @polokelophenyo7548

    7 жыл бұрын

    phenyo

  • @abelccoyccosi7427
    @abelccoyccosi74275 жыл бұрын

    Great

  • @umangsarumgr9790
    @umangsarumgr97906 жыл бұрын

    Same to u

  • @laibamalik5162
    @laibamalik51627 жыл бұрын

    I like this

  • @jaganathapatra4813

    @jaganathapatra4813

    4 жыл бұрын

    Hii

  • @mohammadabduladeem6504
    @mohammadabduladeem65047 жыл бұрын

    Brilliant , But how to measure ZNyn11 using CPC 100 ? I couldn't find the above vector group in the mentioned test device. Regards

  • @omicronenergy

    @omicronenergy

    6 жыл бұрын

    Dear Mohammad Abduladeem, Yes, unfortunately the zic-zac vector group on primary side is not supported in the Primary Test Manager software for CPC 100 yet. However, it is possible to document it in a special field. Thus, the measurement can be performed. If you have any further questions, please feel free to contact us directly: support@omicronenergy.com Best regards, Your OMICRON Team

  • @bourun790
    @bourun7902 жыл бұрын

    អគុណបង, thanks

  • @dharmikmistry8781
    @dharmikmistry87815 жыл бұрын

    👌🏻👌🏻

  • @Bilalchntdc
    @Bilalchntdc4 жыл бұрын

    How to find Vector Group. I could not find the vector group in the list provided in PTM

  • @omicronenergy

    @omicronenergy

    4 жыл бұрын

    Dear Muhammad Bilal, for the CPC100 the vector group check is done standalone on the device itself, by using the CP SB1. The vector group check is available for TESTRANO 600 (PTM version 4.50). If TESTRANO 600 is the control device, the vector group check can be selected under “Tests”, within a PTM job (guided workflow) or when a manual job is performed. Best Regards, Your OMICRON team

  • @ritikawaghamare3124
    @ritikawaghamare31246 жыл бұрын

    transformer is fixed by nut bolts in substation on the cement concrete structure. but nut bolts loose every week , so why nut bolts loose & need to fix it every week ?

  • @omicronenergy

    @omicronenergy

    6 жыл бұрын

    Dear Ritika, we usually have nothing to do with the assembling or installing of transformer, especially not with the fundament of transformers. But this sounds like the screws have gone through, I would recommend to contact the company which concreted this fundament. Someone with experience in this topic has to take a look at the problem on site to suggest a proper solution. Best regards, Your OMICRON Team

  • @jahnerik2161
    @jahnerik216111 жыл бұрын

    Vhitc transformer vere you testing

  • @shashikantshashi4504
    @shashikantshashi45045 жыл бұрын

    Like

  • @danielyang5370
    @danielyang53706 жыл бұрын

    how you treat used transformer oil ?

  • @omicronenergy

    @omicronenergy

    6 жыл бұрын

    Dear Daniel, this depends very much on the oil condition and planned use of it. Quite typical are vacuum drying processes. Best regards, Your OMICRON Team

  • @PMEUROPE
    @PMEUROPE11 жыл бұрын

    people work without safety gear. Above 2.5 m they must bring protective clothing. These are rules in the Netherlands and Europe Engineer said Bourbab from Netherland

  • @polokelophenyo7548

    @polokelophenyo7548

    7 жыл бұрын

    all so in my country botswana

  • @iClueYuin
    @iClueYuin11 жыл бұрын

    So basically this system helps make trans setup idiot proof for the construction crew. That's a good thing :)

  • @matchenko8
    @matchenko83 жыл бұрын

    Где пояса? Лазят они!

  • @omicronenergy

    @omicronenergy

    3 жыл бұрын

    Уважаемый Евгений Попов , Мы ценим ваши отзывы - они очень ценны для нас. Вы правы, правила гласят, что люди должны носить защитное снаряжение при подъеме на большие трансформаторы. Мы пропустили это, когда было снято видео. Тем временем, в компании OMICRON действует строгая программа по использованию средств индивидуальной защиты, в рамках которой мы гарантируем соблюдение действующих правил и норм безопасности при проведении всех будущих видеосъемки. Еще раз спасибо за ваш отзыв. Лучшие отзывы, ваша команда OMICRON

  • @user-oe5vb7ok9h
    @user-oe5vb7ok9h4 жыл бұрын

    Make it by Arabic if you can please

  • @omicronenergy

    @omicronenergy

    4 жыл бұрын

    Dear عبدالجبار عركي , thank you for your comment and your interest in our products. Unfortunately we can't provide all of our videos in every language. If you have any questions regarding our products, please feel free to get in touch with your local contact person. You can find them here: www.omicronenergy.com/addresses Best regards, Your OMICRON team

Келесі