National Electrical Code (NEC) Box fill calculations

Ғылым және технология

How many wires can you stuff in a box, and how do you count them? This video goes over the National Electrical Code requirements of 314.16, based on the 2020 NEC.

Пікірлер: 101

  • @kratunkov
    @kratunkov10 ай бұрын

    Thank you Sir for your hard and consistent work to give us this knowledge on an understandable level!

  • @Self_Evident
    @Self_Evident2 жыл бұрын

    For what it's worth, here's a little tip/note regarding the 2020 box fill updates for EGC's. Basically, once there are 4 or more EGC's in the box, just divide the total by 4 to get the required allowances. That is, for your example with 46 EGC's in the box, there is no need to think, "Well, there's 1 allowance for the first 4, and 42/4 allowances for the rest". Instead, you can just calculate 46/4 for the total EGC allowances needed, as the math works out the same, to 11.5 in this case. I don't know about anyone else, but that wasn't obvious to me at first, but now that I know it, it simplifies things a little, mentally speaking. Now, if I ever actually come across a box with 46 or more (or even many less) EGC's, I'm outta there! :)

  • @PNW.sparky
    @PNW.sparky Жыл бұрын

    01 apprentice here. Great video, very informative!

  • @intheskymusic
    @intheskymusic2 жыл бұрын

    Best channel on the electrical field. Great way to review any electrical topic. Thank you sir.

  • @realvanman1
    @realvanman12 жыл бұрын

    I'll admit, I came to see that photo at the end. And I was not disappointed! Learned quite a bit too. ;)

  • @JeremySpidle

    @JeremySpidle

    Жыл бұрын

    Until you've rewired one of those after a fire, you've never really rewired anything.

  • @dane5167
    @dane51672 жыл бұрын

    you really got a few hundred million likes but most people hit the thumbs up button twice to show how much they love you. i only hit it once though..your alright lol

  • @binaryglitch64

    @binaryglitch64

    2 жыл бұрын

    I hit it 3 times just to be sure.

  • @jgnzz5351
    @jgnzz53512 жыл бұрын

    Ryan- just want to let you know how much I appreciate you for providing this good information. Much appreciated

  • @jeffparry2426
    @jeffparry24262 жыл бұрын

    "Party foul" lol. I'm going to write that in an inspection. "Item #14 turn the receptical under the sink that is facing up onto its side. This is not a violation but a definite party foul and should be corrected."

  • @felixsandoval486
    @felixsandoval4862 жыл бұрын

    Excelent content Ryan, one of the most violated items of the NEC. Clear as mud. Great job. Thanks

  • @2feetaguywith
    @2feetaguywith2 жыл бұрын

    Great video as usual. I think I learn better from you than even Mike Holt.

  • @jasonokane496
    @jasonokane496 Жыл бұрын

    Fantastic video with so much useful information! Thank you for kicking down some your knowledge. It doesn’t go unnoticed

  • @electricalron
    @electricalron2 жыл бұрын

    Hi Ryan! Good to see you in good health and back to doing what you do best. Happy Holidays!

  • @johnlasher3103
    @johnlasher31032 жыл бұрын

    Thanks for the concise and very informative video, Mr. Jackson.

  • @xxgeadxx2293
    @xxgeadxx2293 Жыл бұрын

    Awesome video, appreciate your content. Keep up the good work. Thanks 👍

  • @ignacioflores7781
    @ignacioflores77812 жыл бұрын

    Great to see you back Mr Jackson, keeping us sharp. Happy Thanksgiven to you and your love ones. charlotte,NC

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 жыл бұрын

    Cheers Ignacio!

  • @johnmaranuk1842
    @johnmaranuk1842 Жыл бұрын

    Love your videos! Always so informative. God bless, and cheers from Pennsylvania!

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    Жыл бұрын

    Thanks John!

  • @johnmaranuk1842

    @johnmaranuk1842

    Жыл бұрын

    @@RyanJacksonElectrical You're welcome! I look forward to seeing your videos

  • @aaryanmoore5423
    @aaryanmoore54232 жыл бұрын

    It’s very odd. We have ran into a pissing match at work on how to calculate this and over the I went through the internet looking for information and directly to your KZread looking for this video…and tadah you made. Universe is mysterious.

  • @J-Jim
    @J-Jim2 жыл бұрын

    Glad to see you on my learning screen again! I’m also glad to see that the second paragraph of the clamp fill section might get struck. I never understood it either.

  • @realestateservicessaleshea99
    @realestateservicessaleshea992 жыл бұрын

    Welcome back Thanks again for the videos. 🥃🥃🍺🍺🍺🍿🎯

  • @mcarroll598
    @mcarroll598 Жыл бұрын

    Great explanation Ryan!

  • @educationpower1823
    @educationpower18232 жыл бұрын

    Nice job Ryan...hope you're ok Always enjoy and appreciate your efforts....Robert from Omaha Keep up the good work

  • @camoapajafa
    @camoapajafa2 жыл бұрын

    What a mess in the last pic, Mr Ryan, I will never do that wow i have seen a lot of videos about gutters calculations or u pull, angle pull and so forth but this is is insane, wow. Spechless, but thanks for all your videos sir, always following you in all your videos. Great

  • @icevariable9600
    @icevariable96002 жыл бұрын

    Excellent video. Keep in mind, nonmetallic boxes can also have cable clamps that clamp down on Romex.

  • @rogpic15
    @rogpic152 жыл бұрын

    You just earned a new subscriber! I love your attitude and ability to teach. Side question for ya. With all this box fill mentioned, what is the wire length they use to get these calculations? I know other places in the code mentions length minimums, so do they go off that minimum? Thanks for making such great content!

  • @freiky26597
    @freiky265972 жыл бұрын

    Excellent video

  • @eugenesenter84
    @eugenesenter842 жыл бұрын

    As a fellow electrical instructor, I use this video as a review before a box fill test. By the way, practice makes better because perfect does not need practice. just something I teach my students. Thank you for your continue support of the trade. God bless.

  • @jodiegarcia3925
    @jodiegarcia39252 жыл бұрын

    Love the videos great teacher. Today just passed my Tx journeyman

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 жыл бұрын

    Sweet! Congratulations!

  • @farmerdave7965
    @farmerdave79652 жыл бұрын

    If you are wondering if a box is overfilled, it is.

  • @fisforfriendship6093
    @fisforfriendship60939 ай бұрын

    i heard from somewhere else that heat isnt the real reason we have conduit fill. i think if i remember correctly its simply because it would be too hard or troublesome to pull too many wires whether there's damage or not especially in 360 bends. i think they might have mentioned something about noise or feed back so maybe having copper wires all close to eachother could induce something but i think there are grounding methodes for certain stuff like that

  • @marcusreed8432
    @marcusreed84322 жыл бұрын

    As a commercial Electrician I’ve NEVER calculated box fill. I always oversized my box’s. I always use deep box’s unless the wall is too shallow and IF more than 2 MC cables in a box I up it to 4-11/16 deep box. ALL home run box’s get 4-11/16 box whether one MC or 4. ALL switch box’s get 4-11/16 box with 3/4” conduit to above ceiling.

  • @Jv2020perro
    @Jv2020perro Жыл бұрын

    Great information

  • @Ali_Alhamaly
    @Ali_Alhamaly2 жыл бұрын

    0:40 I see what you did there Ryan. Nice one!

  • @paul4800

    @paul4800

    2 жыл бұрын

    I made sure to hit the thumbs up twice, just to show that extra love. ;)

  • @garbo8962
    @garbo89622 жыл бұрын

    Glad to see you back. Wish the NEC would address the extra deep 120 volt receptacles with

  • @garbo8962

    @garbo8962

    2 жыл бұрын

    Sorry cont . The 120 volt receptacles with.

  • @davenag957
    @davenag9572 жыл бұрын

    Actually, the extension ring shown at the beginning is for a 4-11/16 square box, hence the larger capacity. You can tell by the mounting screw locations and the ko placement is farther apart. In Chicagoland, we refer to that size jbox as an 11b box.

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 жыл бұрын

    Agreed, definitely a 4 & 11.

  • @Ittiz
    @Ittiz Жыл бұрын

    Talking about conductors that just pass through boxes... yeah the code needs to address that. So needed to covert from a regular indoor wire to an outdoor conduit. Obvious I wasn't going to just have the wire go into the conduit, although I didn't check if that was to code (this is my house and I'm not an electrician, although I did consult one), I've only ever seen a transition to conduit in a box, so that's what I did. I used a metal box as nothing but a pass through, no splices no nothing. Then when I went to show someone the box I got and unpleasant surprise, the entire metal box was energized and ungrounded. In spite of the issue my electrician friend said the box was to code, but he thought that it was stupid. As it turns out, even though I couldn't find any marks in the romex one of the screws that seal the box had some how managed to penetrate the insulation on one of the hot wires. Well sufficed to say I opened the romex and grounded the box properly! All metal that can be in direct contact with a live wire needs to be grounded!

  • @FENATECH
    @FENATECH4 ай бұрын

    Hi there Ryan. Thank you for all your videos and content. I know this is an older video but really was a great easy to understand explanation about box fill. I recently shared the video link with a friend and he asked about the specific reason for 22.5 volume. After watching the video again myself to see what he was referring to I realized I either missed it or that you did not come back to it. At you mention that there is a very specific reason for the 22.5 volume. Would you be able to explain what this reason is? Thank you.

  • @arturogaray1465
    @arturogaray14652 жыл бұрын

    Hello. From Chicago!

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 жыл бұрын

    Cheers, I hope you're well!

  • @garbo8962
    @garbo89622 жыл бұрын

    Sorry people with fat fingers should not attempt to type on cell phones. Wish the NEC would address the extra deep 120 volt receptacles with USB &/or cell phone charger ports. At the hospital that I retired from we had Hospital grade tamper resistant ones that were over 2.5" deep. Maybe they should supply a rubber maker with each 10 pack of them. Only kidding. I always used a deep box and never used duplex switches for any new work. Great to see you back. Can remember back in the 1970 when GFCI receptacles came out and you had to install a 1" deep wiremold box onto wall case to get them to fit.

  • @kevinthompson4690
    @kevinthompson46902 жыл бұрын

    Hubbell part #809c cubic inches is 6.5 for 2 Decora devices installed in a 4 square box when using this cover

  • @aptd3174
    @aptd3174 Жыл бұрын

    Regarding Internal Cable Clamps: at 16:38 you say that it’s not too often that we have to deal with internal cable clamps - but what about non-metallic boxes? I know that if you ask 20 electricians whether the clamps on NM boxes count 19.5 would say “no!” But, when you look at the information provided by, e.g. Carlon, you can see that they believe the clamps do count and need to be deducted from the volume available. See question at bottom of page 3: carlonsales.com/techinfo/faqs/FAQ-ZipBoxes.pdf “The volume inside an outlet box does not include any deductions for integral clamps. The clamps are removed from the box when the volume is determined by UL. Therefore a single deduction in the NEC is required for the space the clamps take up inside the box.”

  • @josephdestaubin7426
    @josephdestaubin74262 жыл бұрын

    As a facilities manager, hashtag not an electrician, I find the maximum allowable conductors in most boxes to be way, way more that is reasonable to work with. Fortunately, I don't often run into these maximums. And it goes without saying that a lot of this is just my own lack of skill.

  • @jaredfournier3824
    @jaredfournier3824 Жыл бұрын

    How can you divide the EGCs as 4 if they are #12s? Im confused because wouldnt it be ¼ of 2.25 cu in since there #12s? Or are EGCs counted as 2.00 like a #14 is no matter what?

  • @FlatbottomBomber
    @FlatbottomBomber Жыл бұрын

    At 11:47 you count 9 #14 conductors, but I count 12... what am I missing? I see (4) 14-2's and (1) 14-3.

  • @freiky26597
    @freiky265972 жыл бұрын

    That is the same in New York?

  • @earthelectricinc.154
    @earthelectricinc.1542 жыл бұрын

    I wonder if Alumiconns Will ever make their way into the NEC for box fill requirements.

  • @elingenieroelectrico
    @elingenieroelectrico2 жыл бұрын

    Hi Ryan, good video. You have or know a reference to why the EGC is only counted as a unit in the box fill calculations. In new versions the change adds 1/4 unit after the 4 leads but can still cause a fill problem, from my perspective. The only reason that comes to mind is that since they are not current-carrying conductors, they do not add additional temperature in a box. Any idea?

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 жыл бұрын

    I think it is because, although they add volume, damaging their insulation doesn't really matter. That's my opinion.

  • @elingenieroelectrico

    @elingenieroelectrico

    2 жыл бұрын

    @@RyanJacksonElectrical Right, good point. It is a matter of interest since many electricians ask me the question. Thanks for the reply.

  • @dylane330
    @dylane330 Жыл бұрын

    I've always been curious why the right side of (t)314.1(a) allows for a greater capacity than is calculated in (t)314.16(b). There isn't, to my knowledge, any ability to "round up" ie.... 4 X 1/4 round/octagonal box allows 5 - #8s. 5-#8s is 15in3. Box allows 12.5in3.. There are a few examples of this... Why? Anybody have a code reference why this is allowed? Seems that it should be rounded down and only 4 conductors allowed since you can't have a partial conductor in a box. Besides devices, clamps, etc. makes the right side of (t)314.16(a) garbage anyway. Seems like it should be removed IMO.

  • @binaryglitch64
    @binaryglitch642 жыл бұрын

    On your last point about the 11½, 8 gauge conductors... Maybe that's where the AHJ's discretionary power should be granted??

  • @markf.r4538
    @markf.r4538 Жыл бұрын

    for code section {314.16 B 1} each conductor that passes through the box without Splice or termination Shall Be counted Once { We count foe the entire wires passing through Once {or} we count for each individual conductor Once?!!!!! my understanding is for each individual conductor we count ONE

  • @knotbumper
    @knotbumper2 жыл бұрын

    When did the E ring "quantity" change? 1978 code restricted E rings to two maximum.

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 жыл бұрын

    I would have to look that up in my 1978, but I don't believe the NEC has ever had such a restriction. In UL Product Cateogry QCIT it specifically states that "one or more" can be uaed.

  • @garbo8962

    @garbo8962

    2 жыл бұрын

    Several times had to go into a box that had 3 e rings. Should not be allowed.

  • @ubaldoperez8881
    @ubaldoperez88812 жыл бұрын

    Good work you seem different from when you used to be with mike holt

  • @wim0104
    @wim01042 жыл бұрын

    hah; never seen those barriers before, I really need to buy your illustrated code books!

  • @wim0104

    @wim0104

    2 жыл бұрын

    max extension rings I've seen is 5. lucky me.

  • @jeffparry2426

    @jeffparry2426

    2 жыл бұрын

    His three volume set is invaluable! Makes people think I'm a code guru!

  • @aaryanmoore5423
    @aaryanmoore54232 жыл бұрын

    Also you mentioned single conductor do not have bending space requirements. Where can I find this or how would a test question ask this! Thank you for everything you do. You energy and information has saved lives and money

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 жыл бұрын

    The same place you find any rule that doesn't exist...nowhere. Seriously though, there is no requirement.

  • @phillhuddleston9445

    @phillhuddleston9445

    2 жыл бұрын

    The rules mostly state what you can not do or limits to what you can do not what you can't do.

  • @markf.r4538
    @markf.r4538 Жыл бұрын

    in the paragraph talking about the 314.16 B1 {Exception} it should be {14AWG} not {16 AWG} as its written in the paragraph you provided {It's a typo}

  • @adelhomeserviceselectrical728
    @adelhomeserviceselectrical728 Жыл бұрын

    More grounding video I'd appreciate that

  • @strangerofthe2067
    @strangerofthe20672 жыл бұрын

    As far as that last picture goes, if you’re gonna do it wrong, at least do it BIG!!! 😂 kudos to whoever is responsible for that monster 😆

  • @jonathansnead7736
    @jonathansnead77362 жыл бұрын

    The extension ring around 3:50 has got to be for a 4-11/16ths box.

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 жыл бұрын

    Yep, I think you're right! Good catch

  • @cletus7419
    @cletus74192 жыл бұрын

    7:50 I think you meant 50.5?? Or did I add incorrectly?

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 жыл бұрын

    50.5. 😀

  • @JacobYoces
    @JacobYoces2 жыл бұрын

    Wait a minute, you're telling me there are NO minimum bending radius limits for individual conductors under 1000v? Is that just for 6awg and smaller? Or all conductors under 1000v?

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 жыл бұрын

    All.

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 жыл бұрын

    Take a peak at 300.34, then notice that no such requirement exists in Part 1 of Article 300.

  • @JacobYoces

    @JacobYoces

    2 жыл бұрын

    Thank you. I'll use this knowledge to my advantage from now on.

  • @manuellastrollo2168
    @manuellastrollo21689 ай бұрын

    sir may i insert some. would it be possible for you to discuss about lumens & watts. subcriber here, Electrician from Philippines

  • @cgsound
    @cgsound Жыл бұрын

    hahahaha I ran into this in Malls on many occasions 12x12x4 pull box FILLED several conduits and multiple 12 MC's or 4x4xbox with 5 extensions on it..... Glad I don't do that anymore

  • @kevinthompson4690
    @kevinthompson46902 жыл бұрын

    At the 5:55 mark or so you mention the 4 square box with extension ring and a plaster ring. I dont think that is a plaster ring.

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 жыл бұрын

    Funny, I didn't even click to that point of the video but I know you must be talking about the two-gang raised steel cover. Argh! You're 100% right.

  • @chipkapowski1781
    @chipkapowski17812 жыл бұрын

    Is that pic of the giant JB stuffed with wires real?

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 жыл бұрын

    Yep!

  • @jasonarkitekt9140
    @jasonarkitekt91402 жыл бұрын

    Some of these pics gave me a brain hemorrhage

  • @CalonLEnt
    @CalonLEnt2 жыл бұрын

    8:27 that’s the bottom

  • @hloyhesit8403
    @hloyhesit84032 жыл бұрын

    You supposed that 8 AWG wire would be going to a 50A receptacle around 21:35 I definitely think 6 would be more appropriate. Great video other than that

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 жыл бұрын

    ???

  • @hloyhesit8403

    @hloyhesit8403

    2 жыл бұрын

    @@RyanJacksonElectrical could you be specific on what you are questioning me on? Or is your intent belittlement?

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 жыл бұрын

    @@hloyhesit8403 No, I genuinely didn't understand your question/statement. A 50A receptacle is very often supplied by 8AWG copper.

  • @ryanjourneymanwireman4937
    @ryanjourneymanwireman49372 жыл бұрын

    No way that box fill at the end was real.

  • @kevinthompson4690
    @kevinthompson46902 жыл бұрын

    sorry the 6:05 mark

  • @bramcoteelectrical1088
    @bramcoteelectrical10882 жыл бұрын

    My god usa is diffcult wiring on boxes us easy in uk

  • @alvilla701
    @alvilla7012 жыл бұрын

    I will prefer if large devices coun for 3 (some people want to save 15 cents instead of doing something right), also I did not know that it was illegal to use a different type of screw (drywall screws) in nonmetallic boxes to hold the devices, I see that so often

  • @huestifer
    @huestifer2 жыл бұрын

    Thumbs down 👎 button pressed twice like you advised! 😂

  • @isaacwebber704
    @isaacwebber704 Жыл бұрын

    Thanks John Cena

  • @MrKen59
    @MrKen59 Жыл бұрын

    You crack me up - click dislike twice? 😂.