Box Fill for NEC 2023 with an Example + What got Deleted?

Klein GFCI Receptacle Tester with LCD Display, for Standard 3-Wire 120V Electrical Outlets Klein Tools RT250: Amazon: amzn.to/2QbXSJo
Leviton 5625-W 15 Amp, 120 Volt, Decora Single-Pole, AC Combination Switch, Commercial Grade, Grounding, White: Amazon: amzn.to/3rZpn6U
Leviton 5623-2W 20 Amp, 120/277 Volt, Decora Plus Rocker 3-Way AC Quiet Switch, Commercial Grade, White: Amazon: amzn.to/39LYBsc
3-Way Switch Videos by Sparky Channel: • 3-Way Switch Videos by...
Wago (25) 221-412 (25) 221-413 (25) 221-415 Lever-Nut Assortment Pack: Amazon.com: amzn.to/29huPiB
Wago 221-415 LEVER-NUTS 5 Conductor Compact Connectors 25 Pack: Amazon.com: amzn.to/29lLQpq
Wago 221-413 LEVER-NUTS 3 Conductor Compact Connectors 100 Pack: Amazon.com: amzn.to/29i3fPh
Wago 221-412 LEVER-NUTS 2 Conductor Compact Connectors 100 Pack: Amazon.com: amzn.to/29lMe7b
Wiha 30747 Insulated SlimLine Xeno Driver #2, 6.0mm Blade Diameter: Amazon: amzn.to/2O83pQh
VOLTCLAW-12 Nonconductive Electrical Wire Pliers: Amazon: amzn.to/3aG8EPU
Klein Tools CL380 AC/DC Digital Clamp Meter, 400A Auto-Ranging: Amazon: amzn.to/39RRxqQ
Fluke 117 Electricians True RMS Multimeter: Amazon.com: amzn.to/2cA1fne
FLUKE-117/323 KIT Multimeter and Clamp Meter Combo Kit: Amazon.com: amzn.to/2dolxyH
Extech CT20 Remote and Local Continuity Tester: Amazon: amzn.to/2MplSH6
Leviton GFTR1-W Self-Test SmartlockPro Slim GFCI Tamper-Resistant Receptacle with LED Indicator, Wallplate Included, 15-Amp, White: Amazon: amzn.to/33k1qhj
Leviton GFTR1-I Self-Test SmartlockPro Slim GFCI Tamper-Resistant Receptacle with LED Indicator, Wallplate Included, 15-Amp, Ivory: Amazon: amzn.to/318g8oG
Leviton, AGTR2-W SmartlockPro Dual Function AFCI/GFCI Receptacle, Wallplate Included, 20 Amp/125V, White: Amazon: amzn.to/2EuccqD
Leviton GFWT1-W Self-Test SmartlockPro Slim GFCI Weather-Resistant and Tamper-Resistant Receptacle with LED Indicator, 15-Amp, White: Amazon: amzn.to/39LKyRF
Shipping, Entertainment, etc. Discounts:
Amazon Prime Student 6 month Free Trial: amzn.to/2J4txZw
Prime Video Channel Free Trial: amzn.to/3mwgUEW
Amazon Prime 30 Day Free Trial: amzn.to/3mqTcdq
Amazon Music Unlimited Free Trial: amzn.to/35IlgC6
Discount on Amazon Prime: amzn.to/37ZJmLN
Audible Gift Membership: amzn.to/31Oxb08
Try Audible and Get Two Free Audiobooks: amzn.to/37NMydc
Amazon Business Account: amzn.to/31NGgGw
Amazon Kids+ : amzn.to/2J6xFIt
Exclusive benefits on Twitch: amzn.to/2HCWNpN
Amazon Home Services: amzn.to/3jxIFez
Kindle Membership Plans: amzn.to/31O9Pro
Amazon Prime as a Gift: amzn.to/3jxxF0U
Create an Amazon Wedding Registry: amzn.to/3jyHL1m
Create an Amazon Baby Registry: amzn.to/35CGa5K
My Gear and Software:
Green Screen Webaround Big Shot Gen2 Portable Webcam Background, 56 Inches: Amazon: amzn.to/3egFLde
The video was taken with the: PANASONIC LUMIX GH5 Body 4K Mirrorless Camera, 20.3 Megapixels, Dual I.S. 2.0, 4K 422 10-bit, Full Size HDMI Out, 3 Inch Touch LCD, DC-GH5KBODY (USA Black): Amazon: amzn.to/2VvWVcV and the PANASONIC LUMIX Professional 8-18mm Camera Lens, G LEICA DG VARIO-ELMARIT, F2.8-4.0 ASPH, Mirrorless Micro Four Thirds, H-E08018 (Black): Amazon: amzn.to/2Yem0JO
Saramonic UwMic9 96-Channel Omnidirectional UHF Wireless Lavalier Microphone System Two Transmitters and One Receiver for Nikon Canon Sony DSLR Cameras, for Video, Field Recording,Interview, ENG, TV: Amazon: amzn.to/2Kc5qWe
This video was edited with: Cyberlink PowerDirector 19: Amazon: amzn.to/382SH5p
To make this video I used the ZoMei Z818 Light Weight Heavy Duty Portable Magnesium Aluminium Travel Tripod: Amazon.com: amzn.to/1XOgA5T
This video was made using the: Transcend 64GB Class 10 SDXC Flash Memory Card (TS64GSDXC10E): amzn.to/1w02Oxn
Bill and sparkychannel.com are participants in the Amazon Services LLC Associates Program, an affiliate advertising program designed to provide a means for sites to earn advertising fees by advertising and linking to Amazon.com

Пікірлер: 65

  • @gregoryreffner2939
    @gregoryreffner2939 Жыл бұрын

    Thanks for the great video. Box fill is often overlooked by homeowners doing their own electrical. I know I've overlooked it in the past. The code and table references will help me calculate all neccesary allowances on future projects.

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    Thanks Gregory!

  • @Aepek
    @Aepek Жыл бұрын

    Always a pleasure Bill, always a pleasure Cheers✌🏻

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    Good to hear from you! Cheers from San Diego!

  • @brianmcdermott2430
    @brianmcdermott2430 Жыл бұрын

    Great info. Sparky. Thanks.

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    You bet!

  • @jamisongillespie3524
    @jamisongillespie3524 Жыл бұрын

    Thanks Sparky!

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    No problem, thanks!

  • @USAV3T
    @USAV3T Жыл бұрын

    Love watching you explain the code Sparky.

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    Sounds good, thanks!

  • @garydudgeon
    @garydudgeon Жыл бұрын

    Always enjoy your code interpretation explanation Sparky. Another great video.

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    Thanks Gary!

  • @CaptainSeamus
    @CaptainSeamus9 ай бұрын

    Thanks for this! I'm going to add it to my NEC class rotation.

  • @SparkyChannel

    @SparkyChannel

    9 ай бұрын

    Excellent! It sounds like you're doing a great job of teaching!

  • @im2yys4u81
    @im2yys4u81 Жыл бұрын

    I really needed this! Best explanation I've seen. I've read the NEC article, but seeing it explained by example really clarified things for me. THANKS!

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    Fantastic! Thanks.

  • @Eddy63
    @Eddy63 Жыл бұрын

    Love these little code book explanations and love your back yard pond especially the chimes 🤣😅😂 Thx as always for posting as they are very educational ...

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    Thanks Eddy! That's the San Diego Botanical Gardens. It's very relaxing.

  • @MrTooTechnical
    @MrTooTechnical Жыл бұрын

    Great vid

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    Thanks Dave!

  • @garbo8962
    @garbo89629 ай бұрын

    While adding a new cable into an existing one or two gang box sometimes the only way to not go over the box capacity is to use the receptacle to join two sets of wires rather then adding two splices .Best practice is to use deep boxes everywhere. Good luck attempting to get the extra deep receptacles with USB charging outlets into a 2.5" deep wall case that contains two cables. Will need a shoe horn rubber mallet & an extension box.

  • @kenbrown2808

    @kenbrown2808

    6 ай бұрын

    funny thing was when I left brand X, who insisted on using the shallowest box the conductor count would allow (resulting in having to change out at least two boxes during the wiring process of every house, at the cost of time) I found out that full depth boxes were a cent cheaper than shallow boxes.

  • @jefffree6990
    @jefffree6990 Жыл бұрын

    Good to know, Thanks! As a DIYer doing my kitchen this is important from a practical point of a view. I was installing some 12 ga Armored Cable and had a tough time in any box that had more than a single cable / device. Even if it was technically within spec. First, the 12 ga conductors are much stiffer than the 14ga i had been working with previously. Internal clamps that come with some boxes are very wasteful, so i switched to the external clamp where possible . I also removed unused internal clamps ( if there's 2 cables, put them on the same side (top or bottom) and remove the unused clamp) I also noticed that the internal Metal Cable clamps can damage conductors - they protect it where it enters through the hole; but a conductor thats folded back and pushed in can contact a sharper edge. Big boxes and Mudrings help, especially with GFCI receptacles

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    Excellent points, thanks!

  • @PhillyFixed
    @PhillyFixed Жыл бұрын

    Bill, you need to get your content approved for continuing education credits, would love to be able to watch your vids towards my PE renewals!

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    Great idea, thanks!

  • @anthonyelectric6045
    @anthonyelectric6045 Жыл бұрын

    Hey Bill. Great coverage on this topic 👍 sooo many people don’t know how to properly apply the math on this subject. Especially when there’s different size wires to contend with. Great explanation Bill

  • @im2yys4u81

    @im2yys4u81

    Жыл бұрын

    I've read the article several times, but I was a bit confused. The explanation with a visual aide really helped me. Now I know how to correct the jboxes in my attic. When I rewired my 1950 house I removed all the cotton wrapped/no ground wiring, and replaced it with 14-2 & 12-2 Romex. NOW I know how I can remedy my overfilling with a mud ring.

  • @anthonyelectric6045

    @anthonyelectric6045

    Жыл бұрын

    @@im2yys4u81 boy over my time as an electrician I came across some of these old houses and it’s amazing how the electric system survived. Back in that day you were lucky if you had an electrician do the job. Plus there was hardly any NEC to go by. What was your biggest challenge?

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    Thanks so much!

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    @@im2yys4u81 Excellent!

  • @im2yys4u81

    @im2yys4u81

    Жыл бұрын

    @@anthonyelectric6045 My journey started when I first bought my house in 2018. I went to replace an old light fixture, and when I removed it the only thing poking through the ceiling was a bare wire. That led to my going up in the attic and finding jboxes filled with melted wires and branch circuits with the insulation falling off. Took me a bit of time, but I eventually rewired the entire house with 14-2 Romex for my lights, and 12-2 for my wall receptacles. I added several GFCI's. 4 in my kitchen (one on each end of my kitchen counter and one in each wall), one in my bathroom, and one dedicated GFCI in each room. For safety sake I divided the lighting and receptacles into three zones, with each zone having it's own home run on the appropriate sized breaker. Prior to that my old glass fused panel was filled with 30 amp breakers, which I KNEW wasn't right. My biggest challenge has been the one Sparky just covered. Several of my jboxes are overfilled, but I didn't know that because I assumed that whoever wired the house knew what they were doing. As of now, I've replaced all the wiring, and this past week I dove in and replaced my old fuse panel with a Square D Homeline. The truth is it was a cakewalk. I ended up having to run a 4awg ground from my main disconnect to the sub because when they added the 200 amp main they only ran 3 wires (two hots and a bare stranded neutral) to my sub, and they did not separate the neutrals and the grounds. I had added a ground bar to the sub, but I was unaware that there needed to be a ground wire from the main to the sub. I ended up taping the bare stranded neutral with white phasing tape, and ran a green 4awg from the main to the sub. Best I know I am now 100% code compliant, with the exception that the jboxes in my attic are overfilled, which I'll remedy TODAY by adding a mud ring and a cover. ALL my connections were made with Wagos, and I did install green grounding pigtails inside my jboxes. To give credit where it is due, I am NOT an electrician, and EVERYTHING I did I learned on Sparky's channel. My real estate agent informs me that my improvements increased the value of my home by $15-$20,000, but my biggest reward is job satisfaction, and knowing my house isn't going to have an electrical fire.

  • @kenbrown2808
    @kenbrown2808 Жыл бұрын

    I prefer to do my math in the other direction. take the box volume (42 and change cubic inches) and divide by my conductor volume (2.25) which lets me know I can have 18 conductor counts in the box. another thing an inspector pointed out ages ago: since I'd laid the box in so neatly that there was clearly room for any size device; there was no need for him to count conductors.

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    Good tip, thanks!

  • @coypatton3160

    @coypatton3160

    Жыл бұрын

    Yes you get a conductor count up front, but you still have to do Bill’s math direction to an extent to have your answer. While you do not have to multiple your conductor count, you did by dividing. Sorta like 5+5=10, 2+8=10, 3+7=10, 2*5=10; get the ideal?

  • @kenbrown2808

    @kenbrown2808

    Жыл бұрын

    @coypatton3160 yes, it is still math, it's just a matter of preference. If you are aware of box capacity in conductors, you can easily see if you're going to have to think about box fill before you commit.

  • @chaser9363

    @chaser9363

    6 ай бұрын

    As of the 2023 code that will be a flawed method, as it doesn't take into account for any extra EGCs above 4. Which if you had 4 extra EGCs, you would have to allow for a whole extra conductor. 🤔

  • @kenbrown2808

    @kenbrown2808

    6 ай бұрын

    @@chaser9363 OMG, you mean because the number of grounding conductors makes the grounding conductor count as 2 conductor counts, I can no longer calculate the number of conductor counts allowed in my box, rather than calculate how many cubic inches my conductors add up to, and then find out if that is bigger than my box? does that mean quality box manufacturers will also stop staming the box with how many conductor counts it can accommodate based on the AWG of the conductors; because the grounding conductors might count as two conductors?

  • @laboye
    @laboye Жыл бұрын

    Hi Sparky, what's your position on non-metalic boxes with integral clamps like the plastic Carlon boxes? Should those have a volume allowance taken? I figure it's already been taken into account in the stamped/listed volume of the box, but the code still doesn't seem clear on that.

  • @steve_shec

    @steve_shec

    Жыл бұрын

    Integral clamps count as one allowance no matter how many there actually are

  • @Makitafan
    @Makitafan Жыл бұрын

    Is the conductor volume allowance 314.16(b)(1) based on 6" of conductor length?

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    They reference the code I discuss in this video: How Long do Wires Need to be in 2023? NEC 2023 300.14 and 314.17(B)(2): kzread.info/dash/bejne/ZK5qk9ONls6-itI.html

  • @brianmcdermott1718
    @brianmcdermott1718 Жыл бұрын

    Good morning Sparky, What would cause lights to flicker in some areas of my house and not others. Thank you.

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    Loose wires can do it. Also, too much voltage drop can do it.

  • @brianmcdermott1718

    @brianmcdermott1718

    Жыл бұрын

    @@SparkyChannel Thank you Sparky.

  • @ramserdm
    @ramserdm Жыл бұрын

    Just curious, if this setup was meant to be covered with drywall, then would you need to have a neutral in the box with the single 3 way switch? Awesome info though!

  • @CaptainSeamus

    @CaptainSeamus

    9 ай бұрын

    The NEC code changed a cycle or 2 back (sorry, can't remember exactly when and my code books are at the office) - but you now must run a neutral wire even if not connected to each 3 way switch. Reason: the newer "Ring" or other smart switches require a neutral in order to work correctly, so we're now required to run a neutral out even if it's just wirenutted off.

  • @bradc7767
    @bradc7767 Жыл бұрын

    How long have devices counted as 2 (two) conductors?

  • @SparkyChannel

    @SparkyChannel

    Жыл бұрын

    Quite a while, I'm not exactly sure though.

  • @ricks1611
    @ricks1611 Жыл бұрын

    If there were no other receptacles on this circuit then that single receptacle (wired to a 20 amp circuit) must be a 20 amp receptacle according to code.

  • @chaser9363

    @chaser9363

    6 ай бұрын

    That's not a 20 amp receptacle. If it was the grounded conductor slot would have like a sideways "T" configuration.

  • @wolfworrier3169
    @wolfworrier3169 Жыл бұрын

    Is a switch loop necessary, we use it in Jamaica but I hate it

  • @kenbrown2808

    @kenbrown2808

    Жыл бұрын

    you might want to clarify what you mean by a "switch loop" what it means to me is when the power comes into the light, and a single cable comes from the light to the switch. the only time that is necessary is if your switch is designed in such a way that there is only enough wiring space in the box for the one cable.

  • @wolfworrier3169

    @wolfworrier3169

    Жыл бұрын

    Yes it comes in at the light

  • @kenbrown2808

    @kenbrown2808

    Жыл бұрын

    @@wolfworrier3169 in the us, most electricians run power to the switch location and one cable to the light like bill has it in this video. Some run one cirxuit for both lights and receptacles, bit i prefer to run a 15 amp circuit just for lights, and a 20 amp circuit just for receptacles.

  • @jimmac1185

    @jimmac1185

    Жыл бұрын

    @@kenbrown2808 I agree 100%, that way you can kill the power to the receptacle circuit and work on it with the lights on!

  • @kenbrown2808

    @kenbrown2808

    Жыл бұрын

    @@jimmac1185 or turn off the light circuit to work on it and plug in a worklight.

  • @michaeljavert4635
    @michaeljavert4635 Жыл бұрын

    I think the NEC people are electricians that feel like they need more money. I am NOT rewiring my house. And if I ever MUST, because of a failure, I am drilling a lot of holes in my floor for conduit pipe. I am NOT opening walls. I like the industrial look anyway. They go a little too far sometimes.

  • @garbo8962

    @garbo8962

    9 ай бұрын

    Like conduit in unfinished section of my basement & garage but no where else Good luck selling a house with conduit in every room.

Келесі