How To Fix Daikin FIT Communication Issue. HVAC System Repair
Ойын-сауық
Inverter systems are awesome but problems, especially intermittent ones, can be a real headache. This guide will help you solve the communication error so you can stop pulling your hair out.
Follow us on Instagram at:
worldofhvac
Check out our store at:
Etsy.com/shop/worldofhvac
#hvac #daikinac #hvacproblems
Пікірлер: 24
The best thing about that machine is that you can see the transducer and thermistor data when u access it through the service menu. It makes everything easier being able to see all the data and feedback from the system live
Very helpful
@WorldofHVAC
6 ай бұрын
Thanks! Thats the goal!
Do you leave the dip switches in the off postion or turn them back on once reading the correct dc voltage?
@WorldofHVAC
6 ай бұрын
Leave them off. They dont have to be touched again
@jonathonmonique9069
6 ай бұрын
@WorldofHVAC thank you
@WorldofHVAC
6 ай бұрын
@@jonathonmonique9069 You're welcome
Is .9 volts to Much for communication?
About to have one of these installed. What are the symptoms that signal these issues?
@WorldofHVAC
19 күн бұрын
You won't have to worry about it. They updated the units and the thermostat. The bias problem doesn't exist on the new ones
@chuffman24
19 күн бұрын
@@WorldofHVAC wow, fantastic!
What company? All i caught was south Louisiana Are you near new Orleans
@WorldofHVAC
6 ай бұрын
Yea Covington
@user-jr2mk7mw5w
6 ай бұрын
@@WorldofHVAC thanks,,nice over there
@WorldofHVAC
6 ай бұрын
Yea man I love it over here. I grew up in Harahan and moved up here in 2016. I try and stay away from the soutshore as much as possible
@user-jr2mk7mw5w
6 ай бұрын
@@WorldofHVAC it was really nice before all the development started,,last time I went north shore the older areas,, were still nice and uncrowded
is .5 for communication bad?
@WorldofHVAC
Ай бұрын
Thats what you are getting? I wouldnt say its bad, all of the issues we were having were at .3ish. .6 is ideal Are you still getting codes with .5?
@pedrovelez3591
Ай бұрын
@@WorldofHVAC the complaint was not keeping up temp. I was told that not to care superheat and subcool on this unit which seemed odd. However in cool check mode it kept ramping up and down and didn’t seem to run at a steady 100%
@pedrovelez3591
Ай бұрын
@@WorldofHVAC I found a bent shrader core leaking a soon as i unscrewed the valve cap. So I assumed it was low on refrigerant to I recovered pulled vacuum and refilled and got out of there. It was draining 😂
@WorldofHVAC
Ай бұрын
In the book you can find subcool levels that match the unit
@pedrovelez3591
Ай бұрын
@@WorldofHVAC thx
You started this video by saying the Daikin Fit is great at dehumidifying. I totally disagree. I am having a horrible time getting mine to dehumidify my house.
@WorldofHVAC
Ай бұрын
Gotta check the settings and see how tight your house is. Also check calibration. The thermostat has to stay 100% off for 30 mins. Then check the calibration on temperature and humidity and see if it needs adjusting