THAT DAIKIN U4 FAULT ! BUT DID YOU KNOW WHY ?

Thanks for watching 🙌🏼🙌🏼
Massive thanks to everyone who has Subscribed. 6K 🤯 I’ll be dropping a Giveaway soon to say thanks to you all 🙌🏼
Obviously this video is only for entertainment purposes 👍🏼
.
Catch me over on Instagram
/ hvac_uk

Пікірлер: 105

  • @stijnvercruyssen4429
    @stijnvercruyssen44293 жыл бұрын

    Hi I'm a test engineer for hq for Daikin Europe in Belgium. I've been following your videos already for a while. Good to see issue in real life situations and not only in perfect test room conditions. We will have in mind all your problems you faced, to avoid in the future.

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Thanks for watching Stijn 🙌🏼 Yes, always nice to see issues in real life conditions ! That sounds good 👌🏼 Appreciate manufacturer’s who listen to engineers feedback and experiences with kit and improve where ever possible 👍🏼👍🏼

  • @stijnvercruyssen4429

    @stijnvercruyssen4429

    3 жыл бұрын

    @@hvacuk8975 if you need extra help, I can always assist you.

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    @@stijnvercruyssen4429 Thank You 🙌🏼👍🏼

  • @stijnvercruyssen4429

    @stijnvercruyssen4429

    3 жыл бұрын

    @@hvacuk8975 I also asked our team to watch your videos to learn from it.

  • @musakavalci9470
    @musakavalci94703 жыл бұрын

    Some great tips and glad your back!

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Thanks mate 🙌🏼👍🏼👍🏼

  • @richardbartlett6932
    @richardbartlett69323 жыл бұрын

    Fair play matey. So glad I'm no longer up on UK roofs getting soaked and freezing 👍

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    It was a bit wet and windy mate 😂🤦🏻‍♂️

  • @po65231r
    @po65231r3 жыл бұрын

    Glad to see your back 👍

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Thanks mate 🙌🏼👍🏼👍🏼

  • @paulbrown1079
    @paulbrown10793 жыл бұрын

    Got a magnetic dish after seeing one of your videos no more casing screws down between grills ! Great video never seen that cooling application for a board before

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    I love a magnetic dish mate 👌🏼👍🏼

  • @andreasgeorgantakis4980
    @andreasgeorgantakis49803 жыл бұрын

    Good to see you back mate!

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Thanks mate 👍🏼👍🏼

  • @rickchan3789
    @rickchan37893 жыл бұрын

    Love your videos mate, keep em comin

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Thanks mate 🙌🏼🙌🏼👍🏼

  • @electroshed
    @electroshed3 жыл бұрын

    Neons on the lil filter board, handy for checking you have all three phases - but can you even see them while the unit is powered? lol

  • @allandewar
    @allandewar2 жыл бұрын

    I had exactly the same problem at a leisure centre in Southam. All 3 condenser pcbs gone in very new units not long ago installed. Daikon supplied and fitted all 3 unfer warranty, no auestions asked.

  • @adamdebelle5819
    @adamdebelle5819 Жыл бұрын

    Brilliant videos mate, love this game

  • @Shmoobiess
    @Shmoobiess3 жыл бұрын

    Hey mate, I've only been in the trade a little over a year but will be doing my cat1 soon, learning alot on the job but after finding your channel a few days ago I've been learning loads. Keep it up mate you're motivating younger engineers like myself 👍🏻 PS - need an apprentice? 😂😂

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Thanks mate, appreciate the kind words 🙌🏼 Glad they are helping ! Good luck with career, sure you’ll smash it mate 👊🏼

  • @jobertpage-et1349
    @jobertpage-et13493 жыл бұрын

    Nice one troubleshooting sir...

  • @desmondbarker-johnson9771
    @desmondbarker-johnson97713 жыл бұрын

    Changed a fair few of them, only on the single fan skyair condensers though. Good vid mate 👍🏻

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Thanks mate 🙌🏼👍🏼 After speaking to some others it seems a lot of the other models don’t have the noise filter on the back so you can just swap the board without taking the frame off but on this model it was hard wired from the main PCB to plugs on the noise filter behind so had to take it off to get to it 👍🏼👍🏼

  • @darpac5969
    @darpac59693 жыл бұрын

    Good too see you doing a video again. Loving your magnetic dish mate, can I get one?

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Thanks mate 🙌🏼 Hopefully getting some more made up pretty soon so keep an eye out 👍🏼👍🏼

  • @mikesolari1939
    @mikesolari19393 жыл бұрын

    keep the good work up

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    🙌🏼👍🏼👍🏼

  • @mradam4430
    @mradam44303 жыл бұрын

    Have probably had three of four R32 ‘Advanced’ OU showing this u4 fault after just a few months, narrowed it down to OU PCB and replaced under warranty but didn’t know it was a known issue. Bit frustrating especially the ones that aren’t local but replacements sent quickly. Import duty charged on the latest warranty PCB but again Daikin sorted that quickly. miss matched units there must be a legit high sensible combination.

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Think there was a bulletin floating around somewhere about it showing the specific model/serial numbers mate. This one was a two hour drive away 😅

  • @deanharris9331
    @deanharris93313 жыл бұрын

    I've had the same thing happen to me, eight split units (R32). All of them went into u4 fault after about eighteen months of being installed. I'm gradually working my way through the pcb's and replacing the suspect capacitors.

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Are you changing the capacitors through warranty mate ?

  • @deanharris9331

    @deanharris9331

    3 жыл бұрын

    @@hvacuk8975 No...apparently the company that installed the units are no longer going. We're still in talks with Daikin where we stand with the problem, but from what I understand it could cause them a bit of a problem as Daikin have sold thousands of these systems. I think they've got a few dedicated field engineers that purely travel around just replacing those capacitors. I ordered about a dozen of those capacitors (kept a few as spare)and just soldered the last one in. Some units did not show a u4 fault but i was not getting any reading's back from the OU thermistors on the wall mounted controller .....which apparently Daikin said is another sign that the capacitor is faulty. Great channel by the way 😊👍

  • @agnisinatria3520

    @agnisinatria3520

    2 жыл бұрын

    I also have the same problem here with the suspended type split unit R32. From all 12 units RZF125CVM4 installed, 11 have U4 fault some after one year, and the rest after 2 years. Looking to the one of the outdoor PCB, the blue capacitors 0.47 uF have lower values. I think Daikin need to recall the PCB units from customer to replace those capacitors.

  • @awaisshahid2625

    @awaisshahid2625

    9 ай бұрын

    ​@@deanharris9331did this work mate did u manege to resolve the u4 errors

  • @craigladewig3158
    @craigladewig31583 жыл бұрын

    Bring back simple contactors with simple controls please, this week replaced 3 LG inverter boards shorted out by geckos , had 2 Daikin boards with U4 and 2 Samsung boards. The money saved in power consumption is spend on pcbs when they go

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    I’ve still got some old fixed speed 22, 407 kit running that never misses a beat ! Don’t think it will ever die 😂👍🏼

  • @rdenir

    @rdenir

    3 жыл бұрын

    I have a 35 year carrier unit and the only thing I have replaced on that is a reversing valve coil. I upgraded the Thermostat to a universal electronic controller just on 20 years ago and it has never missed a beat yet I installed a Daikin 3.5 Kw split 2 months ago and the Outdoor board is faulty and being replaced under warranty..

  • @sjefoekel6058

    @sjefoekel6058

    3 жыл бұрын

    Its called progress, but not to worry things are going for the better, maybe not so good as yesterday but sure better than tomorow🤔🙃😩

  • @mgabrielle2343

    @mgabrielle2343

    2 жыл бұрын

    Too right, where is the sense in replacement boards costing £800. Sure there must be a particular component that fails that can be repaired or replaced by anyone with good soldering and disordering skills and little knowledge in electronics..

  • @NorCal-refrigeration
    @NorCal-refrigeration3 жыл бұрын

    🤘⚡️🤘✨

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Thanks Dave 🙌🏼👍🏼👍🏼

  • @harrycallaghan2531
    @harrycallaghan25313 жыл бұрын

    You do great videos mate. What advice can you give for an Electrician who has just done the 2 year course at Willesden college and looking to get in the game. Do firms expect you to be all singing and dancing or are they reasonable and willing to train one up? Any advice appreciated gezza

  • @Horizon301.
    @Horizon301.3 жыл бұрын

    What are your thoughts on Mitsubishi Heavy Industries wall mounted units?

  • @ukacservice1318
    @ukacservice13183 жыл бұрын

    I find it alot easier to change the board itself rather than the metal back plate aswell. 10 minute job. Have done 10-15 so far. Little heads up aswell, panasonic have a similar issue on their R32 100 units inverter boards, throws a PH29 . 👍

  • @setvencarter2752

    @setvencarter2752

    3 жыл бұрын

    I'd agree with you about the board it's self, daikin love cable ties😁. Had a few panasonics do a P29 on me straight from installing too.

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    I did plan on doing the board only but couldn’t get my hands behind to unplug everything off the noise filter ! After speaking to some others it seems a lot of the other models don’t have the noise filter on the back so you can just swap the board without taking the frame off but on this model it was hard wired from the main PCB to plugs on the noise filter behind so had to take it off to get to it 👍🏼👍🏼 Got fat sausage fingers 😅 I haven’t heard of the Panasonic issue ! Nice one mate I’ll keep an eye out for it 👍🏼👍🏼

  • @ukacservice1318

    @ukacservice1318

    3 жыл бұрын

    @@hvacuk8975 yep one of the plugs can be a bit of a pain on the noise filter, bottom left when looking from above. That's the only issue I've found. Definitely need a syringe for the heat sync too. Makes life so much easier.

  • @ukacservice1318

    @ukacservice1318

    3 жыл бұрын

    @@setvencarter2752 yeah, the fault leads you to think the comp is locked. Inv output is rubbish on them aswell I've found. Can't 100% say if good or not. Will give power for a split second then nothing.

  • @neilvestervictor180
    @neilvestervictor1803 жыл бұрын

    great work

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    👍🏼👍🏼

  • @EverythingHVACR
    @EverythingHVACR3 жыл бұрын

    Nice video man!

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Thanks mate 🙌🏼👍🏼

  • @brendanmurray6836
    @brendanmurray68362 жыл бұрын

    Hey bud hope you're well, another cracking video. Can I ask what you used to download the manual before you started please? Is it a programme or app. Cheers big dog

  • @Tcmairconditioningservices
    @Tcmairconditioningservices3 жыл бұрын

    Changed my first one on a single fan the other day, bit of a pain but fixed my u4 fault! Good job mate!

  • @Harry_hvac_irl
    @Harry_hvac_irl3 жыл бұрын

    The last main pcb I replaced under warranty the new pcb wouldn't engage the coil for the 4 way valve. Took a lot of convincing to get daikin to send another. Also how bad is it the way they send the heat sink.🤣🤣

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Mate !!! Heat sink in a bag ! 🤣🤦🏻‍♂️

  • @Harry_hvac_irl

    @Harry_hvac_irl

    3 жыл бұрын

    @@hvacuk8975 joke. How is a fella ment to get it out... end up with more on your hands then the pcb.

  • @ADP_Artisto
    @ADP_Artisto3 жыл бұрын

    All in one noice filter, inverter, control, overvoltage , voltage Earthleakage , all huh nice

  • @dongwong469
    @dongwong4692 жыл бұрын

    Hey man (great videos) With the faulty caps on the boards , will there still be a signal down the transmission line because of the bad caps?

  • @Hoppa12345

    @Hoppa12345

    9 ай бұрын

    I repair these pcb's many times. there are a few issues. Communication works. But no operation at unit. No communications with still power on signal. and very weak signal ... All of them are resolvable with replacing ALL the caps on the board. not just 1 or 2 .. Everyone of them.

  • @FriotecAVAC
    @FriotecAVAC3 жыл бұрын

    Sometimes it happens between 2 year

  • @jdjavedvlogs222
    @jdjavedvlogs2223 жыл бұрын

    Brother what is the scope of hvac in uk or good or bad how to apply for hvac working team details about tha please please

  • @sterlingarcher46
    @sterlingarcher463 жыл бұрын

    Bro where did you get the magnetic umbrella ? I've been looking for it but can't get my hands on it . Seems like you guys across the channel get way more of the good stuff than we do eh !

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Got it from a wholesalers called Derbyshire Refrigeration mate ! The most money I’ve ever spent on an umbrella 😅 but hoping it will keep me dry doing things like this 🤞🏼👍🏼

  • @kcomfortsystemshvac7060
    @kcomfortsystemshvac70603 жыл бұрын

    Hi,,,mate,,,,,weather in Birmingham,,,rain,,,,!!,,, always good performance,,,,,,, always I will get good knowledge,,,,,,,,😀😀😀

  • @teknics8853
    @teknics88533 жыл бұрын

    Good evening sir how to repair pcb board of daiken u4 error.

  • @guitaristgary
    @guitaristgary3 жыл бұрын

    Just discovered your vids, rhyere great! Do you just use your phone camera to video the footage?

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Thanks mate 🙌🏼 A lot of the time yeah, I have got a GoPro I use too. Depends what I’m doing 👍🏼👍🏼

  • @redfoxsocial52
    @redfoxsocial523 жыл бұрын

    I see that you aren't using video timestamps. This is a really good way to improve your ranking on YT, you should consider it.

  • @JuanTodoli
    @JuanTodoli3 жыл бұрын

    Every single one PCB with the same problem?

  • @joshnewton9277
    @joshnewton92773 жыл бұрын

    Did I spot the supco umbrella at the end there? If so where did you get that from? Been making do with a homemade version of a magnet and sportsworld umbrella for a while 😂💪🏻

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Well spotted mate, the most expensive umbrella ever I think 😂 I was hoping to show it off but it stopped raining 🤦🏻‍♂️ I grabbed it from Derbyshire Refrigeration mate, think they’ve just restocked too 👍🏼👍🏼

  • @joshnewton9277

    @joshnewton9277

    3 жыл бұрын

    @@hvacuk8975 love my gadgets mate! Wera zyklop next for me but can't decide between 1/4 or 3/8 🤔 cheers for that though I will check them out. Will be worth the money on that one day that you dont have it! Especially fault finding in the rain

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    @@joshnewton9277 definitely 👌🏼 I’ve got both the 1/4 and 3/8 Zyklop mate. The 1/4 is the one I grab the most for VRF/Split repairs but the 3/8 is a good choice if you need to go up to 17/19mm too 👌🏼👍🏼

  • @alireda4441
    @alireda44413 жыл бұрын

    The R32 on the panel at the beginning of the video indicates the refrigerant R32?

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Yes 👍🏼

  • @adrianfarhan2659
    @adrianfarhan26593 жыл бұрын

    Are you working with daikin?

  • @rafaeltarragamora8399
    @rafaeltarragamora8399 Жыл бұрын

    The guilties from this failure, are the blue capacitors . Remplace its.

  • @Eastdurhamenduro
    @Eastdurhamenduro3 жыл бұрын

    Where are you getting the manuals from bud?

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    To be honest mate most of them just come from a google search 👍🏼👍🏼

  • @airmensystemscontrol1270
    @airmensystemscontrol12703 жыл бұрын

    Hi Mate! Where is the reason because all those Pc has gone? Highly voltage?

  • @airmensystemscontrol1270

    @airmensystemscontrol1270

    3 жыл бұрын

    Ahh Sorry! Thanks for the video

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    Faulty capacitor on the Main PCB comms circuit which drops the comms voltage causing a U4 error 👍🏼👍🏼

  • @slawekjurek11

    @slawekjurek11

    3 жыл бұрын

    @@hvacuk8975 I have the same problem as you describe in your movie and the same motherboard. Can you tell exactly which capacitor or capacitors I need to replace?

  • @nitishtripathi6426
    @nitishtripathi64262 жыл бұрын

    Daikin Vrv 3 in showing error code U4 How to solve

  • @leewilson6635
    @leewilson66353 жыл бұрын

    Mitsi all the way!

  • @christiansommer914
    @christiansommer9143 жыл бұрын

    Are you self employed or do you work for a company?

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    I actually work for a company mate but look after myself so it’s pretty much like working for myself 👍🏼👍🏼

  • @dantheman9909
    @dantheman99093 жыл бұрын

    Had loads of these go bit embarrassing really.

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    👍🏼👍🏼

  • @maracservices
    @maracservices2 жыл бұрын

    No video mate 👌🏻

  • @ADP_Artisto
    @ADP_Artisto3 жыл бұрын

    It also used for DUCTABLE

  • @ADP_Artisto
    @ADP_Artisto3 жыл бұрын

    U4 is communication error

  • @user-bf5so9dl7d
    @user-bf5so9dl7d3 жыл бұрын

    replacing pcb in a rainy day? good luck with that.

  • @ADP_Artisto
    @ADP_Artisto3 жыл бұрын

    Hmm its smart vrv

  • @ADP_Artisto
    @ADP_Artisto3 жыл бұрын

    Hey man u changed pcb u need to do test mode now

  • @ADP_Artisto
    @ADP_Artisto3 жыл бұрын

    This pcb is very advanced all pcbs in one pcb ossom

  • @ADP_Artisto
    @ADP_Artisto3 жыл бұрын

    If u3 showd then u have to do test mode

  • @ADP_Artisto
    @ADP_Artisto3 жыл бұрын

    Daikin cord it remote

  • @ADP_Artisto
    @ADP_Artisto3 жыл бұрын

    Eey man this is not vrv

  • @armandosairally
    @armandosairally3 жыл бұрын

    Silly question where are you tethering yourself too??

  • @hvacuk8975

    @hvacuk8975

    3 жыл бұрын

    There is a man safe system which is basically like a steel wire that runs around a couple of meters away from the perimeter of the roof. That’s what I was clipped onto mate 👍🏼👍🏼