How to do a Insulation Resistance Test on a Single Phase Installation
How to do a Insulation Resistance Test on a Single Phase Installation. Intro to unit standards course or C.O.C course.
Жүктеу.....
Пікірлер: 53
@mesh6969 Жыл бұрын
Rajen is a legend, done my installation rules with an 'A' pass with his lectures as well as unit standards.
@christophermcewan80652 жыл бұрын
Thank you!
@lalantuddu5 жыл бұрын
Nice sir
@wambuifred6637 Жыл бұрын
This is great
@snenhlanhlankabinde96982 ай бұрын
🙌
@momohboima.s.15952 жыл бұрын
Please thank you for your efforts but please can you break it down to krio
@harunhm92142 жыл бұрын
Helloo... when you did the IR test between LE & NE, you did not press the test button. That why the reading is OL
@212529Y
11 ай бұрын
It's automatic , need not to press
@Abdul_blogs8 ай бұрын
Sir ek problem ye hai ki mere ghar ki electric bill bahut jada aara hai fir mai ne complaint kiya tho electric board wale bolte hai shyd aapki earthing problem hai ya aapke ghar ki wiring problem hai iske wajeh se aapki ghar ki electricity bill aa rahi hai ya aapke ghar ki freeze me problem hai ya aap ghr ki wiring cheak karo ya earthing proper karlo mai ne earthing cheak ki sahi hai bulb se cheak phase aur earthing acche se glow ho rahi hai abh wiring me kya cheak karna hai o batao sir aur proper earthing na hone se electric bill jada aati hai kya 400 unit aati hai har mahine plz help
@paulperriman91444 жыл бұрын
You assumed the power was off and didn't test it for any supply. You also didn't test the meter to see if it functions correctly. Never ASS U ME
@benmakokha3089
3 жыл бұрын
That is right! Especially for a training demo.
@shukelatraining8627
2 жыл бұрын
Isolation process was not shown due to time constraints of video and editing. Video is to encourage enrolment on the course for full details of tests, regulations and instruments used.
@ahxishwe5664
Жыл бұрын
test the new installations first . safety 101.
@mikethesparky40003 жыл бұрын
Do you need to do a loop test when doing test on a single phase power
@shukelatraining8627
2 жыл бұрын
Yes, as per SANS 10142/1
@simonmailu83352 жыл бұрын
Send vedio on how to carry out Pme,earth electrode test,earth loop impedance test pls.
@shukelatraining8627
2 жыл бұрын
Videos will defeat the purpose of the course. Attend the course to get the full run down of the tests, instruments and methods.
@harunhm92142 жыл бұрын
Hello,,,, when you did your IR test on LE & NE, you did not press the test button ;;;; that why the reading is OL
@shukelatraining8627
2 жыл бұрын
Test button can be locked in test position. Video edited.
@nathachasmith38711 ай бұрын
How to insall a pre paid meter
@Xxxcappie232 жыл бұрын
Can you explain why the switches need to be switched on for this test please?
@sanveersookdawe
2 жыл бұрын
Probably to test the full length of the wiring
@shukelatraining8627
2 жыл бұрын
Insulation must be tested up to the point of consumption terminals of lights and appliance. Note loads disconnected.
@prospero9955
Жыл бұрын
If switched off, any hidden blunder or two opposing connector(L&N) might not be detected while testing but while it is energized Surg takes place.
@user-ic1mp8rr8j Жыл бұрын
Oh. I remember when i was conducted practical at my institution school they ask me to explain how do you test insulation resistance test then i explained but i reached there we say select the meter on 500 DC after that invigelator asked me why you put on that 500 dc i failed even today please may someone tell me why?
@winniewamboi6801
10 ай бұрын
This is because if the insulator maintains its integrity at 500V then it will be safe for use under normal day to day voltages of around 240-230V
@arnoldbridgemudimu381411 ай бұрын
Where are located plz
@arnoldbridgemudimu381411 ай бұрын
Where are you located plz
@belimoventures35122 жыл бұрын
Continuity testing
@chukwuamauche18813 жыл бұрын
Please can list all the 16 test to be done before certification of completion is awarded to an installation
@noahjaziel9172
3 жыл бұрын
instaBlaster.
@valdimirputin
2 жыл бұрын
Good question..... One was done, what are the other 15? How are the tests documented as test/fail?
@shukelatraining8627
2 жыл бұрын
All tests are listed in SANS10142/1 or enroll for the course.
@josephomom94922 жыл бұрын
In which condition to you issue your certificate , i need one.
@shukelatraining8627
2 жыл бұрын
Originals from D.O.L or registered organization like ECA, one must be a registered contractor.
@ahxishwe5664
Жыл бұрын
Insulation testing. Design amp for MCB check. RCCB check and testing. Which will be covered in another video.
@muhammadqadeer78084 жыл бұрын
Dear Sir, You have a lot of mistakes in DB 1- Colour Coding RYB 2- Wire lugs and insulation missing 3- Cable dressing not proper
@shukelatraining8627
2 жыл бұрын
The panel is a training panel and the faults are for learners to identify as per your list and more.
@muhammadqadeer7808
2 жыл бұрын
@@shukelatraining8627 plz make sure if you train people then you should have to maintain standards, bcz a lots of people following you.
@williemobrien Жыл бұрын
You might want to learn how to bend pvc pipe first mate
@nathanl84383 жыл бұрын
ha ha ha why dc ? is it a battery ? It needs to be ac :)) good luck to the learners
@roseelectronics4582
3 жыл бұрын
insulation resistance test is done with dc voltage. at least, that's how these testing instruments are designed
@kukrikukemoer4956
3 жыл бұрын
😂😂😂😂 the meter uses Dc
@mlungisimthombo3939
2 жыл бұрын
insulation tests are done with dc voltage
@shukelatraining8627
2 жыл бұрын
Instruments use batteries to operate and the output is therefore D.C.
@30mAkills
2 жыл бұрын
AC results in impedance value which is irrelevant here. See my another comment.
Пікірлер: 53
Rajen is a legend, done my installation rules with an 'A' pass with his lectures as well as unit standards.
Thank you!
Nice sir
This is great
🙌
Please thank you for your efforts but please can you break it down to krio
Helloo... when you did the IR test between LE & NE, you did not press the test button. That why the reading is OL
@212529Y
11 ай бұрын
It's automatic , need not to press
Sir ek problem ye hai ki mere ghar ki electric bill bahut jada aara hai fir mai ne complaint kiya tho electric board wale bolte hai shyd aapki earthing problem hai ya aapke ghar ki wiring problem hai iske wajeh se aapki ghar ki electricity bill aa rahi hai ya aapke ghar ki freeze me problem hai ya aap ghr ki wiring cheak karo ya earthing proper karlo mai ne earthing cheak ki sahi hai bulb se cheak phase aur earthing acche se glow ho rahi hai abh wiring me kya cheak karna hai o batao sir aur proper earthing na hone se electric bill jada aati hai kya 400 unit aati hai har mahine plz help
You assumed the power was off and didn't test it for any supply. You also didn't test the meter to see if it functions correctly. Never ASS U ME
@benmakokha3089
3 жыл бұрын
That is right! Especially for a training demo.
@shukelatraining8627
2 жыл бұрын
Isolation process was not shown due to time constraints of video and editing. Video is to encourage enrolment on the course for full details of tests, regulations and instruments used.
@ahxishwe5664
Жыл бұрын
test the new installations first . safety 101.
Do you need to do a loop test when doing test on a single phase power
@shukelatraining8627
2 жыл бұрын
Yes, as per SANS 10142/1
Send vedio on how to carry out Pme,earth electrode test,earth loop impedance test pls.
@shukelatraining8627
2 жыл бұрын
Videos will defeat the purpose of the course. Attend the course to get the full run down of the tests, instruments and methods.
Hello,,,, when you did your IR test on LE & NE, you did not press the test button ;;;; that why the reading is OL
@shukelatraining8627
2 жыл бұрын
Test button can be locked in test position. Video edited.
How to insall a pre paid meter
Can you explain why the switches need to be switched on for this test please?
@sanveersookdawe
2 жыл бұрын
Probably to test the full length of the wiring
@shukelatraining8627
2 жыл бұрын
Insulation must be tested up to the point of consumption terminals of lights and appliance. Note loads disconnected.
@prospero9955
Жыл бұрын
If switched off, any hidden blunder or two opposing connector(L&N) might not be detected while testing but while it is energized Surg takes place.
Oh. I remember when i was conducted practical at my institution school they ask me to explain how do you test insulation resistance test then i explained but i reached there we say select the meter on 500 DC after that invigelator asked me why you put on that 500 dc i failed even today please may someone tell me why?
@winniewamboi6801
10 ай бұрын
This is because if the insulator maintains its integrity at 500V then it will be safe for use under normal day to day voltages of around 240-230V
Where are located plz
Where are you located plz
Continuity testing
Please can list all the 16 test to be done before certification of completion is awarded to an installation
@noahjaziel9172
3 жыл бұрын
instaBlaster.
@valdimirputin
2 жыл бұрын
Good question..... One was done, what are the other 15? How are the tests documented as test/fail?
@shukelatraining8627
2 жыл бұрын
All tests are listed in SANS10142/1 or enroll for the course.
In which condition to you issue your certificate , i need one.
@shukelatraining8627
2 жыл бұрын
Originals from D.O.L or registered organization like ECA, one must be a registered contractor.
@ahxishwe5664
Жыл бұрын
Insulation testing. Design amp for MCB check. RCCB check and testing. Which will be covered in another video.
Dear Sir, You have a lot of mistakes in DB 1- Colour Coding RYB 2- Wire lugs and insulation missing 3- Cable dressing not proper
@shukelatraining8627
2 жыл бұрын
The panel is a training panel and the faults are for learners to identify as per your list and more.
@muhammadqadeer7808
2 жыл бұрын
@@shukelatraining8627 plz make sure if you train people then you should have to maintain standards, bcz a lots of people following you.
You might want to learn how to bend pvc pipe first mate
ha ha ha why dc ? is it a battery ? It needs to be ac :)) good luck to the learners
@roseelectronics4582
3 жыл бұрын
insulation resistance test is done with dc voltage. at least, that's how these testing instruments are designed
@kukrikukemoer4956
3 жыл бұрын
😂😂😂😂 the meter uses Dc
@mlungisimthombo3939
2 жыл бұрын
insulation tests are done with dc voltage
@shukelatraining8627
2 жыл бұрын
Instruments use batteries to operate and the output is therefore D.C.
@30mAkills
2 жыл бұрын
AC results in impedance value which is irrelevant here. See my another comment.
Thank you!