How Freeze Protection Cables Can Save Your Pipes - Gear Up With Gregg's

Keep your pipes from freezing this winter with these handy, completely self-regulating cables! In this episode, you'll learn how to measure, install and properly maintain freeze protection cables for your pipes.
Chapters:
0:00 INTRO
1:12 PREVENTING FROZEN PIPES
2:18 INSTALLING HEAT CABLES
5:23 INSULATING A PIPE
6:06 GFCI OUTLET
6:36 INSPECTING HEAT CABLE ON PIPE
6:58 OUTRO
If you require more information about any of the products you saw in this video, be sure to check out our website!
greggdistributors.ca/search?q...
Subscribe to our channel and stay up-to-date on all of our videos including Heads Up for Hosers, Gear Up With Gregg's and more!
Founded in Edmonton, Alberta and 100% Canadian owned, Gregg Distributors LP distributes products across Western Canada to the industrial, agricultural, automotive and heavy truck sectors.
Visit our website for location details and information on how you can contact your local Gregg's branch today. greggdistributors.ca/
Follow Us on Social Media!
Facebook: / greggdlp
Twitter: / greggdlp
Instagram: / greggdlp
Also, remember to have a Great Canadian Day!

Пікірлер: 104

  • @glennzanth858
    @glennzanth8582 жыл бұрын

    When installing heating cable this is absolutely the best video to watch for information. All other videos I watched left out the thermostat which is very important, also tells you bout foam insulation which im using. Very informative!

  • @GreggDistributorsLP

    @GreggDistributorsLP

    2 жыл бұрын

    We're glad this was helpful for you, thanks for watching!

  • @mohdissa1093

    @mohdissa1093

    Жыл бұрын

    What happens if we use heat cable without thermostat?

  • @ThrasherGnar
    @ThrasherGnar Жыл бұрын

    Best video on KZread about this product! Thank you

  • @Minimalist11Guy
    @Minimalist11Guy Жыл бұрын

    Thank you very much for such a well-presented guide to pipe trace heating systems.

  • @GreggDistributorsLP

    @GreggDistributorsLP

    Жыл бұрын

    Glad it was helpful!

  • @mariejohnson7575
    @mariejohnson75752 жыл бұрын

    Great video I'll try this thanks.

  • @grumpycyclist3319
    @grumpycyclist33192 жыл бұрын

    Very helpful, thanks!

  • @Speeglelookingglass
    @Speeglelookingglass7 ай бұрын

    Great video. I have a different brand of heating cables and I was about to throw them away not realizing there was a thermostat in them and that the temperature relates to when the cables heat up. I'm thinking he indicated 35 degrees Fahrenheit the cables will heat up. Also I put the cables on the outside of this thick tubular insulation so I have to take all of that off and put it actually on the pipe

  • @josegnz4763
    @josegnz47633 жыл бұрын

    If only houston knew about these feb/2021

  • @Jeremiah-TwistedTrucker

    @Jeremiah-TwistedTrucker

    Жыл бұрын

    Dallas-Fort worth needed these too

  • @davemTX2023

    @davemTX2023

    Жыл бұрын

    Agree - I have them now

  • @mstallard
    @mstallard2 жыл бұрын

    When installing heat trace you are supposed to put it on the bottom where the water flows. Just think of it as a water slide and you should place the trace where the water will flow.

  • @colton5bucks

    @colton5bucks

    Жыл бұрын

    The pipe is generally full and pressurized with water... hence making that not necessary

  • @asclepioesculapio3522
    @asclepioesculapio35222 жыл бұрын

    Good information

  • @rickrolllinks109
    @rickrolllinks1097 ай бұрын

    excellent presentation

  • @mrink9818
    @mrink98185 ай бұрын

    Extra tip!! the place of the cable does matter when the pipes gets thicker. Than you should place the cable at 4 or 8 o'clock on the pipe. You don't choose below (6 o'çlock) because if the isolation leaves water through your cable will be constantly in the wetness. (Cost more energy for same effect) You don't put it on top (12 oçlock) because most of the heat gets lost. (cost more energy for same effect) You should loop your thermostat at the end of the pipe to the top, this way the heat-tracing cable will reach the end of the pipe and the thermostat knows the perfect moment to shut of again. So 3 tips for better energy consumption.

  • @turdferguson8612
    @turdferguson86123 жыл бұрын

    This is a good video on installing it

  • @GreggDistributorsLP

    @GreggDistributorsLP

    3 жыл бұрын

    We're glad this was helpful for you, Jason. Thank you for watching and supporting our all-Canadian channel!

  • @MariaReyes-nz1tn
    @MariaReyes-nz1tn Жыл бұрын

    Thank you 😊

  • @mksiddiki
    @mksiddiki3 жыл бұрын

    Very helpful.

  • @GreggDistributorsLP

    @GreggDistributorsLP

    3 жыл бұрын

    Glad it was helpful, thanks for stopping by!

  • @thomasbrown7728
    @thomasbrown77289 ай бұрын

    Why play background music when you’re talking? Makes it hard to understand what you’re saying.

  • @roofingtips

    @roofingtips

    5 ай бұрын

    I could hear him just fine

  • @benjamincrooker2533
    @benjamincrooker25332 жыл бұрын

    Is there a heat cable that I can put down the drain line I use for my washing machine hooked hose? I cannot get to the outside of the drain line for a conventional heat strap installation.

  • @qp773
    @qp773 Жыл бұрын

    My place had a blankface GFCI indoors if I want to start/turn off the heat tape but I had to get a new one and they were out of stock. Would there be some issues about just putting in a GFCI plug outlet rather than the blankface?

  • @151dreamer
    @151dreamer2 жыл бұрын

    Sense this video was some time back, I don't it will be answered, but here it goes. In my well house they used a rubber hose to go to the fauset outside the well house. Can I apply a heat cable if I apply a foil wrap to the rubber hose? Can a heat cable be used in this situation? what would work best in this case? thank you

  • @rickellithorpe7428
    @rickellithorpe7428 Жыл бұрын

    Can you use this heat tap on the well outside that's only 10 feet deep.

  • @OCOCOCism
    @OCOCOCism9 ай бұрын

    I have a well in my summer cottage, I drain the water out of the pipes in the house and under the house except for about 3 feet of the 1” plastic pipe coming from the well. Would I only put heat tape on that last 3 feet

  • @alanseager5279
    @alanseager52792 жыл бұрын

    it didn't answer the question I asked tho can I use it on the actuators on my snow blower attatchment some times I hate Google

  • @ericeisen7123
    @ericeisen71232 жыл бұрын

    The pipes in my kitchen under the sink seem to always freeze when it gets really cold. Does the size of the cable I choose also include the distance needed to reach the outlet or do I need to use a separate extension chord for the electrical connection?

  • @GreggDistributorsLP

    @GreggDistributorsLP

    2 жыл бұрын

    It all boils down to how far the outlet is from where you'll be installing the cable, but typically an extension may be needed if the outlet is further than usual, as the total length of the cable listed does not take into account the distance needed to reach your outlet since it varies per application. More info here > greggdistributors.ca/electrical/Freeze-Protection-and-Heating-Cables?resp_group=Default,Variations,ItemProperties

  • @MrLjarroyo
    @MrLjarroyo Жыл бұрын

    Do I wrap the heat tape on the cold water inlet pipe ??

  • @GreggDistributorsLP

    @GreggDistributorsLP

    Жыл бұрын

    It is suggested to apply this tape to water pipes where there is a potential for the water to freeze due to external temperatures. For more information on heat protection cables check out our blog greggdistributors.ca/pages/blogs/how-to-install-pronghorn-heating-cables

  • @city8456
    @city84569 ай бұрын

    Can you use this over pex pipe?

  • @josetan1524
    @josetan15243 жыл бұрын

    Where I can this heating cable in Philippines? Thank you.

  • @paulkennedy9824
    @paulkennedy98244 ай бұрын

    I have HAVE AN 4" ABS PRODUCT . DO YOU HAVE AN DIRECT IMMERSIONS PRODUCT THAT WILL kEEP PIPE THAT HAS WATER INSIDE

  • @shawngastiger3886
    @shawngastiger38867 ай бұрын

    It's 43 degrees outside does it have to be 32 to activate and feel heat?

  • @shostetler
    @shostetler2 жыл бұрын

    Can this be used to wrap around a well pressure tank in a small enclosure outside?

  • @GreggDistributorsLP

    @GreggDistributorsLP

    2 жыл бұрын

    Depending on the type of metal your well pressure tank is, an option that would work better than freeze protection cables are drum heaters, which we carry in a variety of power outputs (check them out here: greggdistributors.ca/Material-Handling/Drums-Handling-Equipment/Drum-Heaters?resp_group=Default,Variations,ItemProperties), however for these drum heaters we would still recommend you check with the manufacturer of your tank for compatibility, just to be safe. Thanks for watching!

  • @mazinalbusaidi9384
    @mazinalbusaidi9384 Жыл бұрын

    Thanks for the video, I have a question if the thermostat is setting at 40C and i want to increase the heat in the pipeline so i have to reduce the thermostat seat point ? To increase the temperature?

  • @GreggDistributorsLP

    @GreggDistributorsLP

    Жыл бұрын

    These do not have an adjustable thermostat, it is an automatic thermostat that turns on at 3°C and turns off at 10°C.

  • @sly2599
    @sly2599 Жыл бұрын

    thks for the video I have to go in a crawl space under mobile home to install the heat tape I already have one installed but not sure how old it is... could I leave the one I have in place and install a second heat tape just in case one stops working during winter it is difficult to go under the mobile home

  • @GreggDistributorsLP

    @GreggDistributorsLP

    Жыл бұрын

    You should remove the old tape, as it is not recommended to have 2 heat tapes on a piece of pipe.

  • @anthonyhewetson5086
    @anthonyhewetson5086 Жыл бұрын

    If you have two pipes (hot water and cold water) running parallel can you spiral a cable around both (without overlapping) to prevent freezing of both pipes with one cable ... or do you have to use two cables?

  • @GreggDistributorsLP

    @GreggDistributorsLP

    Жыл бұрын

    No, that is not the correct installation method. You would require one per line.

  • @AZOVdefense

    @AZOVdefense

    Жыл бұрын

    I ran my wire from outside to were my cold and hot busted and got fixed not letting the wire touch and went back along the water line in n the side not touching the wires together so hopefully I get extra heat on me main water pipe going inside and underneath the restroom. Got one longer than needed but I guess extra will work better.

  • @AZOVdefense

    @AZOVdefense

    Жыл бұрын

    Don’t spiral just taped it so it would not touch together on my hot and cold that busted and that’s because I had extra Long cord.

  • @shannond4142
    @shannond41422 жыл бұрын

    If I only have 18 inches of pipe above the slab of an unconditioned garage, what should I do with the extra cable if I had a 3ft. length?

  • @pjbrankin

    @pjbrankin

    Жыл бұрын

    I have about the exact same situation - what did you end up doing in your case?

  • @manuelgarcia9085
    @manuelgarcia90853 жыл бұрын

    Can the built is thermostat be removed to have continuous heat with an external digital thermostat plug in?

  • @GreggDistributorsLP

    @GreggDistributorsLP

    3 жыл бұрын

    Unfortunately the built in thermostat can not be removed with these specific cables and would not be recommended to alter them, as this can cause a safety hazard. Thanks for watching!

  • @paulmaxwell8851

    @paulmaxwell8851

    Жыл бұрын

    Manuel, I installed a heat tape on a water line, where it enters the crawl space. That's where it is vulnerable, where it passes under the footing. I installed a good-quality Honeywell manual thermostat very low to the ground, feeding a receptacle. Now the 4'C heat tape thermostat is controlled by the new thermostat, set for 2'C. This allows me to only run heat when absolutely necessary. It has worked well for fifteen years.

  • @1967odie
    @1967odie2 жыл бұрын

    i was wondering can you replace the thermostat on them or just buy another heat cable my plug end is lighting up but that's it

  • @GreggDistributorsLP

    @GreggDistributorsLP

    2 жыл бұрын

    The thermostat can not be replaced on these Freeze Protection Cables, as they are built in. You would have to just replace the entire heat cable. Thanks for watching!

  • @rodola647

    @rodola647

    Жыл бұрын

    Did you put ice around the sensor for it to kick on and heat otherwise if you plug it in and it’s above 37° you won’t feel nothing and just have the light

  • @gremlingirl101
    @gremlingirl1015 ай бұрын

    my pipe starts in house basement where it is warm then goes through wall into a location where i can not reach under the house..if i put cable on pipe will it warm it enough to keep pipe from freezing? about 15 feet away..also how will it come on in a warm location.

  • @GreggDistributorsLP

    @GreggDistributorsLP

    5 ай бұрын

    Unfortunately, the cable only heats up the portion of the pipe that it sits on. Also, since it would be in a warm area, this would not trigger the thermostat to turn on the heat in the cable.

  • @ubacow7109
    @ubacow710912 күн бұрын

    I have a pipe that isnt straight and has a lot of 90 degree bends do you have advice for this? On the instructions in the box it usually says not to bend them but idk how i'm supposed to get around the 90 degree bends if i cant bend it.

  • @GreggDistributorsLP

    @GreggDistributorsLP

    2 күн бұрын

    You can get away with slightly bending these cables on a pipe, however a 90 degree bend would be unsafe for your application.

  • @playall.8844
    @playall.8844 Жыл бұрын

    Can I used this in side the bucket for goats winter time getting frozen water bucket?? Is this can help??

  • @GreggDistributorsLP

    @GreggDistributorsLP

    Жыл бұрын

    This product is intended for Rigid Pipe; however, you may want to consider this bucket heater for your application: greggdistributors.ca/Tools-Shop-Equipment-and-Storage/Hand-Tools/flooring-tools/mst742g

  • @jeep79cj00tj
    @jeep79cj00tj3 жыл бұрын

    Can this be installed inside a outside sump line?

  • @GreggDistributorsLP

    @GreggDistributorsLP

    3 жыл бұрын

    No, the product is designed to be installed on the outside of pipe.

  • @samshare2146
    @samshare21465 ай бұрын

    This looks like a great system, but...can it be used for pipes that are hidden behind walls/ceilings? I have pipes that are prone to freeze/burst and they are not easily accessible. I would like a system that monitors temperature and automatically heats the pipes in case the temperature gets too cold and prevent water in the pipes from freezing.

  • @GreggDistributorsLP

    @GreggDistributorsLP

    5 ай бұрын

    As far as we are aware, a system that you have described (while it would be nice!) does not exist. Thanks for watching our video!

  • @samshare2146

    @samshare2146

    5 ай бұрын

    ​@@GreggDistributorsLPThank you for the quick response. Alas, disappointing to hear. I had a pipe that broke last night (ergo, how I found your video looking for a long-term more reliable solution) that was repaired this morning. Last time this happened was during the 2021 "Big Freeze" in TX. This time, we found that a soldered joint in an elbow joint in a pipe failed when the water expanded while freezing. The location is a bedroom and bath above a garage that is reached from a walkway over a port-cochere. This exposes the pipes going to the bathroom through the access hallway to cold temperatures under it. The pipes are, obviously, hidden which is why I asked. Fearing the response was "no", I asked my repair guys of the possibility of making a panel in the garage to gain easy access to a pipe heating system and he said that it would be possible. The pipe is fixed, so now time for the repair guys to finish cutting out the ceiling, remove all the (wet) insulation, and drying everything for the next couple days before they start putting everything back together. This will give me time to continue to explore pipe heating systems as well as installing a heater in the garage as a backup.

  • @sumerbc7409
    @sumerbc74093 жыл бұрын

    you're going to need the most heavy duty industrial sticky tape made for this... 10 years from now you don't want unraveling tape holding down the heat cable...

  • @ShawnShaddock
    @ShawnShaddock2 жыл бұрын

    Do I need freeze protection cables when running a buried pipe from my house to an out building?

  • @GreggDistributorsLP

    @GreggDistributorsLP

    2 жыл бұрын

    Your safest bet would be to refer to your local plumbing & heating codes in your city, to ensure that where you'll be installing these cables will meet the safety standards. Thanks for watching!

  • @paulmaxwell8851

    @paulmaxwell8851

    Жыл бұрын

    No, just bury below the frost line. Ask your local building inspection office what that is. It's often found online.

  • @mfurtman1
    @mfurtman13 жыл бұрын

    Our bathroom is over an unheated crawl space. Hot and cold pipes run to the bathroom, then split to shower, again to sink, and cold to toilet. If cable is place on each pipe, that's a lot of plugs to connect to the outlet. What do you suggest for such a layout? Would it be enough to just heat the two main lines and not worry about the off-shoots?

  • @GreggDistributorsLP

    @GreggDistributorsLP

    3 жыл бұрын

    Without knowing all the specifics, it's hard to say for sure. Typically the two mains would enter the heated space and then tee off to the off-shoots so these would not need to be heated. Unless your hot water supply is on a heat loop, which we assume it is not, you would probably want to add a heat trace to both hot and cold main lines. Depending on how long the runs are in the exposed crawl space, you could use one heat trace line. For example, if both of your runs are 15ft you can use a single 30 foot cable which you can find below. Hope that helps! ohcanadasupply.ca/electrical/Freeze-Protection-and-Heating-Cables/pcr216018

  • @leerein9818
    @leerein9818 Жыл бұрын

    HOW often should you replace the heat tapes?

  • @paulmaxwell8851

    @paulmaxwell8851

    Жыл бұрын

    When they burn out. Unfortunately, they don't tell you when they've failed. I've had heat tapes last ten years, but others have had them fail at five.

  • @tafiqsyed9614
    @tafiqsyed96142 жыл бұрын

    Can we use this inside the concrete wall

  • @GreggDistributorsLP

    @GreggDistributorsLP

    2 жыл бұрын

    Your safest bet would be to refer to your local plumbing & heating codes in your city, to ensure that where you'll be installing these cables will meet the safety standards. Thanks for watching!

  • @peterc8021
    @peterc8021 Жыл бұрын

    What’s that foil fiberglass tape called? Name brand? I can’t find it anywhere, thanks

  • @GreggDistributorsLP

    @GreggDistributorsLP

    Жыл бұрын

    It is called pipe wrap insulation, Check it out here. greggdistributors.ca/Maintenance-Repairs-and-Operations/Insulation-Products/dddrxspw02025?resp_group=Default,Variations,ItemProperties

  • @mrjoehimself
    @mrjoehimself Жыл бұрын

    How do I connect 12v heat cable to my RV's battery?

  • @GreggDistributorsLP

    @GreggDistributorsLP

    Жыл бұрын

    The heat cables featured in this video are 120VAC, you cannot connect them to a 12V RV Battery.

  • @dawndarling8588
    @dawndarling8588 Жыл бұрын

    Can this be used on a heavy water hose?

  • @GreggDistributorsLP

    @GreggDistributorsLP

    Жыл бұрын

    The intended purpose for this product is primarily for rigid pipe.

  • @501talon
    @501talon Жыл бұрын

    Is it safe to put the Pronghorn heat tape on Pex Pipe & insulate it?

  • @GreggDistributorsLP

    @GreggDistributorsLP

    Жыл бұрын

    This heat tape is suitable for use on both plastic and metal pipes, so that should be fine.

  • @501talon

    @501talon

    Жыл бұрын

    @@GreggDistributorsLP Thank you!

  • @Ben-ww1zq
    @Ben-ww1zq5 ай бұрын

    How can I repair the thermostat in the cable?

  • @GreggDistributorsLP

    @GreggDistributorsLP

    5 ай бұрын

    We wouldn't recommend replacing the thermostat in the cable, as this is a fire hazard. Instead, you would have to replace the entire cable assembly if the thermostat isn't working as it should. Thanks for watching!

  • @johncox1570
    @johncox15706 ай бұрын

    can you tie it to pressure switch

  • @GreggDistributorsLP

    @GreggDistributorsLP

    6 ай бұрын

    No, to the best of our knowledge, that is not recommended.

  • @MissCleo1953
    @MissCleo19534 ай бұрын

    Can I use this on vinyl tubing?

  • @GreggDistributorsLP

    @GreggDistributorsLP

    3 ай бұрын

    These freeze protection cables are typically used on rigid pipe, not really on a flexible material like vinyl tubing.

  • @MissCleo1953

    @MissCleo1953

    3 ай бұрын

    Could I cover the vinyl tube with a larger pvc pipe then use the heat trace over the pvc pipe?

  • @bobbg9041
    @bobbg90412 жыл бұрын

    by code this cannot be behind finished spaces, this kind of defeats the use of them in a garage with bathrooms over it.

  • @clonejones7955
    @clonejones79552 жыл бұрын

    Buy Canadian!🇨🇦👍

  • @Josh-mh3kl
    @Josh-mh3kl2 жыл бұрын

    will this work on a 1" rubber hose?

  • @GreggDistributorsLP

    @GreggDistributorsLP

    2 жыл бұрын

    Hi, Josh. For this product to be most effective, the manufacturer recommends the use of freeze protection heating cables only on pipes, metal or plastic. Thanks for watching!

  • @jefffloyd3480
    @jefffloyd3480 Жыл бұрын

    Cable need to be put on Bottom

  • @user-dv8ie8kk5l
    @user-dv8ie8kk5l8 ай бұрын

    😂

  • @isabelamateo783
    @isabelamateo7833 жыл бұрын

    Are wad ex

  • @stephensoles3773
    @stephensoles3773 Жыл бұрын

    The heat tape I bought at Can Tire instructions say not for use for a drain pipe ( not a constantly filled pipe, like a water line) Are these heat tapes different? The brand I bought also has a thermostat.

  • @GreggDistributorsLP

    @GreggDistributorsLP

    Жыл бұрын

    No, these are not intended to be ran inside of a pipe, they are for external use only.

  • @stephensoles3773

    @stephensoles3773

    Жыл бұрын

    @@GreggDistributorsLP I did not mean inside a pipe, but on the OUTside of a pipe that only has water in it intermittently - specifically the drain from my high efficient forced air furnace. The thermostat will be outside all winter (northern canada cold) so I expect the heat tape to be warm ALL the time keeping the drain (3/4" pipe) from freezing. Will having this energized all winter damage it?

  • @GreggDistributorsLP

    @GreggDistributorsLP

    Жыл бұрын

    No, using it in that application will not damage the product, that is what it is intended for.