Flow Test of an Electric Fire Pump

Тәжірибелік нұсқаулар және стиль

Performing the required NFPA 20 and 25 annual flow test of a small 500gpm horizontal split case centrifugal fire pump with an electric motor driver. There are several required items that are not covered in this video. This video is just to give you an idea of what is done during a fire pump flow test. Even after I cut some steps out of the video, it's still long. I added a timeline to help you find each step.
Timestamp
0:00 - Introduction
2:55 - PSA about NFPA 25 8.3.3.13
3:50 - Grease pump
6:00 - Calibrated gauges
10:44 - Tachometer
12:13 - Flow Chart
15:53 - Test header and hose setup
18:20 - Hose monster setup
22:23 - Test header control valve
22:35 - Start churn test
27:42 - Start 100% flow test
30:06 - 100% flow readings
31:41 - Start 150% flow test
35:17 - 150% flow readings
36:29 - Generator test at peak load
38:43 - Readings while on generator
40:37 - Conclusion

Пікірлер: 28

  • @FireSprinklerTech
    @FireSprinklerTech11 ай бұрын

    Please like and subscribe to help the channel grow. Feel free to leave a comment. I would like your input so I can improve the channel. Thanks for watching!

  • @jj13jh

    @jj13jh

    9 ай бұрын

    When testing do you have to close the valve to the main fire system..?

  • @FireSprinklerTech

    @FireSprinklerTech

    9 ай бұрын

    @@jj13jh NFPA 25 doesn’t require you to close it, but you can. If you decide to close it pay attention to where the sensing lines for both the fire pump and jockey are connected. It shouldn’t be an issue if installed correctly but I have had problems with this in the past.

  • @mohieldeen9140
    @mohieldeen9140Ай бұрын

    good

  • @tristanwilson286
    @tristanwilson2869 ай бұрын

    Always better to find out something’s wrong at peak flow in a routine test than in a fire when the fire department shuts off power to the building. Great choice to go back to NFPA recommended test procedure!

  • @sharonzelikovich4381
    @sharonzelikovich43812 ай бұрын

    When the pump on zero flow shut down the primary source of the power does not activate the secondary power source / generator? why did you need to get inside the settings of the transfer switch?

  • @fredhollinger
    @fredhollinger6 ай бұрын

    Good job on the explanation. When I'm testing fire pumps I will always inform the owners and if possible, their insurance company to get approval before performing peak alternative power test. After explaining the possibility of damage, though small, I have had some ask we do not perform that test. We still make sure the generator kicks on when simulating power loss just not always at peak. My experience over the years is that standards change. So before performing tests that could potentially cause damage be sure to cover all your bases and think through it before you do it. The potential damage will most always be blamed on the company performing the tests.

  • @kensheets5189
    @kensheets51896 ай бұрын

    good overview, thanks

  • @jmcguire5151
    @jmcguire51515 ай бұрын

    Yet another great video. I did pick up a few pointers. You mention the Bluetooth transducers . My company just got me a set of them. I've used the once so far, just haven't figured them out yet. I'm sure I'll get the hang of them this summer.

  • @FireSprinklerTech

    @FireSprinklerTech

    5 ай бұрын

    Nice, let me know what you think of them after you use them for a while.

  • @Mikefrom843
    @Mikefrom8436 ай бұрын

    This video has helped me out alot and im not just saying that. I run the diesel fire pump and electric fire pump every week/month at work and this has trained me on some conponents that i didnt know about. Just subscribed

  • @suzylarry1
    @suzylarry18 ай бұрын

    that new technology will be great for you guys testing , save you running time back and forth and als you can work those outside valves correctly !

  • @kpj9028
    @kpj90284 ай бұрын

    Well that amd in the case that they water mains do fail. At least you aren't finding out in an emergency.

  • @beckyb943
    @beckyb9438 ай бұрын

    we use a different type of grease on our pumps and electric motors. we use a die eletric grease on the motors

  • @brianeaton8905
    @brianeaton89058 ай бұрын

    -30 vacuum reading isn’t just for tank supply. You can pull vacuum on city supply mains and collapse the underground. Having tested fire pumps for the better part of 20 years I can get pretty damn close to zero on the city supply and listen for cavitation to prevent any damage.

  • @dannyspiker1549
    @dannyspiker154911 ай бұрын

    MAN A SET OF THE NEW SMALL HOSE MONSTERS WITH REMOTE STATION WOULD BE SWEET!!… Just a quick check to see if OUR bosses are watching!!…

  • @JohnSebeny
    @JohnSebeny11 ай бұрын

    Hmm, we don't run our generator when we churn test

  • @FireSprinklerTech

    @FireSprinklerTech

    11 ай бұрын

    You are not required to transfer to the generator during the churn test. You are required to during the annual flow test.

  • @jj13jh
    @jj13jh9 ай бұрын

    How do you test the a pump?

  • @FireSprinklerTech

    @FireSprinklerTech

    9 ай бұрын

    I’m not sure what you mean? That’s what I’m doing. I’m flow testing the pump to make sure it can pump the required amount of water.

  • @meljohniyoy2584
    @meljohniyoy25846 ай бұрын

    Hi Sir, May i know the specs of grease gun that u used? and the types of grease? Thanks a lot

  • @FireSprinklerTech

    @FireSprinklerTech

    6 ай бұрын

    I use Mobil Polyrex EM on the pump and electric motor. www.mobil.com/en/lubricants/for-businesses/industrial/lubricants/products/products/mobil-polyrex-em

  • @terrythurman5869
    @terrythurman586911 ай бұрын

    How many HP is that pump?

  • @terrythurman5869

    @terrythurman5869

    11 ай бұрын

    Ours is 75hp

  • @FireSprinklerTech

    @FireSprinklerTech

    11 ай бұрын

    That motor is only 25HP, it's a small pump.

  • @terrythurman5869

    @terrythurman5869

    11 ай бұрын

    @@FireSprinklerTech I work in maintenance at a 350000 sq ft distribution center. I handle the monthly testing on ours but we contract out the yearly testing. Nice video.

  • @mxslick50
    @mxslick507 ай бұрын

    Nice setup, too bad they used the worst motor...WEG motors are junk. Not what I'd want on a critical system. Edited to add: Your peak transfer test is totally invalid. By throttling the flow back, you lowered the current draw on the pump and completely voided the intent of the test. This is a serious issue, and hope you did change your proceedure after as you said you would. And IF a water hammer happened and caused damage, better to find out under test than during a fire.

  • @ryangardner9683
    @ryangardner96833 ай бұрын

    U need a helper