Feeder installation review

This #IAEINewsLive session is pre-recorded and is a review of an installation. This session will be the base of future sessions that will review in detail various aspects of the installation in regard to NEC requirements.

Пікірлер: 15

  • @ricopearce4127
    @ricopearce4127Ай бұрын

    Educational 👍

  • @user-he5mh4so1p
    @user-he5mh4so1p6 ай бұрын

    Thanks for bringing the code to the real world and interfacing it with this install. Good examples. A lot of AHA moments.

  • @ehammond30
    @ehammond30 Жыл бұрын

    Tom - Great educational example for the multiple NEC Articles at play here! Coming from an electrical engineering background, I have learned that a picture is worth a thousand code references... or however that saying goes 😄 Answers to your questions throughout the video: Q: 23:40 - What Section of the Code explains how many threads of a screw need to be engaged for a bond? A: NEC 250.8 Connection of Grounding and Bonding Equipment - Not less than two threads or secured with a nut (depending on screw type) Q: 36:10 - What Section in Article 250 relates to Objectionable Current on Equipment Grounding Conductor? A: NEC 250.6 Objectionable Current

  • @SB-dc9qb
    @SB-dc9qb Жыл бұрын

    Please keep this content up! GOLD

  • @D.Hozzie
    @D.Hozzie Жыл бұрын

    Just great stuff Tom. Thanks.

  • @educationpower1823
    @educationpower1823 Жыл бұрын

    Tom nice job Robert from Omaha Great to see you here in Sioux Falls

  • @Money-yj4wg
    @Money-yj4wg6 ай бұрын

    Great stuff

  • @TheArtOfConduitBending
    @TheArtOfConduitBending Жыл бұрын

    Amazing

  • @eraydin41
    @eraydin41 Жыл бұрын

    nice content

  • @joewebb4836
    @joewebb48369 ай бұрын

    I think I would have made the secondary sealtite a little longer and strapped it to the transformer pad as I would be afraid of some building maintenance guy stepping on it . Also, the pipe with LB out of the right end of the gutter should be supported some how (maybe its not complete) .

  • @davem5392
    @davem5392 Жыл бұрын

    At the 42 minute point should there be the bonding of the neutral at the first disconnect since it a new (separately derived) system

  • @tektonelec4695
    @tektonelec4695 Жыл бұрын

    Hi Tom, your right this is phenomenal stuff.. Question for you when you were sizing the secondary OCP you used 175%, and went to the next size up OCP. Could you please tell me so that I know where you found 175%. I checked the 450.3(B) table and did not see it. Please help me understand this better.

  • @rundetoured
    @rundetoured Жыл бұрын

    Can you explain why on calc. the fault current on secondary that you divided voltage by z% ?

  • @user-ll1vj7qo1m
    @user-ll1vj7qo1m4 ай бұрын

    250.104(D)1 and 2. Separately derviced system must be grounded to metal water pipe and structural steel. No requirement for ground rods needed and in fact is not providing a effective return path and should be removed immediately.