Boiler Aquastat Relay Troubleshooting and Control Wiring!

In this HVACR Video, I go over the Boiler Aquastat, How it Works, Troubleshooting, and Control Wiring. I power the relay and follow the voltage through to show how it works and what should happen! Supervision is needed by a licensed HVACR Tech while doing this as Experience and Apprenticeship garners Wisdom and Safety.
Tools Used In The Video
UEI DL479 Multimeter With Temp Sensor amzn.to/2jtsUbJ
Magnet Jumpers- amzn.to/2PyKPQZ
▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
Our Related Videos/Articles
• Boiler Aquastat Relay ...
• Wiring a Heat Pump The...
• Wiring a Thermostat, F...
• Boiler Training Class,...
▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
Our HVACR Educational Books, E-Books, Workbooks, Cards, Posters, and PowerPoints:
All Our Educational Products on Our Site: www.acservicetech.com/store
All Our Educational Products on Amazon: amzn.to/48pDd82
Mini Split Book and E-Book on Our Site- www.acservicetech.com/mini-sp...
Mini Split Paperback on Amazon- amzn.to/3ytHJSs
Mini Split Paperback on TruTech Tools- www.trutechtools.com/BooksGui...
Refrigerant Charging Book and E-Book: www.acservicetech.com/ac-book
Refrigerant Charging Paperback on Amazon: amzn.to/46xTeHf
▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
Our HVACR Online Resources!
Our HVAC Calculators: www.acservicetech.com/hvac-ca...
Our Newest Articles: www.acservicetech.com/articles
Try our HVAC/R Quizzes! www.acservicetech.com/quizzes
Our Other Resources: www.acservicetech.com/resources
▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
Tools Used in Our Videos!
Tool Links on Our Site: www.acservicetech.com/tools
Our Tool List on Amazon: www.amazon.com/shop/acservice...
Support the Channel by purchasing tools through TruTech Tools!
Use this link www.trutechtools.com/?aff=8
Save 8% at checkout using code "acservicetech"
▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
Follow Us On Our Social Media & Podcasting Channels!
Patreon: / acservicetech
Facebook: / acservicetech
Instagram: / acservicetech
X: / acservicetech
LinkedIn: / ac-service-tech-llc
Tiktok: / acservicetech
Spotify: open.spotify.com/show/74KXLz5...
Apple Podcasts: podcasts.apple.com/us/podcast...
▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
⚠️ Disclaimer:
Information in this video is intended for educational purposes only. Any work related to the topics in this video should be performed by licensed technicians or by apprentices under the supervision of licensed technicians. AC Service Tech LLC is not responsible for any possible damages or injuries caused by the use or misuse of any information provided. ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
#hvacr #hvacr #hvactrainingvideos #hvactraining #hvactraining101 #acservice #acservicetech #wiring #boiler #thermostat #aquastep #wire #wiring #controlboard #circuit #circuitboard
▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal.

Пікірлер: 233

  • @acservicetechchannel
    @acservicetechchannel6 жыл бұрын

    Tool List- www.amazon.com/shop/acservicetech Support- www.patreon.com/acservicetech For those that are looking for the tools used in the videos: (Links in the Description Section)

  • @mqira00

    @mqira00

    5 жыл бұрын

    Great video. Very much appreciate your time and effort. Just wanted to point out the reason you dont read 24v from B2 to TV is they are both on the common,....the same leg/potential.

  • @mackenziegray2090
    @mackenziegray20902 жыл бұрын

    Thanks to this video I have outsmarted my trainer. The call I was on with him had voltage and calling for heat. The relay was pulled in but was not passing power to the limit. He believed the vent damper was bad. It was horizontal and wasn't open. He ordered the new damper and installed it. Unit still never came on. I got a pair of jumpers and hooked them to Z and top of the limit, the boiler fired up.... he was pissed.

  • @samjg1
    @samjg14 жыл бұрын

    Best video I've seen explaining the workings of the aquastat. Thank you.

  • @Melvinschroeder
    @Melvinschroeder4 жыл бұрын

    Your knowledge and communication skills make you videos the best at helping us to understand what we are looking for!

  • @acservicetechchannel

    @acservicetechchannel

    4 жыл бұрын

    Thank you Melvin!

  • @WaltonStinson
    @WaltonStinson4 жыл бұрын

    Thanks for the verbal diagram of the operation. I couldn't find a schematic of this unit and now can draw one myself based on your excellent explanation of this circuit.

  • @acservicetechchannel

    @acservicetechchannel

    4 жыл бұрын

    Awesome Walton, thanks!

  • @geoffreyahmann320
    @geoffreyahmann320 Жыл бұрын

    Fricken life saver man!!!! Just trying to upgrade the thermostat from an old turn dial to a programmable digital. Thermostat manual made it seem so easy, followed it to a T and got nothing! Read both boiler and thermostat manual, scoured Honeywell's site, scoured Google, but had no clue what to look for. Stumbled on your videos and now I understand exactly what is going on! Great simple teaching and explanation! Thank you so much!!!!

  • @andreagate542
    @andreagate5423 жыл бұрын

    Great Vid!!!! Came across one of these well in the field today and had a few questions that I did not get an answer..... you nailed it for me🙏🏾🙏🏾🙏🏾

  • @uslandmanagement1
    @uslandmanagement15 жыл бұрын

    Best video I have seen in a long time. Great explanation, very knowledgeable !

  • @acservicetechchannel

    @acservicetechchannel

    5 жыл бұрын

    Thanks USlandmanagement1!

  • @rthinds
    @rthinds Жыл бұрын

    Holy smokes! This is a great video! My boiler took longer and longer to fire up until one day it just didn't. Not wanting to spend $1000 or more on a service call, I found this video and followed the path of the voltage to the Z terminal, which was not conducting any to the W terminal (despite calling for heat) and, by extension, none to the T. Shutting off all electricity, I unscrewed the Z terminal and out-popped a small piece of paper in the perfect shape of the screw head. Obviously whoever installed mine decades ago just ripped a paper tab off instead of removing it. It was probably "barely working" for decades! No wonder it took an hour or more to "fire up" in the fall. Once I tightened the Z terminal (and all the other terminals) down - everything is working perfectly! Thank-you so much for such a detailed video!!

  • @davidallen4804
    @davidallen4804 Жыл бұрын

    Great explanation of how the high and low voltage work under what we se o the surface of the control.👍

  • @Pretzel114
    @Pretzel1146 жыл бұрын

    thanks for the reply Acservicetech. You always help me out.

  • @acservicetechchannel

    @acservicetechchannel

    6 жыл бұрын

    Glad to help Nick!

  • @christopherlarson3136
    @christopherlarson31364 жыл бұрын

    Terrific, well explained, thorough, and most of all helpful video. Thank you for taking the time to create and share this! I was able to diagnose a High Limit cutoff failure on my L8148e.

  • @androidresults
    @androidresults3 жыл бұрын

    Fantastic video! My niece just bought a new house and her thermostat was wired incorrectly. This video was exactly what I needed to fix her problems! Thank you!!

  • @acservicetechchannel

    @acservicetechchannel

    3 жыл бұрын

    Great to hear!

  • @deependz3231

    @deependz3231

    2 жыл бұрын

    @@acservicetechchannel "AC Service Tech LLC AC Service Tech LLC 1 year ago "Great to hear!".................That's you responding only to self praise, and anyone who had required a technical question be damned, pretty pathetic on your part. Next time you post anything, do everyone a favor who might waste their time asking a question, turn the comment section OFF.

  • @beemerkon
    @beemerkon2 жыл бұрын

    How can anyone put a thumbs down this video

  • @PBS-nm1uu
    @PBS-nm1uu3 жыл бұрын

    love your videos, still do not understand how you understand the sequence so well, keep them coming.

  • @gyver471
    @gyver4715 жыл бұрын

    Great instructions and explanations.

  • @wildgoose6596
    @wildgoose659610 ай бұрын

    Without this video, I would have had to call for what I am sure would have been a very expensive repair as there are unfortunately so many "parts changers" out there. Thanks! We have heat again! I just needed to know these basics, and I was able to diagnose my newer and slightly different L8148E. Way better that other videos out there!

  • @MikeJamieGavin
    @MikeJamieGavin Жыл бұрын

    Fantastic video. It's pretty much the same troubleshooting the L8148A, except it doesn't have the 24V transformer. All the voltages are 120V on the L8148A. You'll need a separate 24V transformer for your thermostats. Adding this info so that others can find if if they are trying to troubleshoot at l8148a since it's pretty much the same thing.

  • @kennyw7453
    @kennyw74536 жыл бұрын

    Great demo and explanation, as usual.

  • @acservicetechchannel

    @acservicetechchannel

    6 жыл бұрын

    Thanks Kenny!

  • @hermansummers487
    @hermansummers487 Жыл бұрын

    Love the detail in your video

  • @dougjones4987
    @dougjones49874 жыл бұрын

    Great explanation, thanks a bunch this really helped me out.

  • @acservicetechchannel

    @acservicetechchannel

    4 жыл бұрын

    Glad to help Doug!

  • @michaeldower4335
    @michaeldower43356 жыл бұрын

    Great video. Very informative, thank you.

  • @acservicetechchannel

    @acservicetechchannel

    6 жыл бұрын

    Thanks Michael!

  • @fern284
    @fern284 Жыл бұрын

    Great video, very thorough

  • @jimmyung3212
    @jimmyung32126 жыл бұрын

    Thank You for the detail. You are a very teacher.

  • @acservicetechchannel

    @acservicetechchannel

    6 жыл бұрын

    Thanks Jimmy!

  • @jimmyung3212

    @jimmyung3212

    6 жыл бұрын

    Hi could you make a video on economizer.

  • @ingridhen619
    @ingridhen6193 жыл бұрын

    You are a LifeSaver! Thank you so much!

  • @acservicetechchannel

    @acservicetechchannel

    3 жыл бұрын

    You're welcome!

  • @amirmf1814
    @amirmf18143 жыл бұрын

    man you are really the best for training . appreciate if you put up some video about taco and tekmar control for boiler. again thanks . merci

  • @Sfey3386
    @Sfey33863 жыл бұрын

    Extremely helpful. Thank you

  • @acservicetechchannel

    @acservicetechchannel

    3 жыл бұрын

    Glad it helped Steve!

  • @PBS-nm1uu
    @PBS-nm1uu Жыл бұрын

    this is a great explanation, thanks

  • @devinmccloud
    @devinmccloud5 жыл бұрын

    Thank you so much for sharing this info. My Becket AFG burner would not start the blower and fuel pump. I thought maybe the blower motor was shot. I could feel the relay box vibrating.The Honeywell Aquastat Relay was humming but the motor and Becket burner would not start when turned on. The light indicated that it was locked out. The relay was stuck so I pushed it a few times. I then turned on the burner and for the first time it started the motor, burner and circulating pump. Hope this info helps someone else.

  • @acservicetechchannel

    @acservicetechchannel

    5 жыл бұрын

    It may have been out of alignment or the contacts were pitted and not making goo contact, thanks Devin!

  • @bigthey1827
    @bigthey1827 Жыл бұрын

    Great video 👍

  • @rcytb
    @rcytb2 ай бұрын

    Very helpful. Thank you!

  • @gyver471
    @gyver4714 жыл бұрын

    Great information can you do one of these for the new hydrostat controls.

  • @dritanshabani6396
    @dritanshabani63964 жыл бұрын

    What a awesome video very informational

  • @acservicetechchannel

    @acservicetechchannel

    4 жыл бұрын

    Thank you very much Dritan!

  • @mp-mh3wf
    @mp-mh3wf5 жыл бұрын

    Thanks any way for your help on the question I had on my boiler it was the aqua stat

  • @acservicetechchannel

    @acservicetechchannel

    5 жыл бұрын

    Thanks m p!

  • @patohara8430
    @patohara84306 жыл бұрын

    Very good video. Thanks.

  • @acservicetechchannel

    @acservicetechchannel

    6 жыл бұрын

    Thanks Pat!

  • @marvincarranza096
    @marvincarranza0965 ай бұрын

    God bless you brother !! 🦾

  • @billwatson3713
    @billwatson37133 жыл бұрын

    Excellent video

  • @acservicetechchannel

    @acservicetechchannel

    3 жыл бұрын

    Thanks for the visit

  • @rickychavez1473
    @rickychavez14733 жыл бұрын

    Nice!!! good explanation 👍👍 👍

  • @acservicetechchannel

    @acservicetechchannel

    3 жыл бұрын

    Glad you liked it!

  • @jashua2089
    @jashua20892 жыл бұрын

    Thank you 🙏

  • @hvac01453
    @hvac014535 жыл бұрын

    At 3:40 it appears you in fact DO have voltage on the contact on the right , like 26 or 27... or maybe you didn’t let the meter Seattle down. That’s the one hing I do prefer about analog meters, the needle would swing... good explanation on its workings.

  • @andreaalcalde7458
    @andreaalcalde74584 жыл бұрын

    Hi, thanks for the video. Our transformer started smoking. Is it possible to replace the transformer only? Or do we need to replace the whole system for the aquastat

  • @FigGolf
    @FigGolf2 жыл бұрын

    My thermostat intermittently loses power usually in the middle of the night or when I'm not at home (both are not very good times). My Google Nest Thermostat will show a no power condition making me believe that the transformer on my L8148E is going bad. I will have to check for loose connections, but when I pulled on the wires they seemed to be tight. The unit is over 17 years old, so I had a new one ready to go. Thanks for the video!

  • @samuelferrer805
    @samuelferrer8053 жыл бұрын

    thanks for the video, I have the L8148E, and I want to change my thermostat for the RTH6580WF. I only use the heat and my old thermostat works with two wires. where you should connect the wires for the other thermostat. Thanks

  • @jcstevegigs
    @jcstevegigs4 жыл бұрын

    Great video. My boiler at my rental has a summer/winter hookup. The tenant says heat works fine but that the hot water is hot, but not like it used to be. She says it’ll get cold for a little and then warms up after a few minutes. I guess if the heat works then the problem would be the mixing valve? I’m assuming the boiler is kicking on to supply heat but NOT kicking on when running the hot water? Any ideas? Thanks.

  • @uslandmanagement1
    @uslandmanagement15 жыл бұрын

    Thank you very muck

  • @acservicetechchannel

    @acservicetechchannel

    5 жыл бұрын

    Thanks USlandmanagement1!

  • @smidi0924
    @smidi09243 жыл бұрын

    Great video! Does both jumper are connected from your voltage tester or separately? Thank you

  • @arielhernandez2911
    @arielhernandez29113 жыл бұрын

    How come at 3:56 time frame when you tested voltage from b2 to w you had 22volts if that jumper isn’t hooked up wouldn’t it be zero volts thanks video are so helpful

  • @olderrol1968
    @olderrol19686 жыл бұрын

    How do you check the relay. What wire connections do you check. Can you illustrate like how you showed how to check the Transformer?

  • @adzar4148
    @adzar41482 жыл бұрын

    Great video.I have the bad relay that when i call for heat does not get sucked in when i push it down with a wood stick the system start working.it’s any way that relay can be fixed Thanks

  • @elijahgoodman3140
    @elijahgoodman3140 Жыл бұрын

    Great video! Question, due to the high limit cutting off the burner @ 180 degrees or so, the thermostat can still be calling for heat correct? If this is the case, then the burner will cycle on and off on high limit until thermostat is satisfied, or am I missing something?

  • @pubchat2913
    @pubchat29133 жыл бұрын

    Awesome vid thank you. Where would the inducer motor be connected? P.s I got your AC book, amazing. Do you have one for the heating season too?

  • @smidi0924
    @smidi09243 жыл бұрын

    Goog morning I have relay switch honeywell R845A( which is # 1,2,3,4, 5&6 and T-T). Do i need to follow the same test you did to check if my relay works before i wire it. Thank you.

  • @smitty03281964
    @smitty032819643 жыл бұрын

    I have Aquastat L8148G, which I don't see anywhere but it's almost identical to this L8148E except that it doesn't have the Z to W connection. It's actually set up TV--T--Z. My question is from the thermostat does it matter whether the common go on TV or T. Also I don't have any power on the temp controller, but my gas valve open and closes. I also notice that it heats the water up to 230 degrees, maybe even 240. My first issue with that is why it doesn't have power. Everything else works as it should. It's been that way since the early 90's. Recently I had a problem with no heat and took the Aquastat apart and found a frayed wire that was touching the outside of my transformer. I was actually getting 20 volts on the outside of the transformer. The relay was sticking. Taped up the wire and now I don't have the relay sticking, or the 20 volts on the outside of the transformer. After watching your very great video. I'm going to go look the entire system over.

  • @powerram92
    @powerram92 Жыл бұрын

    my relay just melted n was wondering if any other testing should be done once i replace the relay so i know it wont melt again.

  • @jeffhopkins979
    @jeffhopkins979 Жыл бұрын

    Great video, I have the L8148E aquastat relay. My boiler previously heated up to 180 and shut off, now it is heating up to 200 before it shuts off. There is a stationary arrow on the side of the temperature sensor that I assume indicates where the temperature dial should be set and mine is pointing to 180. The circulating pump is circulating and does stop when the burner kicks off at 200. I can only think that the temperature sensor or the Thermopile that sets in the well has gone bad. Is another option that might be causing this issue? I assume that I need to replace the entire aquastat relay as I had not found any information of people only replacing parts of the aquastat relay. Thank you for your help.

  • @gyver471
    @gyver4715 жыл бұрын

    Does it matter if different probes touch different screws? Like at one point the red touched l1 but then you switches and it touched b2. I ask because I don’t want to short anything out.

  • @uncle_mike
    @uncle_mike3 жыл бұрын

    I have the Honeywell L8148A attached to my boiler. The high limit works fine but the boiler will not fire when the water temp is low. Is there an existing low limit or "limit range" on the relay that I missed or should test? Thanks in advance...

  • @kennethdavis5077
    @kennethdavis50773 жыл бұрын

    Is it possible to wire a Nest thermostat to this aquastat . Where would I connect the common ?

  • @AkA-me-Kenny2
    @AkA-me-Kenny24 жыл бұрын

    What might be causing the oil hydronic burner, to once it reaches the high limit temp. and shuts down, it immediatily fires up again before you could blink an eye or take a breath? Three Facts, 1- boiler high temperature has been reached, and 2- there is no call for circulator to run, 3- no domestic water is being used at the time! What should I be looking for? Thank you for your help!!!

  • @jls1337
    @jls1337 Жыл бұрын

    Can you recommend how to test the high limit dial? I get continuity between the tow leads (B-R) but when I check voltage between that B screw where the blue wire attaches and B2 I only get 12V. The burner doesn't turn on. I get 0 volt between B1 and B2. And if it went bad, can it be replaced or does one have to get a whole new aquastat?

  • @jamesdago13
    @jamesdago132 жыл бұрын

    I have a L8124A, C using a nest and trying to do an add a wire kit, is there no constant on these boards for my smart thermostat?

  • @Kevin-to9gq
    @Kevin-to9gq Жыл бұрын

    Thanks man, I like the way you teach. You have a gift... I need help with my L8124A regular for C1 C2 . I am checking the voltage on C1 and neutral C2 and it reports back 13.42 volts when I jumper the thermostat connection. Is that the correct amount of voltage that it is reporting? Issue: circulator pump not activating when furnace is fired up and on. when I jumper L1 and C1 as a test, it works fine with no issues. I am focusing my troubleshooting on the honeywell relay that you are displaying next to the multimeter (not sure what that relay is called) Im so close to fixing this thing man and its getting cold.......any suggestions? I will look over your vid again, maybe I missed something in regurads to cleaning contacts etc...

  • @gjones5153
    @gjones51533 жыл бұрын

    I have this controller on a castiron powervent boiler also using a taco SR503 switching relay. my problem is that when the thermistat is calling for heat the taco sends power to c1,c2 which also send power to the blower vent motor. When the high limit shuts off the boiler and the thermistat still calling for heat the blower motor continues to run sucking warm room temp out of building. this continues to short cycle until the thermistat is satisfied. Is there any way to use the high limit to shut off the blower motor

  • @KeepItReal1973
    @KeepItReal1973 Жыл бұрын

    Hey there. I came across this video and found it very informative but I have a question that I hope you can help me with. First off my aquastat works fine, it turns on when needed and fires up the boiler but I don't seem to have any 24v reading from the B2 to any connection from the Z W or T. My volt meter is working fine too because it reads a car battery no problem. Any ideas as to what is going on? My aquastat looks exactly like the one you have in the video.

  • @forevertwowheels717
    @forevertwowheels717 Жыл бұрын

    I have a honeywell hydronic zone valve control panel. In the panel it has 2 wire connection for boiler. Do i connect that to the T & TV on aquastat.

  • @viper22304
    @viper223045 жыл бұрын

    Thanks for the video.. question: a loud humming sound is going out from the transformer? This mean I need to replace whole relay? Is it bad if i leave it running until replacing it?

  • @acservicetechchannel

    @acservicetechchannel

    5 жыл бұрын

    They may get a little louder as they get older and if the resin wears down. It just depends on how loud really but at some point it would need to be replaced, thanks!

  • @jasonschroeder8671
    @jasonschroeder867110 ай бұрын

    So what's the issue if the relay isn't getting sucked in? Checked everything I could without tearing apart the switch, even replacing batteries in the thermostat control in the living room, and everything seems good. I can manually push it and it works fine so I assume contacts are functional. Just replace it or somewhere else to look?

  • @Xbreaselx
    @Xbreaselx4 жыл бұрын

    Same concept for millivolt aquastat and B2 still common or would b3 be common?

  • @Pretzel114
    @Pretzel1146 жыл бұрын

    Hi Acservicetech! Thanks for the video. I been waiting for this one. One question. The temp dial on this single aquastat, is that the same as the red dials on the triple aquastat? Do they serve the same purpose? Thanks again.

  • @acservicetechchannel

    @acservicetechchannel

    6 жыл бұрын

    Yes it is like the red dial except this is always just the high limit. You can add a low limit to this externally. Also if you see the two red dials then that is a high and low limit so your burner can heat up the water before circulating, thanks

  • @ricoz8649
    @ricoz8649 Жыл бұрын

    Is it common for failure of the temperature sensor to expand the bladder under the temperature dial and not close the switch? If so is this a part that can just be replaced?

  • @12jason223
    @12jason2235 жыл бұрын

    Awesome video, helped my identify the issue with my aquastat. Is it possible to replace just the circulator relay or does the entire aquastat need replaced?

  • @acservicetechchannel

    @acservicetechchannel

    5 жыл бұрын

    Usually you need to replace the whole aquastat, thanks!

  • @firstjohn26

    @firstjohn26

    4 жыл бұрын

    Jason, I run my circulators on a hot circuit all winter to get around the relay and it works fine. I retain the relay only for the 24V to the gas valve.

  • @BelleRiverHeating
    @BelleRiverHeating6 ай бұрын

    Does the temperature sensor actually sit in hot water or just into a hole on the side of the boiler?

  • @KamberBCT
    @KamberBCT Жыл бұрын

    Don't know if you'll even see this since the video was posted a while ago but I have an Aquastat Relay Type L8148J and unfortunately only have a R and W wire going to the thermostats on the Upper and Lower Floors. I am trying to add a wifi thermostat to make scheduling easier but don't have a C connection. What would I connect to make this work or am I out of luck? Having a hard time getting an electrician to come out since it is such a small job.

  • @Batalia122
    @Batalia122 Жыл бұрын

    Hello, hopefully you can answer this question. My boiler has been turning on without the thermostats connected and I think it's the Aquastat. When I remove the Thermostat wires from the Aquastat both or the white the boiler doesn't turn on but when they are connected it turns on. I've cut the wires to the Thermostats so I know they aren't connected. Do you think the Aquastat is bad and bridging the wires without the thermostat? Thanks

  • @markgattinger3958
    @markgattinger3958 Жыл бұрын

    I have a L8148E and need the relay on that board. I'm only finding the entire board and box complete. Is that relay available anywhere?

  • @jackpast
    @jackpast6 жыл бұрын

    Nice one, Craig. I’m guessing on the wires going to the thermostat that the 24 v. common is not run to the thermostat? If not, makes trouble-shooting harder when checking for 24v at the thermostat.

  • @acservicetechchannel

    @acservicetechchannel

    6 жыл бұрын

    Yeah typically you have a battery operated stat or mechanical due to the VA size of the transformer in the aquastat, thanks Jack!

  • @gerardtom
    @gerardtom3 жыл бұрын

    Can a aquastat lock out the burner and put the light on the burner button?

  • @EnjoyCalculus
    @EnjoyCalculus2 жыл бұрын

    Craig, can you please do a boiler sequence of operation video? I have yet to find one

  • @deependz3231
    @deependz32314 жыл бұрын

    What causes a oil boiler to continuously run, even with the relay in the open position (non energized)? In other words, you can switch the power on/off but relay doesn't move either way, stays in open position, power on, boiler starts.

  • @zeeshawn15
    @zeeshawn152 жыл бұрын

    Do I put T Stat's red(r) to TV or T? Where does the white(heat) from T Stat go? TV or T? Some Aquastat says TH instead of TV right? Tv and T both are powered I believe but which one is for T stats power and which one is for T Stats (heat)?

  • @erikengquist2216

    @erikengquist2216

    Жыл бұрын

    My thermostat's white (heat) wire is connected to TV, and red (power) is connected to T.

  • @zekeilleyva1735
    @zekeilleyva1735 Жыл бұрын

    Do you have a part number for the thermostat switch(you refered to it as a "relay")? Is it a universal part as long as it has the 120 v / 24 voltage capability?

  • @SeongJinShim
    @SeongJinShim4 жыл бұрын

    Can I use Honeywell L8148E instead of L8124E?

  • @michaelmace924
    @michaelmace924 Жыл бұрын

    Question: I have a customer that's been using me for a long time, 20-22 yrs. He has an older Columbia boiler that needs an AquaStat but other than that it's in perfect shape. The transformer blew out, replace the AquaStat & be done. Normally this is the case, but this boiler is old and the damper is old and AquaStat is old. The damper doesn't have the molex plug on the end of the wires, and the new aqua stat has the molex plug in it. I'm trying to save the old man money, he's on a fixed income. Is it gonna be a mission to replace the transformer in the AquaStat or is it pretty much just unsolder then resolder?

  • @Arieldny
    @Arieldny2 жыл бұрын

    hi can you make a video how would you wire this to a 2 or 3 Honeywell system (4 wires, thanks)

  • @danieldummett3731
    @danieldummett37316 жыл бұрын

    Hey quick question regarding gas valves. On old furnaces with the combination gas valves if it says mv on it that means that the main gas valve only opens when 24v dc from the pilot flame is powered to it through the t-stat? Or would it still work on a 24v transformer system?

  • @acservicetechchannel

    @acservicetechchannel

    6 жыл бұрын

    Hey Daniel, the pilot valve must be opened first before the gas even gets to the main valve. Have you checked this video out yet?- kzread.info/dash/bejne/aaFpvKavf9K8p7g.html -- also I have written 32 articles and have videos over on patreon.com/acservicetech if you are interested. The access is the community level at $3 per creation but you can set a monthly max at $3 per month. It is also something that can be canceled easily. Anyway just letting you know and it also includes email q/a as well thanks

  • @jimbobigdude
    @jimbobigdude6 жыл бұрын

    Thank you for taking the time to show how this is supposed to work. In my case, the circulator sometimes runs intermittently, so I know it's not frozen. How can you troubleshoot the aquastat when the circulator IS operating correctly? Or do I have to troubleshoot it when the circulator doesn't turn on? I'm thinking that either the relay is bad in the aquastat or the temp control. But if the relay operates sometimes and does turn on the circulator, could it still be bad? Maybe just changing the aquastat completely would take care of both possible issues within the aquastat? It's a l6006a Honeywell. Thanks again.

  • @acservicetechchannel

    @acservicetechchannel

    6 жыл бұрын

    Unfortunately, we usually need to have the system problem occurring while checking readings in order to determine what the problem is. If you don't have another circ or zone controller and the wires are providing a good 24-29v under load then it may be the aquastat, thanks

  • @jimbobigdude

    @jimbobigdude

    6 жыл бұрын

    Thank you for the quick reply. I'll give that a shot...single zone, one circ. Thanks again!

  • @lalaniathielen8917

    @lalaniathielen8917

    2 жыл бұрын

    Good question

  • @MikeJamieGavin

    @MikeJamieGavin

    Жыл бұрын

    For anyone else reading this years later, I had that exact problem. My issue was the solder joint under the relay had cracked. So I wasn't getting 120v at the circ pump terminal, but the relay was closing. The contacts checked out good so I checked for continuity (with power off) from the relay to the C1 and had no continuity no mater what position the relay was in. Pulled the board and saw the crack. Resoldered it, checked again, and was back in business.

  • @jasonschroeder8671

    @jasonschroeder8671

    10 ай бұрын

    ​@MikeJamieGavin so what happens when you manually close the relay and it fires up? My relay won't close at all. It's humming to get going, but no closure of the relay.

  • @learndaanswers3066
    @learndaanswers30664 жыл бұрын

    7th boiler mechanic who can't solve the issue of why my boiler aquastat will not shut off my steam boiler from running constantly. They disconnected the house thermostat but soon as the water got cool the boiler started up and ran which heated the whole house until the tenants turn off the emergency switch. Is this something that can be fixed or is the company just not knowing. They changed the aquastat three time already....can you suggest maybe a new type of aquastat?

  • @jetmike747
    @jetmike7475 жыл бұрын

    Awesome video. So if I understood correctly, if you were to get a thermostat that required a C wire, could the C wire be hooked up to terminal B2?

  • @acservicetechchannel

    @acservicetechchannel

    5 жыл бұрын

    I wouldn't add an extra load onto this setup. The transformer may not be upsized to handle the extra thermostat load, thanks

  • @TheSchwartz36

    @TheSchwartz36

    5 жыл бұрын

    @@acservicetechchannel im new to this! how would i add an extra load ?

  • @dannyolivares6757

    @dannyolivares6757

    Жыл бұрын

    Have the same concern right now, were you able to run the common on B2 without any issues??

  • @justjon907
    @justjon90711 ай бұрын

    Are you able to replace just the relay?

  • @markbrassette3406
    @markbrassette34065 жыл бұрын

    Awesome video, thanks! Quick question ... so I need 24VAC for Ecobee smart thermostat. Looks like I can get that from B and Z terminal for continuous power. Ecobee support said I I need a separate transformer to power the stat, and not to use the one on the boiler. This is running 3 zone valves then signal back through end switches to fire burner etc? Any reason for that you know of we'd need an extra transformer?

  • @acservicetechchannel

    @acservicetechchannel

    5 жыл бұрын

    It is so that you don't go over the VA of the transformer on the board. You can just run a transformer from the main 120v and come off that to power the stat to be safe. Make sure the transformer is inside of an electrical housing and that no 120v wires are exposed, thanks

  • @stifflers69mom1

    @stifflers69mom1

    5 жыл бұрын

    Yes I just went through this myself the problem is the the transformer in the honey well is not meant to run the burner,rely AND your new thermostat it over loads it and could possibly shorten the life ...just listen to this guys advice and buy a separate transformer to power the thermostat

  • @jameseiden2340

    @jameseiden2340

    3 жыл бұрын

    I don’t get it it’s only a thermostat how many VA is going to be

  • @lolsimon

    @lolsimon

    2 жыл бұрын

    Hi I replaced an old one with a new model today and when I switched on the boiler I had 24 volts at b1 and b2 while the thermostat was calling for heat. After a minute or so, b1 and b2 was reading less than 10 volts. Circulator was still running fine and the transformer was still outputting 24 volts. Do you think there is a short somewhere that caused the relay to go bad? Thank you

  • @tentman4fun
    @tentman4fun9 ай бұрын

    What do you hook to buner

  • @brink1123
    @brink1123 Жыл бұрын

    What aquastat supersedes that aqua stat because I can not find one just like that I'm looking at a 1265

  • @shelby50411
    @shelby504116 жыл бұрын

    Great video.....is the relay within the aquastat replaceable?

  • @acservicetechchannel

    @acservicetechchannel

    6 жыл бұрын

    No not unless it was unsoldered off the board, thanks

  • @santanapati7418
    @santanapati74184 жыл бұрын

    I have a question hope some one can help, i got a new relay box but I don’t get a reading of 24v on B1 but i do have 24v on the orange wire wend i turn on my thermostat, i got my burner to start up by connecting b1 directly to the orange wire . Help pls

  • @zoglchaim5634
    @zoglchaim56345 жыл бұрын

    what connects W to T? is that a resistor? by me, its open... does it mean that resistor burned out?

  • @carlcarl9290
    @carlcarl9290 Жыл бұрын

    Just put a brand new relay and the circulator stil not working. (There is no power coming out of aqua stat to circulator) I have connected the circulator with direct power and runs properly. What could cause this issue?

  • @integrity5264
    @integrity52642 жыл бұрын

    Hi Craig, love your subjects, your a great teacher. I know this is an old post but I was just wondering what the differential is on this high limit control? Is it 10 degrees ? Thanks for sharing your knowledge . I have your book, great information their.

  • @geojor
    @geojor6 жыл бұрын

    could you explain how a L8124A triple aquastat works in a combination wood/oil hot water boiler, it also has an isolation relay ...

  • @acservicetechchannel

    @acservicetechchannel

    6 жыл бұрын

    Are you talking an outdoor wood boiler connected to the return side of an existing oil burner with a plate heat exchanger?

  • @geojor

    @geojor

    6 жыл бұрын

    no, a combination wood/oil New Yorker boiler in the basement of a house ...

  • @christinestrahan8727
    @christinestrahan87275 жыл бұрын

    I have a Honeywell Aquastat relay #L8148B for my gas furnace. I had a electrician hook up a plug to my power switch so I could use my furnace with a generator if I lose power. We had power to the relay but when we tried it with the generator the furnace would not work. We removed the generator and had to wait about a half hour to the furnace would run. Is there any safety delays in the relay or any idea what’s going on.

  • @acservicetechchannel

    @acservicetechchannel

    5 жыл бұрын

    That doesn't sound right. Is it possible, the power is feeding into this backwards with the hot being common and common the hot accidentally?

  • @dvonpache
    @dvonpache3 жыл бұрын

    Correction @ 05:30: the 24V line is in the RED wire and that's why @ 06:30 you've clearly tested ~(21 - 24)V (while you were saying "we have nothing") in the BLUE and B1 wires because the aquastat was closed. So annoying to have expert tell you something when I see it with my own eyes it isn't so and no errata was issued...WTF?