If a digital input confirms flow, does it send voltage voltage out and when it gets it back, it confirms it is going?
Yes, you are right.
Thank you very much for this video, lot of my doubts are resolved. Minimum differential pressure requirement is across inlet and outlet?
Yes in order the spring to work properly. You can measure it using the pressure ports available on PICV.
Brother if Bacnet mstp is used with almost 8 to 10 vfds (objects) and all are in loop with each other, and if one of them is not working, will it effect the status on bms screen ? The ON OR OFF status on screen ?
Hi if one of the VFD is offline, it might show error on the BMS workstation depending on the configurarion. All other VFD points shall be normal.
It is similar to scada
Hatts off
Could you please provide you whatsapp no. to connect with you online to discuss further.
Hi Rehman, Good to watch your videos on how BMS works, what protocols used, field devices, IO details, DDC Panels and controllers. Need your support to understand the configuration of system protocols like which Microsoft Windows Server used, which Microsoft Windows OS for client used and which are all BMS softwares are available in the market.
Hindi me video banao
BMS operator book ha
HVAC book 📚
Nice
I have submitted the form 👍
Thank you. This was very helpful in understanding how BACnet IP works, especially in different IP subnets.
जब इंगलिश में दिक़्क़त है तो हिन्दी में वीडियो बना दो। मतलब सीखा रहे हो की देख कि ख़ुद याद कर रहे हो। ग़ज़ब ही चोदू हो।
excellent explanation
Hi @TechSystems thank you for the video. You mention in the video that the motorised butterfly valve is their to isolate the nonoperational chiller but in the video when the second chiller is off at low load the chiller is not isolated in order to maintain a constant flow at all times. Question - In what scenario would you isolate a chiller and what effect would the drop in volume have on the 3-port control valves downstream (e.g. in-balance, decrease in authority)?
Sir I want learn where your institute in India
HI Syed I don't have any institute, I only this channel and a course on Udemy.
*Transform Your BMS Skills!* 🌟 Enjoying my videos? Dive deeper with my BMS Fundamentals course on Udemy. For a limited time, it's available for only $12.99! Don't miss out - click the link below to enroll now. www.udemy.com/course/bms_fundamentals/?couponCode=A949368A4127D587E926
*Transform Your BMS Skills!* 🌟 Enjoying my videos? Dive deeper with my BMS Fundamentals course on Udemy. For a limited time, it's available for only $12.99! Don't miss out - click the link below to enroll now. www.udemy.com/course/bms_fundamentals/?couponCode=A949368A4127D587E926
*Transform Your BMS Skills!* 🌟 Enjoying my videos? Dive deeper with my BMS Fundamentals course on Udemy. For a limited time, it's available for only $12.99! Don't miss out - click the link below to enroll now. www.udemy.com/course/bms_fundamentals/?couponCode=A949368A4127D587E926
*Transform Your BMS Skills!* 🌟 Enjoying my videos? Dive deeper with my BMS Fundamentals course on Udemy. For a limited time, it's available for only $12.99! Don't miss out - click the link below to enroll now. www.udemy.com/course/bms_fundamentals/?couponCode=A949368A4127D587E926
*Transform Your BMS Skills!* 🌟 Enjoying my videos? Dive deeper with my BMS Fundamentals course on Udemy. For a limited time, it's available for only $12.99! Don't miss out - click the link below to enroll now. www.udemy.com/course/bms_fundamentals/?couponCode=A949368A4127D587E926
Your videos are awesome! Thank you for your hard work and sharing of these videos.
😊
Thanks 😊
Great video
Please sir make vedio in hindi language
Throughout the video, I keep on laughing at this guy about the pronunciation of Measure. He is so stupid and never attempted to learn correct pronunciation and he claimed he is a 5 year experienced engineer. My foot.
Great Course
isnt the AO the speed control and AI the status feedback ? little confused :/
Yes from DDC controller's reference;AO is the speed control and AI is the feedback. While if see from VFD reference AO is the feedback and AI is the speed control signal. I hope it would clarify.
@@TechSystems Ah okay, so if you were to wire this to the DDC, the AI on the VFD terminal would go to the AO terminal of the DDC? or vice versa?
Yes it would go the same way as you described.
This youtuber does not know how to pronounce "measure or measurement". He needs to go to primary school. I stopped watching his video in-between so he will not earn money from KZread management
I just finished all your videos and they’re the best I’ve seen by far. I appreciate the effort you put into making these and hope to see more in the future. Thanks
I am glad that you find my videos helpful. Thanks for this amazing feedback.
Very well done - well illustrated, well laid out, well narrated -- hats off! :)
It's a very interesting topic, solid presentation.
Thank you very much bro...
kzread.info/dash/bejne/oHt8j6qhktK8fbg.html
Sir your videos are good and provide precise information..please can you provide the control system of the chilled water district cooling on the building side..not on the district cooling provider side
Good video for beginners.
Sir...can the dia of bypass line shall be equal to the header pipe dia or the chiller pipe dia..please explain
Bless you Sir. Thank you for the Videos. Ive an interview next week, going from HVAC Engineer to Control and Systems Engineer. Thanks again
All the best for your interview.
Submitted the form complete steps.
Good experience and explain you information thank you
@techSystems - love the video, thank you. Just a question: At around 9:15 in the video, only 1 chiller is running due to low load conditions, but why not switch the accompanying pump off as well to save pumping energy costs? It is not necessary to run both pumps in this configuration with only 1 chiller running?
Hi, This is a constant flow system with 3-way control valves at the AHUs and FCUs. So that's why both pumps needs to run to always maintain constant flow through system. Due to this drawback, this system is no longer used in the new buildings instead variable flow system is used with 2 way control valves.