Viking Double Interlock Preaction System - System Reset Procedure
System reset procedure for the Viking Double Interlock Preaction System. More information available at vikinggroupinc.com/
Жүктеу.....
Пікірлер: 10
@danielsantos-kq8sf10 жыл бұрын
Wow ! Good job guys !!!!!
@aljonsumayang20257 жыл бұрын
good
@frankrogan51118 жыл бұрын
I noticed you did not close the pilot line ever. Is there a reason for it? I've heard of the valve premature tripping because the solenoid did not reset properly if you don't run water thru it while resetting the the panel via solenoid.
@jiromartinez33015 жыл бұрын
Can i use this system in a non-ulfm pump should i buy a ulfm controller my client needs that kind of system
@mohamedgaber14629 жыл бұрын
Dear Mr. Martin, we install this valve and the client want to operate the deluge valve using an electrical " manual release call point " connected to the control panel - is this possible ?
@vanthanhnguyen53847 жыл бұрын
Could you tell me about Pre-Action Valve of Shilla ? Thanks
@dathuynh8704
5 жыл бұрын
What is Shilla?
@rapidfiredm11 жыл бұрын
Vics stick often just my opinion did 5 today 1 didnt open 5 yrs old
Пікірлер: 10
Wow ! Good job guys !!!!!
good
I noticed you did not close the pilot line ever. Is there a reason for it? I've heard of the valve premature tripping because the solenoid did not reset properly if you don't run water thru it while resetting the the panel via solenoid.
Can i use this system in a non-ulfm pump should i buy a ulfm controller my client needs that kind of system
Dear Mr. Martin, we install this valve and the client want to operate the deluge valve using an electrical " manual release call point " connected to the control panel - is this possible ?
Could you tell me about Pre-Action Valve of Shilla ? Thanks
@dathuynh8704
5 жыл бұрын
What is Shilla?
Vics stick often just my opinion did 5 today 1 didnt open 5 yrs old
Hindi me banayea video
No volume