THIS TRANE SPACESHIP JUST STOPPED WORKING

This unit is a bit much for a little restaurant like this but I got it back up and running as best as possible.
HVACR VIDEOS NEW MERCH WEBSITE - www.hvacrvideos.com
Please consider supporting my channel by
Becoming a Patreon member - Patreon / hvacrvideos
Becoming a KZread channel member / @hvacrvideos
By purchasing tools via my affiliate links below at TRUTECHTOOLS.COM and use the offer code BIGPICTURE to save 8% on your total purchase (exclusions apply)
Visiting my website and purchasing merch www.hvacrvideos.com
HVAC OVERTIME CHANNEL LINK - / hvacovertime
Social Media
Facebook / hvacr-videos. .
Instagram / hvacrvideos
For any inquiries please contact me at chris@hvacrvideos.com
Mailing Address
HVACR VIDEOS
12523 LIMONITE AVE.
440 - 184
MIRA LOMA, CA. 91752

Пікірлер: 306

  • @grilnam9945
    @grilnam9945Ай бұрын

    Give this a like if you are watching this in 2025.

  • @jacknasty6940

    @jacknasty6940

    Ай бұрын

    😂

  • @ChannelJanis
    @ChannelJanisАй бұрын

    2025? Well that is an early upload!

  • @altzan2602

    @altzan2602

    Ай бұрын

    I almost started having an existential crisis and panicking because I haven't remembered a single thing from 2024

  • @RichaRat

    @RichaRat

    4 күн бұрын

    It is so cool to watch something that hasn't happened yet.

  • @standardstyle5976
    @standardstyle5976Ай бұрын

    So they spend all this research and development time to create a unit with self diagnosis and maximum effeciency, and then they put a sensitive electrical component in an area that is guaranteed to be high in humidity during normal operation. Brilliant.

  • @bobchamp3159

    @bobchamp3159

    Ай бұрын

    It is brilliant, designed to fail and create more work 😂

  • @demonknight7965

    @demonknight7965

    Ай бұрын

    All hail the all mighty 💵 😂

  • @danielcelis7089

    @danielcelis7089

    Ай бұрын

    Their banners at the shops, it's hard to stop a trane.. Yeah because they never start 😂😂😂

  • @NotSexualAtAll

    @NotSexualAtAll

    Ай бұрын

    It's seems like such a racket. I genuinely wonder if the cost of throwing replacement parts in a landfill doesn't just destroy any "efficiency" gain you got by using them in the first place. Same with the required economizer. I have to have one, but I can set it to mix however I want, what did we accomplish, California?

  • @Lovin2LiveLife

    @Lovin2LiveLife

    Ай бұрын

    Carrier has been putting them directly next to their evaps as well. Ive been bypassing when they fail and leaving them out.

  • @The98deville
    @The98devilleАй бұрын

    2025? Wow it also does time travel

  • @rf159a

    @rf159a

    Ай бұрын

    It uses Hasslein's Hypothesis. My bet is there are a bunch of apes as waiters in the restaurant. I'd be careful Chris they might capture you and do experiments on you!!

  • @stormeagle28

    @stormeagle28

    Ай бұрын

    Only when it gets hit by lightning while travelling 88 miles per hour.

  • @keith_5584

    @keith_5584

    Ай бұрын

    Or Slingshots the sun to talk to Macintosh, I mean save whales or something...

  • @shadowdemon7770

    @shadowdemon7770

    Ай бұрын

    And he didn't even fix it 😂 I had to look at my calendar, to make sure I didn't miss a year

  • @I_am_Allan

    @I_am_Allan

    Ай бұрын

    @@keith_5584 "Hello, Computer."

  • @darthdzl
    @darthdzlАй бұрын

    I was yelling at my screen when you fixed all the time elements except the year (it ain't 2025 yet!). 😮

  • @alext424
    @alext424Ай бұрын

    The more bells and whistles a unit has, the more there is to break down in my opinion… Awesome video Chris!!! 👍🏻👍🏻👍🏻

  • @ryanisaacson118

    @ryanisaacson118

    Ай бұрын

    Kiss keep it simple stupid

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    Thanks

  • @jeffreywhitlatch1409

    @jeffreywhitlatch1409

    Ай бұрын

    Here here I say

  • @harbosonius
    @harbosoniusАй бұрын

    I work for a Trane Comfort Specialist for almost 20 years, and I love the product . That being said, it's always a " shake my head" moment for me to see technology that is supposed to save you up to 40% on energy consumption but ultimately ends up eating all that savings up in repairs (that are usually close to 1800 bucks minimum), and usually will have multiple expensive electronic failures in the future. It's not just Trane, manufacturers are literally engineering the reliability out of everything with this high falootin' crap.

  • @coreyr8870

    @coreyr8870

    11 күн бұрын

    Engineers and designers are making the call to order based on customer saying they want to be a little greener. They are then cashing their checks before the high maintenance costs or failures

  • @ImagineeringAerospace
    @ImagineeringAerospaceАй бұрын

    wow videos from the future

  • @Ak3rn0
    @Ak3rn029 күн бұрын

    That “Trane” drive is actually a Danfoss drive - I’m willing to bet you could’ve found an identical drive in stock somewhere directly from them for cheaper than Trane sold it to you. Also, that A38 fault was a communication error within the drive, if you take it apart a little you might be able to fix it and get yourself a working spare out of it!

  • @halverde6373
    @halverde6373Ай бұрын

    SO GLAD I retired 15 years ago. Trane began their psychosis about 35 years ago! The ECM motors were the final failures . Condenser fans were sheer idocy! As much air possible should go through that coil in the lower 48!

  • @RT-qd8yl

    @RT-qd8yl

    29 күн бұрын

    Unfortunately it's getting to the point that we have no other choice though. With how much electricity costs now, most people wouldn't be able to afford to continue using the old equipment with its power consumption. I agree with you, the older stuff worked great and didn't fail often. If energy sources didn't cost so much now I'd love to have them back.

  • @ApacheFPV
    @ApacheFPVАй бұрын

    5:31 thanks for the jump scare lmao

  • @hoggsoft

    @hoggsoft

    Ай бұрын

    I thought he somehow got zapped

  • @justindarkcloud

    @justindarkcloud

    Ай бұрын

    Right!?! What happened??? Startled the crap out of me

  • @Insanekiller278

    @Insanekiller278

    Ай бұрын

    Capacitor maybe? :o I couldn't tell either

  • @SmallKittyPaw

    @SmallKittyPaw

    Ай бұрын

    Pretty sure he was losing grip on test leads and just trying to catch them

  • @starlite528

    @starlite528

    Ай бұрын

    It got me too, rofl!

  • @kg650ig8
    @kg650ig8Ай бұрын

    Great video Chris. I've taken note of the following points: 1. The Trane engineers need to be adequately compensated and need to prioritize the work environment for the equipment and service technicians. 2. Trane wholesalers need to gain essential knowledge. It would help if they were familiar with their own equipment. 3. You've worked on a work order related to Trane spaceships🚀. You should consider meeting with someone like Elon Musk for such endeavours. 😆

  • @phildegruy9295
    @phildegruy9295Ай бұрын

    When the touch screens get really dirty around where the bezel meets the screen they don't respond to touch very well and won't calibrate. Take a wet wipe and clean the screen and around where the screen meets the bezel with the wet wipe and your fingernail. Get all that crud out of there and off the screen and that should do the trick. Automotive plants have thousands of touch screen HMI's and robot touch screen teach pendants. They are always dirty and not working well. A little cleaning works wonders. I think the 38 (1284) code is a communication fault (error) between the control card and the power card (don't have my manual for it anymore). Re-seating the cards in the drive and connectors going to the cards has been known to work.

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    Thanks for the tip

  • @aleksandarvasilevski7410
    @aleksandarvasilevski7410Ай бұрын

    Am I the only one that waits to see teardown of that VFD unit?

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    You are not

  • @keithfarnham8720
    @keithfarnham8720Ай бұрын

    Hey Chris , when that TD5 display module boots up it automatically goes into a screen calibration mode. In the future , don’t touch the screen in that calibration mode and it will time itself out after 30-45 seconds and resume normal operation. You’re lucky that the screen calibration actually worked for you. I have seen a few of those displays bricked from the calibration process going wrong.

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    Thanks for the tip

  • @JlerchTampa

    @JlerchTampa

    Ай бұрын

    That is an 'awesome' human interface design feature to frustrate the Un-Trane'd techs and help generate support revenue....... Step #1: Power On Step #2: Instruct Un-Trane'd tech to perform action Step #3: IF Step#2 performed GOTO Step #1; ELSE timeout and resume normal boot sequence.

  • @keithfarnham8720

    @keithfarnham8720

    Ай бұрын

    @@JlerchTampa you get the idea . The screen calibration is there for a reason, you just ignore it 99 percent of the time when you’re working on a system and use it only when the screen does something funky.

  • @damianorsini6468
    @damianorsini6468Ай бұрын

    “Know what I mean….Vern?” Hahahahha I see you Chris, you’re the best. Ernest goes to camp and Ernest goes to jail we’re hilarious 🤣

  • @throttlebottle5906
    @throttlebottle5906Ай бұрын

    "it's only going to be in there for a couple days". just like that condenser fan motor? 🤣🤣 we know how it goes, working and out of sight out of mind. **well surprise surprise, actually got the parts and installed them! lol

  • @Freonleon
    @FreonleonАй бұрын

    Never seen a vfd last in the blower compartment.

  • @zack9912000

    @zack9912000

    Ай бұрын

    They are in Yorks as well like that

  • @analogmoz

    @analogmoz

    Ай бұрын

    $100 motor starters get put inside the conditioned space, $1,000 drives get put in the pigeon poop.

  • @JohnDoe-sf6ee
    @JohnDoe-sf6eeАй бұрын

    This dude living in the future. Must have been the space ship.

  • @Josh.SPublishingTeam2024ii
    @Josh.SPublishingTeam2024iiАй бұрын

    Look like the unit one year in the future, this unit real old! Always be safe working on these units!

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    I will do my best in the future

  • @cyborgsheep6077
    @cyborgsheep6077Ай бұрын

    oh boy! the video you`ve been waiting for. The spaceship condenser fan motor that takes 100 years to ship LOL also a fault like that means the transducer in the thermostat detected that the customers wallet was getting fat

  • @TheShotgn
    @TheShotgnАй бұрын

    The way I was instructed by Trane to reset the alarm on the VFD is to make sure the Unit is off on the touch screen then cycle power for about a minute. Once the screen comes back on then put the unit back to cooling or occupied or whatever it is programmed for. That clears the alarm of the vfd every time for me.

  • @Rollerguitar96

    @Rollerguitar96

    5 күн бұрын

    this is right, but when you get an Internal Failure (Alarm 38) you can not reset the Drive. Its the same for the Danfoss VFD‘s. The Interface and Panal looks just the same. Greetings from Switzerland.

  • @akshonclip
    @akshonclipАй бұрын

    Reminds me of the Winnebego from SpaceBalls.

  • @jesseh5554
    @jesseh5554Ай бұрын

    Had one of those drives go bad, 8 months back order last year, called the ABB rep and they sized an ABB and we installed and got it up and running.

  • @RT-qd8yl
    @RT-qd8yl29 күн бұрын

    Neat video, man. I did commercial and industrial refrigeration and HVAC before cancer took me out of the game. I still miss doing the work but my body can't hold up to 8-10 hours a day of it again. It's nice to be able to sit and watch what I loved to do so I can hold on to my knowledge. Thank you.

  • @Colt-wr6wx
    @Colt-wr6wxАй бұрын

    Well done Chris 👏... love that you used the control wires for the VFD and installed a contactor. 👍

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    Thanks

  • @jimmynoleaksboilerman7348
    @jimmynoleaksboilerman7348Ай бұрын

    Restaurants not doing maintenance , pigeons in the blower compartment, good for you getting the a/c back on without any negative attitude , on a hot roof.

  • @djenson
    @djensonАй бұрын

    Do you have VRF units in the US? those would blow your mind - 3 sandwiched layers of PCBS with inverter boards etc crammed in everywhere, copper lines running everywhere like a maze. Canbus communication to all indoor units. Complexity is insane

  • @christopherreinoso9828
    @christopherreinoso9828Ай бұрын

    I love working on these guys, there great units, only down side is train wanted to step there game up with controllers but they put them in bad spots. But I’ve made this repair 100 times in the tri-state.

  • @djrenault
    @djrenaultАй бұрын

    one of my clients has banned danfoss drives from their site entirely. some equipment only comes with danfoss, so they wait until the danfoss dies and then put something else in. they built a building a decade ago which had 50-100 danfoss drives in it, and not all stuffed in supply air plenums like this, most just standing on unistrut in mechanical rooms, and ten years later, only half the drives are still working. the other half were replaced with siemens bt300, which then got discontinued, so now they're only using ABB. they also like the reliability of yaskawa but their techs said they're really hard to program.

  • @murrals

    @murrals

    Ай бұрын

    Danfoss drives are garbage. Just like their expansion valves, garbage. Had a restaurant with 2 Tranes chillers with DX coils. Drives for first CFM on each circuit. In the 5 years servicing the place. I bet we replaced a dozen drives. Pretty sure our cost was over 2k per drive.

  • @thebigmacd

    @thebigmacd

    Ай бұрын

    In my experience ABB drives are the best value. Availability, useability, flexibility, reliability.

  • @thebigmacd

    @thebigmacd

    Ай бұрын

    ​@@murralsDanfoss everything seems to suck these days, even their hydraulic pumps and motors.

  • @rockyhighwayroad7365
    @rockyhighwayroad736521 күн бұрын

    Wow that air conditioner unit has a little TV on it

  • @bwcnation
    @bwcnation21 күн бұрын

    Few years back a convenience chain I took care of started upgrading rooftops to carriers with ABB drives. When they failed it was pretty convenient just swap to spare legs and it just runs normal. Interfaces went by tonnage of units though so I'd save em and label them and use them to run diagnostics

  • @elcrazy8017
    @elcrazy8017Ай бұрын

    I had the same alarm last week. The VFD card was bad. Replaced drive all good now

  • @jasonjohnsonHVAC
    @jasonjohnsonHVACАй бұрын

    Supply fan failure on those is the air proving switch. It's looking for a contact closure. I remember chatting about this drive. Cool to see the video for it. Yeah about Trane Supply....they are seriously lacking in experienced people....I have that out here my way too.

  • @tschuuuls486

    @tschuuuls486

    Ай бұрын

    Would be fun to find out if the main control unit will talk to a generic non trane branded vfd. You could probably make a bunch of money selling them :D

  • @Colt-wr6wx

    @Colt-wr6wx

    Ай бұрын

    ​@tschuuuls486 won't work.. trane units need specific trane parts or they don't run.. I know from experience...

  • @jasonjohnsonHVAC

    @jasonjohnsonHVAC

    Ай бұрын

    @tschuuuls486 all the board does is send a speed reference signal. It goes on AI1 normally. Besides the "trane" VFD is really a Danfoss with Tranes junk written all over it. You could replace it with any brand, the parameters is where it can get tricky. You'd have to program all the parameters yourself if you used, say an ABB. A drive is a drive. I've done it on Trane units. Normally I tend to go OEM just because it fits just right without any modifications and the programming is already done. It's not hard to do, just a little time consuming.

  • @tschuuuls486

    @tschuuuls486

    Ай бұрын

    @@jasonjohnsonHVAC Nice, I thought it would communicate via serial with the drive or something. Can you dump the old parameters via usb and just upload them to a same brand drive?

  • @jasonjohnsonHVAC

    @jasonjohnsonHVAC

    Ай бұрын

    @tschuuuls486 you sure can. It's a process, but definitely can be done. Usually on a trane they will have the HMI display in one part and the drive in the other with a cable to connect the 2. Is that what you were referring to a serial connection.

  • @kg4muc
    @kg4mucАй бұрын

    The supply chain seems to be ruined on just about everything these days. Great job with the psc evap fan temporary fix and by passing the vfd for the indoor blower. They would have gotten a bit warm otherwise considering the fiasco they gave you getting the right parts. Covid is the excuse for our parts problems but I believe it goes way deeper than that. Great Job as usual. Have a quiet weekend 😊

  • @stephengalante2973
    @stephengalante2973Ай бұрын

    that blower motor looks fun to change lol

  • @WackyAmoebatrons
    @WackyAmoebatrons28 күн бұрын

    Another spaceship had a 1201 alarm. Hat tip if you know which!

  • @JSoroka93
    @JSoroka93Ай бұрын

    I've personally worked on these units a few times that have had faulty VFDs. I usually end up just replacing the VFD with the contactor since it is so much cheaper for the customer and just adjust the sheave for the proper amp draw and airflow.

  • @Damicske
    @DamicskeАй бұрын

    "Rebadged" Danfoss drives. FC-202P3K7T2E20H2XGXXXXSXXXXAXBXCXXXXDX is the equivalent but I would recommend a IP55 enclosure (change the E20 part in the model number to E55), problem with that is that the size gets bigger (from A3 to A5). Another option is coated pcb FC-202P3K7T2E20H2XGCXXXSXXXXAXBXCXXXXDX, same size but the pcb's are coated against moisture ;)

  • @curtiskelley3327
    @curtiskelley332714 күн бұрын

    Good logic.I us too be a drive repair man for eurotherm drives.Very important too give the distributor.Numbers off the Ac unit and Drive Number Cuts down Guessing.And Confusion.Your an excellent repair man.Super Tech.

  • @joshperez7731
    @joshperez7731Ай бұрын

    Glad to see you posting videos on units like this, I've been getting thrown on calls expecting a light rtu unit only to come across this beast and not know what to do. They can be very intimidating.

  • @lsx_moe
    @lsx_moeАй бұрын

    Blower compartment is best spot for the VFDs. After evaporator so cool semi-dehumidified air to cool the capacitors and IGBTs.

  • @MartinNyxel
    @MartinNyxelАй бұрын

    I like the obvious premium build quality of this thing... as well as the late night engineering decisions inside it. Its always the "same" story - your project manager said: "VFD is a must!" =D ...and your boss: "No problem" :DD And finally YOU, after only about ~27 restarts of CATIA did put the VFD somewhere, where did not die to overheat aftrer only a few days. =DD

  • @analogmoz
    @analogmozАй бұрын

    VFDs save you 8% on that motor with a $100 a year of energy usage. The failed drive costs $1,000. Progress!

  • @mackenziegray2090

    @mackenziegray2090

    Ай бұрын

    Be 10 years to get your money back lol

  • @chadhartsees
    @chadhartsees12 күн бұрын

    "Spaceship" well said. Heck, 'intelligent' variable speed drive and pool pump repair was 3 or 5 times more expensive than a drop-in single speed 'dumb' drive and pump. I can't imagine what it's like in commercial HVAC world.

  • @guygfm4243
    @guygfm4243Ай бұрын

    I think if you had some wet wipes for the touch screen it would help you stop having problems with it. Needs to be free of dust or it thinks something is wrong. Thanks for sharing

  • @Matt-my8nm
    @Matt-my8nmАй бұрын

    Should have added an overload to that blower contractor, the vfd was the overload before it was bypassed. Thanks for all the great videos

  • @Jason-wc3fh
    @Jason-wc3fhАй бұрын

    Yorks often have the blower VFD right in the mixed air location close to the blower. I'm assuming they likely coat the circuitry to be compatible with a more humid environment... Also, the more bells and whistles with communicating equipment and VFD controls to help make the equipment run more efficiently will cost the customer less with energy but will always cost the customer more in the long run as these fancy parts are insanely expensive to replace when they break, and the expensive fancy parts are the ones that will break. Not a question of if, but when.

  • @nolanchambers4408
    @nolanchambers4408Ай бұрын

    trying to get into hvac school that has refrigeration in GA. your channel got me into this

  • @mathanyoseph4349
    @mathanyoseph4349Ай бұрын

    VFD need to be serviced regularly by a installation company (usually BAS techs), if not dirt builds up in the VFD and it will start putting up all types of faults for no reason.

  • @hvacrnortheastern2110
    @hvacrnortheastern2110Ай бұрын

    Great video haven’t work on RTU in last 20 years l remember the Trace Voyager RTU. We had lot of them in the northeastern area what happen did they over engineer these units for energy saving 😃

  • @BenTh17
    @BenTh17Ай бұрын

    My company pretty much only buys AAON units. They have some good and some bad things about them, but they definitely seem to have figured out where to put VFD’s, it is in a “semi-conditioned” compartment with the compressors and I barely ever see them have problems. Not sure why someone would think putting it in the blower compartment would be a good idea 😂

  • @tschuuuls486

    @tschuuuls486

    Ай бұрын

    Trane probably do it because capacitor life will shorten with temperature. Every 10°C cooler will double the lifetime. And those big caps in the drives are probably rated 5000h-10000h at 105°C which could make it fail in warranty. If this is a problem in real world conditions vs. humidity/thermal cycling issues is a different story.

  • @whoisderf

    @whoisderf

    Ай бұрын

    Aaon has only a few good things and countless bad….too many to bother listing. Straight off the factory floor, they are the worst unit on the market.

  • @BenTh17

    @BenTh17

    Ай бұрын

    @@whoisderf not disagreeing with you there, especially recently. They have been sending units with the wrong condenser fan motors, routinely sending them way overcharged, then sometimes even when they’re not overcharged they just trip out in high pressure for the fun of it.

  • @whoisderf

    @whoisderf

    Ай бұрын

    @@BenTh17 i run into that high pressure switch trip often. Aaon tech support has no clue what the problem is and tell you to call Yaskawa (for the CFM on drives). Yaskawa rep will tell you they get calls about it often, they’ll walk you thru the parameters AAON ENGINEERS WANT, maybe have you change a few things. It will still trip pressure switch. I haven’t ran into over charge yet. I have a building with about 40 Aaon, and all the 16 ton units have this issue, with a mix of straight DX cooling and DX+reheat. I legit believe it’s the way Aaon’s controllers/boards are computing what the pressure transducers are reading. Still working on the true solution on this one, whenever I go to site. Maybe the fan blades are pitched wrong… maybe it’s the micro channel coil design….. Aaon is literally no help. Couple of my favorite Aaon moments: Brand new unit (don’t remember tonnage), 2 circuits, each with 1 comp and 1 CFM. Both circuit would trip high pressure. Ended up finding CFM1 wires landed on CFM2 relay and CFM2 wires on CFM1 relay. Call stage 1, Comp1 runs, CFM2 runs. Another Brand new unit… was having control voltage issues. 24v would be here, but not there, then it would go away completely. Every single wire landed on the low vault terminal blocks, both the 24v and common blocks, they didn’t strip the freakin wires before crimping on the push connectors…. Like what the eff?!!! I’ve been told they test every unit before it leaves the plant… I kinda miss using my Aaon/Orion handheld controller….back when Aaon was actually one of the better brands.

  • @davidathey7903
    @davidathey7903Ай бұрын

    You jumped! Did your heart skip a beat? Glad you are okay.😅

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    Yes! Thank you!

  • @elcrazy8017
    @elcrazy8017Ай бұрын

    I work on a lot of TRANE voyagers I never knew those units had variable speed compressors? Just simple contactors and a drive for the indoor blower motor. Good to learn new things

  • @markbeiser
    @markbeiserАй бұрын

    After a full day of chasing down issues with a VRF system I was thinking I'd rather just work on package units. Then this video reminded me of these particular units. I think I'd rather stick with VRF systems.🙄 I've "temporarily" bypassed VFDs to get people going like that a few times. I think I'm about 50/50 on the customers being willing to pay for a new VFD...🤣

  • @cr76802
    @cr76802Ай бұрын

    Learned at working at a cookie factory. That vfd drives can be pretty sensitive static discharge/temp change Allen Bradley was horrible about melting down

  • @bigrigotj
    @bigrigotjАй бұрын

    Anyone see that white wire had a run out spot? Saw copper through the insulation. 10:18 in the video

  • @everlastingdane
    @everlastingdaneАй бұрын

    Someone probably already mentioned this but the VFD with that error code means the drive's contactor is stuck closed (welded together), the VFD checks for this and when the contactor doesn't open inside it, it throws out that code, also you know we are in the year 2024 right lol, you didn't change the date from 2025. 😜

  • @dannythompson1948
    @dannythompson1948Ай бұрын

    Dan foss customer service/tech support is fantastic.. dont hesitate to call them... That's what THEIR techs do!! Lol

  • @StephenCole1916
    @StephenCole1916Ай бұрын

    Spaceship? You sure it's not a TARDIS? Being from the future that is... 🤣

  • @Blasterxp
    @BlasterxpАй бұрын

    Awesome machine, so much to learn

  • @m9ovich785
    @m9ovich78528 күн бұрын

    Another strange thing about this unit. Is the backwards configuration of the Idler Pulley for the Fan. In that set up it is taking 'Grip" away from the other Pulleys Should be a Flat Pulley pulling the belt into the Drive/Driven Pulleys...

  • @MariosACandRefrigeration
    @MariosACandRefrigerationАй бұрын

    Nice work.thanks for sharing.

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    Thanks for watching!

  • @TheChipmunk2008
    @TheChipmunk2008Ай бұрын

    Chris, it worried me seeing ou using those LONG exposed probes on a high current 208 circuit, that's how arc flash happens, consider some probe shrouds?

  • @bentlikeitsmaker
    @bentlikeitsmaker29 күн бұрын

    The thing about drives is honestly they need a weather rated passively cooled drive

  • @carloshilarionvazquezaranda
    @carloshilarionvazquezarandaАй бұрын

    Buena tarde Chris, un video de mucho trabajo y mucho que pensar, y la verdad no entiendo por qué venden estos equipos muy caros y además los repuestos con precios muy elevados. Entonces dónde queda el ahorro de energía. Gracias por todo lo que enseñas Chris, saludos desde Coacalco Edo de México.

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    Tiene estas en Mexico? estas Voyager units de Trane ? Gracious por ver mis videos tambien

  • @carloshilarionvazquezaranda

    @carloshilarionvazquezaranda

    Ай бұрын

    Muchas gracias por todo tú apoyo y tiempo. Y tus videos son extremadamente muy buenos, onestamente los veo cuando puedo pero estoy al pendiente de ellos. Saludos a todos cuídense por favor.

  • @RobRocker09
    @RobRocker09Ай бұрын

    Amazing video.

  • @HappilyHomicidalHooligan
    @HappilyHomicidalHooliganАй бұрын

    13:16 The dust and dirt on the screen might be causing it to think it's being touched in multiple places at once... You likely should have cleaned it before starting to diagnose the unit...

  • @zekenzy6486
    @zekenzy6486Ай бұрын

    Great video as always. Good job and Nice work. Thank you for sharing. It is, this trane is spaceship with a lot going on , components . I see you on Sunday ^_^ with another video ^_^

  • @AgustinCesar
    @AgustinCesar8 күн бұрын

    Aaah, the marvelous thing of putting more computers into simple machines... And not putting "more descriptive error messages" for troubleshooting... As a person from the IT world, I do tell you: Welcome to the Jungle Right to Repair out of the window, right?

  • @mrbugenhagen3364
    @mrbugenhagen3364Ай бұрын

    I have changed a lot of VFDs and I mean a lot as in over 100. Usually they don´t even show an alarm refering to "I am broken". It can be everything from the obvious stuck at bootscreen to under or overvoltage which would be a real concern if it was true. Great video as always.

  • @XxTWMLxX
    @XxTWMLxXАй бұрын

    I have one of these on my roof for a bank. Glad i havnt had to mess with it yet. Mostly all older york units. Got called today pne wasnt working. 28c inside. Calling for cold. Compressor runs but no cool air. Havnt gauged it yet. Filters are clean so looking like a gas leak. Identical units on roof working and appear to ve operating the same as far as noise and fan speeds.

  • @hrdworkin7633
    @hrdworkin7633Ай бұрын

    I understand if you call Trane support you get Ted.

  • @Bobherry
    @BobherryАй бұрын

    The looks like a danfoss VFD branded as a trane

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    Yep

  • @bdblazer6400
    @bdblazer6400Ай бұрын

    11:50 Engines starting up

  • @kc0eks
    @kc0eksАй бұрын

    That heating compartment sure looks... Burnt.

  • @mastahc411
    @mastahc411Ай бұрын

    Other than using more power what would be the downside of just leaving the contactor in there? I'm sure the cost of the vfd far outweighs any savings on the electric bill the vfd provides.

  • @ivoryjohnson4662
    @ivoryjohnson4662Ай бұрын

    You knew how to get rid of the bells and whistles to get them going that's what's important. Then put them back to factory specs

  • @sccpsteve
    @sccpsteveАй бұрын

    13:18 I have a touchscreen that always fails calibration... unless you precisely use a stylus to calibrate the screen. You have to use a stylus, or it may fail on you. (based on my experience)

  • @lavina58
    @lavina58Ай бұрын

    Awesome job and video 😊👍🙌👌🍀🙏

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    Thanks

  • @helmsajr
    @helmsajrАй бұрын

    Great job Chris Trane can be a pain in the butt.

  • @Pyro4100
    @Pyro4100Ай бұрын

    Remember it's only temporary unless it works

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    True

  • @ronaldwoofer5024
    @ronaldwoofer5024Ай бұрын

    confirmed time traveling HVAC technician... notice they dint fix the 2025? 🤔🤔🤔🤔🤔🤔🤔

  • @thesilentonevictor
    @thesilentonevictorАй бұрын

    Super tech job Chris

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    Not quite but thanks, lol

  • @pineychristian
    @pineychristianАй бұрын

    Biggest problems i have with VFD's is they are dirty and over heat. Heat is the killer of drives. Water isnt good either.

  • @ryanisaacson118
    @ryanisaacson118Ай бұрын

    The trane symbio units are super nice to work on

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    Good to know!

  • @michaelcoonts6253
    @michaelcoonts6253Ай бұрын

    Wish you showed where you hooked up that temp contactor for the vfd call.

  • @sivalley

    @sivalley

    Ай бұрын

    He picked up the 24v off the vfd enable relay and tied it directly to the contactor so he can undo everything easily

  • @michaelcoonts6253

    @michaelcoonts6253

    Ай бұрын

    Thanks that makes sense

  • @neonhomer
    @neonhomerАй бұрын

    Right now, control guys are screaming at their devices....

  • @pineychristian
    @pineychristianАй бұрын

    Reminds me of my Daikin Rebel RTU's. VFD on blower motors, ecm 480v variable speed condenser fan motors, return fan motors and energy recovery wheel. Also all motors are mod bus and address within the microtech controller. Nice units lots to break and go bad

  • @dashcamandy2242
    @dashcamandy2242Ай бұрын

    I really love the "Future Diagnosis" feature, that's amazing tech right there! 😆 I wish every manufacturer put that feature on their devices! "Oh, my alternator is going to fail in two weeks, let me just order one now so I can swap it out at a convenient time." 5:31 - I jumped, for no reason. 10:30 - I haven't heard the word "dealio" in a long time... I think I might start using it again. Is there a "Core Charge" on VFDs? As in, are failed ones sent back to the manufacturer for refurbishment/repair, allowing you to purchase remanufactured drives in the future, or do they simply become e-waste? As others have noted, the dirt on the touchscreen was likely causing the calibration failures. Those appear to be resistive touchscreens as you'd find on thermostats, as opposed to the capacitive touchscreens more prevalent in our technological goodies like phones and tablets. Dust buildup, especially around the screen's bezel, can cause pressure on the screen, leading to false inputs. Resistive touchscreens rely more on pressure, hence why you can operate them with gloves on, or pointy objects like a stylus, pen, key, etc.

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    100% agree

  • @brettRaperhvactech
    @brettRaperhvactechАй бұрын

    2025? Time flies!😊

  • @johnwalker890
    @johnwalker890Ай бұрын

    Good job Chris........

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    Thanks

  • @DedmenMiller
    @DedmenMillerАй бұрын

    I just got a huge deja'vu! My brain promises me I've seen it before :D Maybe I'm watching too many of your videos.... Nahhh can't be 😅

  • @KevinBenecke
    @KevinBeneckeАй бұрын

    Who else was yelling at him that it's 2024 and not 2025?

  • @Private011
    @Private0117 күн бұрын

    You need to get a can of SprayAway and a soft bristle brush and microfiber to start cleaning. I think that touchscreen needs to be cleaned. That’s why it’s not responding properly. And please use some contact cleaner.

  • @starlite528
    @starlite528Ай бұрын

    You might call it dumb logic but if it works then it's not dumb. I would hope the manufacturers are watching and praising the work, because it's not easy for everyone. Taxi drivers can spend a long time learning 'The Knowledge" and I believe the same is true for electronics troubleshooting. I like to think I have "The Knowledge" in my trade because I feel like I'm pretty good at troubleshooting and resolving problems and I look back on what I did and think "how the f did I do that?"

  • @gregmercil3968
    @gregmercil3968Ай бұрын

    Good god Tranes are weird, and those Voyager “spaceships” are even weirder. I do however like how Trane has their blower belt tensioners set up. Super simple and easy to do.

  • @LOCOLAPTOP

    @LOCOLAPTOP

    Ай бұрын

    And they don't eat belts like Carriers do.

  • @leoschneider3570
    @leoschneider3570Ай бұрын

    I missed a couple episodes, but love the new intro

  • @HVACRVIDEOS

    @HVACRVIDEOS

    Ай бұрын

    Thanks

  • @grandinosour
    @grandinosourАй бұрын

    Build this to save energy cost, but, in the end. it cost much more the keep it running, negating the energy savings.

  • @alexaro1672
    @alexaro1672Ай бұрын

    I understand the intent of the VFDs, but in my experience they fail way too often. Can’t tell you how many I’ve had to replace when I was servicing RTUs and they are not cheap.