RELAY SETTINGS AND CO ORDINATION|PART 2_EARTH FAULT|ELECTRICAL TECHNOLOGY AND INDUSTRIAL PRACTICE

Ғылым және технология

Relay settings and relay co-ordination calculations for earth fault protection is the objective of this video. IDMT relay settings and instantaneous relay settings calculations have been described in this video. These calculations are required for successful implementation of protection of power system against earth fault and protection co-ordination hope you will enjoy this video.
#ElectricalTechnologyAndIndustrialPractice, #IDMT_RelaySetting, #EarthFault, #InstantaneousRelaySettings, #RelayCoOrdination, #RelaySettingCalculation, #OverCurrentRelaySetting,
This video is also applicable for the following topics.
1. Relay setting for earth fault protection
2. IDMT relay setting for earth fault protection
3. Instantaneous relay settings for earth fault protection
4. Relay co-ordination for earth fault protection
5. Inverse time relay for earth fault protection
6. Protection for earth fault protection
7. Relay setting calculation for earth fault protection.
8. How to calculate settings for relays for earth fault protection
9. Relay setting in substation for earth fault protection.
10. Relay setting calculation example for earth fault protection.
11. Time current co ordination for earth fault protection.
12. TCC for earth fault protection
13. Time grading for relay co-ordination for earth fault protection.
14. Relay co-ordination for earth fault protection.
15. relay setting basic for earth fault protection
16. Basic of relay setting
17. How to select time discrimination for IDMT relay.
18. IDMT relay co-ordination.
19. Co-ordination of relays.
20. Relay operating time selection.
21. Earth fault protection
Please visit our website for more:
electricaltechnologyrishi.blo...
Please like, share, comment and subscribe to our channel.

Пікірлер: 58

  • @surendrakverma555
    @surendrakverma5552 ай бұрын

    Thanks Sir

  • @chintanvaria2238
    @chintanvaria22385 жыл бұрын

    Nice explanation. Understood it very clearly. Thank you Sir.

  • @rameshtripathy5978
    @rameshtripathy59784 жыл бұрын

    Very good description & useful for the commissioning engineers !

  • @zoro4zena
    @zoro4zena4 жыл бұрын

    you are my guru now :)

  • @rakeshnanda9506
    @rakeshnanda95065 жыл бұрын

    Nyc explanation with practical solutions...great sir. Plz make a vdo on rotor earthfault relay

  • @shihabahmedalkatrani3050
    @shihabahmedalkatrani30505 жыл бұрын

    Thank you very much for this lecture

  • @khan_tanzeem0521
    @khan_tanzeem05213 жыл бұрын

    Just amazing 👍🏻👍🏻👍🏻👍🏻👍🏻👍🏻

  • @sohrabalmajose4082
    @sohrabalmajose4082 Жыл бұрын

    Thank you for your very informative video

  • @hassanmohammady9827
    @hassanmohammady9827 Жыл бұрын

    Thanks a lot. Merci beaucoup

  • @sanjeevrana8317
    @sanjeevrana83175 жыл бұрын

    Excellent

  • 5 жыл бұрын

    Good video

  • @vineethkk1919
    @vineethkk19194 жыл бұрын

    Hi, Thanks you very much for sharing your knowledge. I request to clarify one doubt. Usually 51N & 51G is setting at 10 to 30%. In video it is setting above 100%.

  • @chandrasekhardas9080
    @chandrasekhardas90804 жыл бұрын

    Thank you sir .... please make check synchronised relay i.e 25M topic lectures.

  • @janakiramanl5992
    @janakiramanl59924 жыл бұрын

    Nice explained sir. Sir, How do you select the feeder wish curves?

  • @khan_tanzeem0521
    @khan_tanzeem05213 жыл бұрын

    🌟🌟🌟🌟🌟

  • @subhramanipradhan8334
    @subhramanipradhan83342 жыл бұрын

    Thanks for nicely explaining the method of earth fault protection and coordination. Can you please post a similar video pertaining to a case of HV system neutral Earthed through Neutral grounding transformer.

  • @stalindevakumar4697
    @stalindevakumar46973 жыл бұрын

    Very nice explanation. One Clarification. I have existing settings from the Client. I am adding new switchgear and MCC in to the existing network. How to start the relay coordination study? Should be from upstream settings (from the client) to downstream or downstream to upstream?

  • @MaheshBaburajapalayam
    @MaheshBaburajapalayam Жыл бұрын

    Pls teach about power generation design

  • @pijushdhar7310
    @pijushdhar73102 жыл бұрын

    Hi Can You please make a video on motor protection setting considering numerical relays. I desperately need it

  • @dschauhanchauhan2012
    @dschauhanchauhan20125 жыл бұрын

    Sir plz guide how to do settings of auto recloser.. And there coordination with feeder and incomers

  • @electricaltechnologyandind5335

    @electricaltechnologyandind5335

    5 жыл бұрын

    i have a video on time gradation. watch that video. then watch this video you will understand. and regarding auto recloser as per i am concerned it is a feature of circuit breaker duty cycle. CIRCUIT breaker has a duty cycle of open and close sequence. for circuit breaker having auto recloser scheme the breaker closes after a delay of 0.3 sec. then it checks if there is still a fault. then again it opens. you do not have to make any setting. it is inherent feature of breaker......

  • @krishnappanac3339
    @krishnappanac33394 жыл бұрын

    you are considering 50N(HV1) Is 5% of 400A. It is very less .it may trip during charging of 6.6/.433kV Transformer due to Inrush current.Because it DMT not IDMT. so you may increase the pickup value to 80% of NGR Rating

  • @enriqueh8847
    @enriqueh88474 жыл бұрын

    Hello, very nice lecture.. thank you. Please, is it possible to do another similar video with relays 67N and 50/51/51N/50N together? In advance thanks

  • @electricaltechnologyandind5335

    @electricaltechnologyandind5335

    4 жыл бұрын

    I shall try

  • @enriqueh8847

    @enriqueh8847

    4 жыл бұрын

    @@electricaltechnologyandind5335 hello,... Thank you very much

  • @ahmadnajem9593
    @ahmadnajem95932 жыл бұрын

    Good evening sir thanks for your video I have question I have O/C relay In=300/1 Is=1.2In Time 500 msec How can I calculate the trip time and accept the relay and saying is agood ?

  • @saravanans9019
    @saravanans9019 Жыл бұрын

    How to calculate for 50 overcurrent protection in trf

  • @azadrokon732
    @azadrokon7322 жыл бұрын

    Please make your video in hindi. It’s humble request.

  • @vsskmarmolleti6570
    @vsskmarmolleti65702 жыл бұрын

    Hi sir..please explain about schneider VIP 45 relay.my system tripping due to earth fault..setting at 7A,0.77msec,on 33kv RMU

  • @electricaltechnologyandind5335

    @electricaltechnologyandind5335

    2 жыл бұрын

    33 kV system shall be solidly earthed. So you can increase the pick up setting. However prior to increasing the pickup check the system throughly if there is really anybearth fault or not.

  • @triptimishra20
    @triptimishra204 жыл бұрын

    Hello, Can you help me with the cable sizing for the NGR ground cable and neutral cable? 1.) Does the ground and neutral cable for NGR to be sized as per 400A or it should can sized lower as earth fault relay will operate at 10% of NGR rating. Please help.

  • @electricaltechnologyandind5335

    @electricaltechnologyandind5335

    4 жыл бұрын

    For 400A

  • @musicalpower8861
    @musicalpower88612 жыл бұрын

    Hhindi mnhi h ka

  • @ashishmahajan7223
    @ashishmahajan72234 жыл бұрын

    Hello sir the video was really good but i have some doubts as follows: 1. When to use 50 and when to use 51 relay? 2. What happens when there is a fault above bus 1? 3. How can we calculate the transformer withstand capability as we need to coordinate the relays accordingly?

  • @electricaltechnologyandind5335

    @electricaltechnologyandind5335

    4 жыл бұрын

    1. use 50 for the end feeder at any voltage like capacitor, motor transformer. say a 6.6/0.433 kv transformer is an end feeder at 6.6 kv level. after that it transfers power at 0.433kv level . 2. for that upstream Protection will work. these protections are arranged in sequence to give serial backup to each other. 3. transformer withstand capability is specified. in general transformer can with stand fault current if the secondary is bolted short circuit with full rated voltage at primary for 2 second. transformer designs are made like that

  • @ashishmahajan7223

    @ashishmahajan7223

    4 жыл бұрын

    Thank you very much sir

  • @vinodsinghnegi6308
    @vinodsinghnegi63084 жыл бұрын

    if 9MW, 11kv generator connected to Grid with continours synchronized condition, .... so Generator NGR keep close condition or not...... can any one explain me......

  • @electricaltechnologyandind5335

    @electricaltechnologyandind5335

    4 жыл бұрын

    See generally generators are connected to grid via a generator transformer which has a vector group of Yd1 or Yd11. So presence of the delta winding isolates thr zero sequence network from getting paralleled. So if you have GT with one winding delta you can comfortably close the NGR

  • @sayphichit7094
    @sayphichit70943 жыл бұрын

    Hallo i am lao can speak english alitebit can you sent me a lession flie becasuse i don't know how to download load file,i need relay protection lession flie,

  • @amant1440
    @amant14402 жыл бұрын

    Are you an Protection Engineer??

  • @electricaltechnologyandind5335

    @electricaltechnologyandind5335

    2 жыл бұрын

    I have experience and interest on the subject.

  • @vickyrock83
    @vickyrock833 жыл бұрын

    Pls check your earth fault current calculations for 433 V system. For solidly grounded system (considering 1 ohm earth pit resistance) = (433 V/ 1.732 )/ Earth resistance (1ohm) = 250 Amps. Correct me if I am wrong.

  • @electricaltechnologyandind5335

    @electricaltechnologyandind5335

    3 жыл бұрын

    No it is wrong. For solidly earth system earth fault current will be mostly same with phase fault current because the earthing conductors will be interconnected. 1 ohm resistance is conductor to ground resistance.

  • @vickyrock83

    @vickyrock83

    3 жыл бұрын

    @@electricaltechnologyandind5335 pls put some disclaimer or correct this video. Else somebody will learn it in wrong way.

  • @electricaltechnologyandind5335

    @electricaltechnologyandind5335

    3 жыл бұрын

    No whatever you are saying is current to ground. But that may not be the earth fault current always.

  • @electricaltechnologyandind5335

    @electricaltechnologyandind5335

    3 жыл бұрын

    I mixed up with NGR calculation. So your observation is wrong. As the current through soil is only 250A so GPR will be 250V. Which will be well within tolerable limit. That is why for LT system we do not need to check GPR criteria.

  • @shameer2880
    @shameer28804 жыл бұрын

    Why u have selected 120 perc of full load current for 51NLV and 51NS why not 5 or 10 perc like upper relays...

  • @electricaltechnologyandind5335

    @electricaltechnologyandind5335

    4 жыл бұрын

    Since the lv neutral is solidly earthed so we can take 120 percent of flc as pickup

  • @shameer2880

    @shameer2880

    4 жыл бұрын

    @@electricaltechnologyandind5335 thanks for ur reply...but in normal condition there will be no current flow in nuetral of trfr. So settings with 10% of ct current is enough for 51NS relay operation.... and at normal condition trfr lv side the resultant current for 51NLV will be zero...so any small current flow during fault can operate 51LV say 10% of ct rating as the resultant current will not be zero... So I want to say that 10% of ct current is enough for EF pickup as we used to provide settings for EF in such a way...

  • @electricaltechnologyandind5335

    @electricaltechnologyandind5335

    4 жыл бұрын

    Yes you can do that. Minimum pick up setting for earth fault is always recommended

  • @piposilvestre3563

    @piposilvestre3563

    4 жыл бұрын

    Correct sir. 120% is too high and it might not trip during ground arcing fault

  • @aakashsatija1119

    @aakashsatija1119

    4 жыл бұрын

    Yes right... if we keep it at 120% then whats the use of having a separate 51N. It is then as good as 51 with 120%.

  • @dilipsahusahu680
    @dilipsahusahu6805 жыл бұрын

    Hindi please sir

  • @patelkaushik2996
    @patelkaushik29963 жыл бұрын

    Hindime bhejona

Келесі