R22 Walk in Cooler is warm. Pumping down a system to replace a liquid line solenoid
Тәжірибелік нұсқаулар және стиль
In this video, I will show how to pump a system down to the receiver via the king valve in order to replace a liquid line solenoid and will go over the R22 Pt chart and saturation temperatures.
Instagram / refrigerationkitchentech
Facebook / rketec
Linked in / refrigerationkitchentech
Пікірлер: 63
Would have been helpful if you showed how you managed the vacuum and the nitro flow for the braze repairs. Missing some good info here. Thanks for the video.
@cruzfernandez4554
11 ай бұрын
He at least mentioned it in the process; if someone new in the trade uses this video as a guide, it could damage the unit.
Exelente teacher , no comparison. God bless and thank you for taking all your valuable time to teach us .
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
👍🙏
You're a good teacher
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
👍 still learning new stuff everyday
Another great video. I never have any good luck with pumping systems down. I usually say screw it and recover everything into a good cylinder. Thanks again.
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
I don’t have room in my truck for an empty recovery cylinder but it’s a good idea for R22.
Thank you for taking the time to teach keep up the great videos!!
Very helpful brother👍blessing from Fiji🇫🇯
Please show complete repair, it would be very helpful
Always watching your videos, thank you they are so instructive, they have been so helpful that ever since I’ve been watching them my troubleshooting has been lot more easier God bless you for taking your time to make them. TKs
Another awesome video 👍👍👍
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
👍👍
Excellent find at the solenoid.
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
👍👍
Awesome explanation
Very nice.thanks for sharing.
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
👍
Love your video…
My god man, thank you so much
Good method tech on this one
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
👍
great video. why head pressure ambient + 30 other time it is ambient + 15 what is different?
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
Depends on what the engineer has it set at, sometime 30F (mostly older equipment) and sometimes 15F (mostly newer equipment)
👍
Great video!
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
Thanks, those compressor video you just put out are next level, great stuff my dude!
Love your videos usually but this one the box temp findings seem a little off… at first you say you want to achieve SST 42F> 71.6psig (which seems a little high) then at the end of the video the result temps/pressures it doesn’t correlate anywhere close to this.. also you used actual box temp instead of previously the desired box temp.. just wondering why? I would have used for eg desired Box temp 36F - 12F = 24F SST= 47.6psig. Still learning just looking for clarity…
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
A cap tube is fixed, meaning the pressures won’t drop as the temperature drops. This is why we use desired box temp. A TXV meters the refrigerant into the coil. So as the temperature in the box drops, the pressure will drop with it to attempt to maintain a 10TD and/or superheat.
Where can someone find these charts
You are very knowledgeable and excellent troubleshooting skills. I like that leak detector. Would you recommend it ahead of the fieldpiece models or the h10?
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
I find theH10 is the most accurate but the Dtek is the most convenient so it’s the one I pull out first. I’ve never used the field piece so I cannot comment on that one
@Thermodynamics6543
Жыл бұрын
@@REFRIGERATIONKITCHENEQTECH Thanks much
@pavelspilberg9310
Жыл бұрын
@@REFRIGERATIONKITCHENEQTECHDoes it work for natural gas as well?
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
No, I use the dtek gas mate for that
@pavelspilberg9310
Жыл бұрын
@@REFRIGERATIONKITCHENEQTECH thanks
No vacuum on the liquid line? Would have to add a process valve. What did you do ?
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
Yes absolutely need to vacuum, or non condensibles will most likely form in th4 system. The vacuum was done with both the receiver and compressor suction valves front seated. Can’t do a nitrogen test because these valves love to leak, so we use the refrigerant that’s in the System.
How do you vaccum the side that you replaced the solenoid?
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
Magnet on the solenoid and vacuum from the compressor suction port.
🇺🇲💪👍❄️ great informative vid. When ur doing manual pumpdown the tstat needs to b calling so solenoid is energized so all refrigerant is out of low side, correct?
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
In just a normal pump down, the solenoid valve should be closed (thermostat is not calling for cooling) which will pump out all of the refrigerant between the solenoid and the suction valve on the compressor.
@shine-cg9uf
Жыл бұрын
@@REFRIGERATIONKITCHENEQTECH correct but in ur situation u needed the valve energized so all refrigerant would b out of line on both sides of the solenoid valve. Right ? N stopped at receiver
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
Yes in this situation
@shine-cg9uf
Жыл бұрын
@@REFRIGERATIONKITCHENEQTECH thanks hopefully the flyers get the no. 1 pick they need help. Go leafs
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
Lol, Bedard is gonna be a stud. I’m a habs fan, hate the leafs lol
Can you recommend which is best leak detector for 404a and 134a
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
Dtek and H10 Are my go to
@sadiqzayn4088
Жыл бұрын
Okay
What’s name of solenoid tool? Thanks
What is the app or web page you use to troubleshoot?
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
These are just charts I made on excel
@davejohnsonnola1536
Жыл бұрын
Went to school for this a lifetime ago but never went into the field. Now as an F&B manager / operator error vs mechanical malfunction triage coordinator, enjoy/putting to use and finally figured out the new company phone screenshot fingerbang to email myself your excel troubleshooting spread sheets! Who says old dogs can't learn new tricks! Woof.
Do you mentor? Or do online teaching sessions or anything of those sorts?
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
I’ve been getting a lot of requests for this so I am considering starting something
@billyhorton5779
Жыл бұрын
@@REFRIGERATIONKITCHENEQTECH I believe people would be willing to pay a nominal fee for a membership or such as other youtube channels do.
@jaysonhines1
Жыл бұрын
I would pay. I like your teaching style.
@davejohnsonnola1536
Жыл бұрын
@@REFRIGERATIONKITCHENEQTECH don't know the specifics but Patreon or KZread subscriptions seem common?
@jaysonhines1
9 ай бұрын
@REFRIGERATIONKITCHENEQTECH just start to put out a syllabus for beginners, offer a small price, and watch the classes take off. I would take all the classes, and even seasoned veterans will still take on new equipment. It would even take off if you did a simple singe Class for techs taking their epa 608 exam for that specific type I,II, or III.
What do you call a split?
@REFRIGERATIONKITCHENEQTECH
Жыл бұрын
Condensor TD
@dwayneclarke2314
Жыл бұрын
@@REFRIGERATIONKITCHENEQTECH how to determine condenser TD?