HVAC: What Is A Intermittent Pilot Ignition Control Module/Sequence Of Operation/Troubleshooting

Ғылым және технология

HVAC: What Is A Intermittent Pilot Control Module & How Does It Work? Intermittent Pilot Control Module For Gas Furnace/Boilers Explained
How to wire and install an ignition control HVAC
Intermittent Pilot Ignition Control Module Sequence Of Operation
HVAC Ignition Control Troubleshooting
=================================================
Sequence of Operation (Utec 1003-600a Series)
1. Call for Heat: The thermostat contacts close,
powering Terminal 2 on the G600.
2. Pilot Flame Checking: If the G600 detects the
presence of pilot flame (from the flame sensor)
when there should not be (i.e., before the call for
heat), the G600 will not operate.
3. Vent Damper Actuation: On models electrically
interlinked with a vent damper, the G600 powers
the vent damper motor. Once the vent damper
reaches its open position, the motor stops, and the
G600 is allowed to begin the prepurge (prepurge
models only) or trial for ignition.
4. Prepurge: The appliance prepurge fan or relay is
energized through the thermostat contacts. The
control delays for the 4-second prepurge before
simultaneously opening the pilot valve and
supplying a continual spark at the pilot burner
(models with prepurge only).
5. Trial for Ignition: During the trial for ignition, the
G600 energizes Terminal 1 and the spark
transformer, which opens the pilot valve and
activates the spark in an attempt to light the pilot
burner. If the G600 detects the presence of the
pilot flame within the trial-for-ignition time, it
proceeds to the run state. If the G600 does not
detect the presence of the pilot flame within the
trial-for-ignition time, it de-energizes all outputs
(locks out) and remains in this condition until the
thermostat is recycled. The G600AX and G600AY
have infinite trials for ignition and spark
indefinitely.
6. Run: If pilot flame is detected within the trial for
ignition, Terminal 3 is energized and the spark
transformer is de-energized, which opens the main
valve and shuts off the spark. The pilot valve and
main valve are kept open throughout the run state.
The control remains in the run condition until the
call for heat ends or until a flameout occurs.
7. Flameout: If, during the run state, the control
detects the loss of pilot flame, it de-energizes the
main valve within 0.8 second (flame failure
response time). The pilot valve is kept open, the
spark is re-established, and another trial for
ignition begins.
=================================================
Honeywell S8610U Universal Intermittent Pilot Module
Field service replacement for most Honeywell, Robertshaw, Johnson, and UTEC (HSC) Intermittent Pilot Ignition Modules. Provides electronic control of most intermittent pilot ignition systems used on gas-fired furnaces, boilers, and other heating appliances.
• Provides ignition sequence, flame monitoring and safety shutoff for intermittent pilot central furnaces and heating appliances.
• Provides 100 percent pilot gas shutoff if pilot fails to light; after 6- minute delay, trial for ignition is repeated. Ignition trial/delay sequence is repeated until the appliance lights or call for heat is removed.
• For use with Natural or LP gas.
• For use in single rod or dual rod/remote sense applications. Includes relay contacts for use with any intermittent pilot gas control string with maximum 1.0A pilot or 2.0A main valve rating; Honeywell VR8204, VR8304 or VR8345M combination gas control recommended.
• Functional equivalent of S86, S8600, S8610 and S90 modules.
• Includes spark cable adapters to allow field replacement of both Honeywell and competitive controls without replacing existing spark cable.

Пікірлер: 88

  • @rubensabeast
    @rubensabeast2 жыл бұрын

    I understood how to troubleshoot these before the video but it was just steps never a meaning behind it, literally the best anyones ever explained this control lol love the vids

  • @JumpermanTech

    @JumpermanTech

    2 жыл бұрын

    That is so awesome to read. Appreciate the feedback very much🙏 Glad you love the vids 🙃 Stay tuned for new videos every week! 🔧⚡

  • @stasanoffstasanov9224

    @stasanoffstasanov9224

    Жыл бұрын

    @@JumpermanTech скажи какое напряжение подается на mv.pv?

  • @teklesenbetgebreamlak7365

    @teklesenbetgebreamlak7365

    Жыл бұрын

    You are make it easy to understand how to troubleshoot, l have no enough words to say thanks, you are the best thankyou again

  • @pcakes1878
    @pcakes1878 Жыл бұрын

    ive been a licensed gas tech for years, but i only work on this stuff in the winter. Supermarket refrig keeps me busy all other times. its nice to have a refresher every now and then

  • @cruzruelaz
    @cruzruelaz2 ай бұрын

    Found a new resource, thank you

  • @tylerr8083
    @tylerr8083 Жыл бұрын

    Excellent video. I was trying to understand this control and you made it so clear. Will help with troubleshooting. Cheers

  • @eriktorres9861
    @eriktorres9861 Жыл бұрын

    Thanks man, you're an excellent teacher.

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    You're welcome & thank you! Much appreciated 🙏 Stay tuned for new videos every week🔧⚡️

  • @williamserver4332
    @williamserver4332 Жыл бұрын

    Great video. I wish I had this info many years ago when I was new to HVAC.

  • @easyon12

    @easyon12

    Жыл бұрын

    I'm 20 years into the biz and I say the same thing everyday!

  • @jrh86
    @jrh867 ай бұрын

    Excellent 👍👍👍💯

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    Thank you! Stay tuned for new videos every week🔧⚡️

  • @flexortiz92
    @flexortiz922 жыл бұрын

    MY BROTHA BACK AT IT AGAIN! Keep doing a great job at this KZread my friend I’ve been in the field lemme show the channel some love

  • @JumpermanTech

    @JumpermanTech

    2 жыл бұрын

    My brother Ortiz! Appreciate your support over all this time & thank you! Respect✊️ Stay tuned for new videos every week⚡🔧

  • @gregord2759
    @gregord27595 ай бұрын

    well done--it's a great explanation for the novice and pros.

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    Thank you very much! Stay tuned for new videos every week 🔧⚡️

  • @spongklong508
    @spongklong5082 жыл бұрын

    Thank you. Very imformative.

  • @JumpermanTech

    @JumpermanTech

    2 жыл бұрын

    You're very welcome & thank you! Glad you found this video informative. Stay tuned for new videos every week⚡🔧

  • @mrtrek64
    @mrtrek648 ай бұрын

    Great viddeo, thank you. On the Honeywell control you remove the black jumper to use with 2 rod systems. Keep it in place for single rod.

  • @marksiegfried
    @marksiegfried Жыл бұрын

    Excellent video, thanks for posting..

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    Thank you! Stay tuned for new videos every week🔧⚡️

  • @chris27289
    @chris272892 жыл бұрын

    I tried to find info on this a while back. I'm planning on a custom project and this will help a lot.

  • @JumpermanTech

    @JumpermanTech

    2 жыл бұрын

    Awesome! Glad you found this video helpful & good luck with your future project. Stay tuned for new videos every week⚡🔧

  • @TitoGomez-ue8jw
    @TitoGomez-ue8jw Жыл бұрын

    Very well explained!!!

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    Thank you! Stay tuned for new videos every week🔧⚡️

  • @wd8557
    @wd85572 жыл бұрын

    Very well explained.

  • @JumpermanTech

    @JumpermanTech

    Жыл бұрын

    Thank you! Much appreciated. Stay tuned for new videos every week🔧⚡️

  • @thesilentonevictor
    @thesilentonevictor2 жыл бұрын

    Multi talented tech

  • @JumpermanTech

    @JumpermanTech

    2 жыл бұрын

    My brother! Thank you! Appreciate the feedback & you watching 🙏⚡

  • @shytown2406
    @shytown2406 Жыл бұрын

    OUTSTANDING very informative. What a main compoent on my Weil Mclain Gas Boiler that will go bad . for my home

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC2 жыл бұрын

    The Honeywell S8610U does also have a separate flame sensor terminal. It is the spade terminal below the sparker. It has a little black wire coming from the controller and pre-wired to the terminal already. You remove it for a separate flame sensor and spark rod, or you can use the spark/ flame sense terminal as you described. It depends on the set up you have.

  • @dudemann8654

    @dudemann8654

    Жыл бұрын

    Thank you! I've been searching for an answer for what to do if you have separate lines for spark and sense and you answered it. You're awesome!!

  • @zacharynolder3385

    @zacharynolder3385

    6 ай бұрын

    Just wired one in today, was kind of confused while I was there, had no trouble with the diagnostic. But swapping a 2902 with one of the Honeywell controls had me a little stumped. Good call on that because I said the same thing.

  • @yungchan8914
    @yungchan8914 Жыл бұрын

    Thanks extremely helpful

  • @JumpermanTech

    @JumpermanTech

    Жыл бұрын

    You're very welcome & thank you! Glad you found this video helpful. Stay tuned for new videos every week🔧⚡️

  • @playmusic972
    @playmusic9726 ай бұрын

    hey this video was very helpful, well explained the operation. thank you so much.

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    You're very welcome & thank you! Stay tuned for new videos every week🔧⚡️

  • @brandonpaul26
    @brandonpaul266 ай бұрын

    Excellent explanation 👌

  • @andrewfordpics
    @andrewfordpics Жыл бұрын

    Great helpful video...Thankyou

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    Glad you found this video helpful 👍 Thank you! Stay tuned for new videos every week🔧⚡️

  • @zipperdingo6385
    @zipperdingo6385 Жыл бұрын

    Great explanation👍

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    Thank you! Stay tuned for new videos every week🔧⚡️

  • @HalfPro
    @HalfPro4 ай бұрын

    Flame sense signal (uA) comes on sense wire and not on ground terminal as said in the video. Sense current flows only if the ground wire is properly connected to chassis.

  • @izzybell11
    @izzybell112 жыл бұрын

    Excellent presentation and tutorial. Job well done JMT.

  • @JumpermanTech

    @JumpermanTech

    2 жыл бұрын

    Thank you very much! Glad you enjoyed the presentation. Appreciate the feedback🙏 Stay tuned for new videos every week⚡🔧

  • @odiferousmusky1299
    @odiferousmusky12992 жыл бұрын

    thanks Jumper Man!

  • @JumpermanTech

    @JumpermanTech

    Жыл бұрын

    You're very welcome & thanks for watching! Stay tuned for new videos every week🔧⚡️

  • @abelurrutia1192
    @abelurrutia11922 жыл бұрын

    Great video.

  • @JumpermanTech

    @JumpermanTech

    Жыл бұрын

    Thank you! Stay tuned for new videos every week🔧⚡️

  • @veganord047
    @veganord0477 ай бұрын

    Thank you.

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    You're very welcome! Thank you! Stay tuned for new videos every week🔧⚡️

  • @jasonjokiel7188
    @jasonjokiel7188 Жыл бұрын

    Great video!!!!!!

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    Thank you! Stay tuned for new videos every week🔧⚡️

  • @lloydrmc
    @lloydrmc Жыл бұрын

    Thank you so much! My controller is a "UT" that looks almost identical to your example.

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    Thank you! Stay tuned for new videos every week🔧⚡️

  • @Bolshevik337
    @Bolshevik3372 жыл бұрын

    Thanks you so much.

  • @JumpermanTech

    @JumpermanTech

    Жыл бұрын

    You're very welcome & thanks for watching! Stay tuned for new videos every week🔧⚡️

  • @luvdogsandhorses
    @luvdogsandhorses2 жыл бұрын

    Nice explanation

  • @JumpermanTech

    @JumpermanTech

    Жыл бұрын

    Thank you! Appreciate the feedback. Stay tuned for new videos every week🔧⚡️

  • @raviyadav8743
    @raviyadav8743 Жыл бұрын

    Very helpful video 😊😊

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    Glad you found this video helpful! Thank you! Stay tuned for new videos every week🔧⚡️

  • @isonlynameleft
    @isonlynameleft Жыл бұрын

    Awesome!

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    Thank you! Stay tuned for new videos every week🔧⚡️

  • @alialhisnawi5673
    @alialhisnawi5673 Жыл бұрын

    Wonderful

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    Thank you! Stay tuned for new videos every week🔧⚡️

  • @olivasurueta
    @olivasurueta7 ай бұрын

    VERY GOOD EXPLAINED, ONLY IF YOU CAN PUT EXAMPLE IN LIVE

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    Thank you! Stay tuned for new videos every week🔧⚡️

  • @MarioDallaRiva
    @MarioDallaRiva2 жыл бұрын

    Bravo! You’re a natural at instruction. Very clear and thorough 👏🏻 ? Is that micro Amps listed on the unit cover (square waves)?

  • @RockoRocko-rz7kx

    @RockoRocko-rz7kx

    Жыл бұрын

    Yes

  • @jmead6121
    @jmead61215 ай бұрын

    Thanks very Much I have the same model # ignition control on an York 300k gas rooftop unit only difference is the labels of terminals .mine shows MV - mv/pv - R1 rollout - TH - gnd buner - 24v gnd - sense - spark so ian assuming TH is my 24 v call Thanks again now i can go back fin trouble shooting no heat call

  • @odishoodisho4904
    @odishoodisho49047 ай бұрын

    Thanks for sharing your experience… if we want to change the module we have to put the same module number or there is a universal module work with all? Thanks in advance

  • @andreagate542
    @andreagate5422 жыл бұрын

    Thank you for another great video…..So for flame sensor you want to try And achieve 3 µA corrrect??? The next step is A signal hast to go back to bored via the intermittent pilots burner ground In order to open the main valve???Is that same signal in Micro amps???? Many Thxs

  • @mikepotter3802
    @mikepotter3802 Жыл бұрын

    How/when do you check the voltage across MV/PV and PV for 24V? During spark? At any time? What if you have no 24V (instead 4.0V) across here? My system is sparking but does not light pilot. I forced sense with a lighter and got MV to light briefly.

  • @aifrisyad7491
    @aifrisyad7491 Жыл бұрын

    hello there, for the GND burner and 24V wire…where should i connect them from module into…thanks man

  • @ddteamrc6461
    @ddteamrc64612 жыл бұрын

    Question, why wouldn't the ignitor be clicking?

  • @litesp
    @litesp Жыл бұрын

    I have an early-90s Carrier 58GSC furnace that does not spark or flow pilot gas when the thermostat calls for heat. There is 28V going to the Ignition module. Could the problem be the Ignition module, igniter, electrode, electrode wire, gas valve. I'm thinking to start at the ignition module, but I'm not sure how to isolate and troubleshoot that. Would pilot gas flow if there is no spark? Please advise.

  • @user-hw6ws2cn9j
    @user-hw6ws2cn9j7 ай бұрын

    What is terminal th-w on other control?

  • @powerstroke1914
    @powerstroke19147 ай бұрын

    Is there a way to jumper the utec control to see if module is bad

  • @jyphc1679
    @jyphc16792 жыл бұрын

    Hi JMT Can you do a AAON’s initial module ? Please thank you

  • @JumpermanTech

    @JumpermanTech

    2 жыл бұрын

    Hello, I will look into that & try to make a video. Haven't came across that yet but I might be able to make a video using some photographs and wiring diagrams. Stay tuned for new videos every week⚡🔧

  • @leonlin4714
    @leonlin47143 ай бұрын

    Why does my boiler stop working when I plug in wire GND (burner)? But it works without plugging in this wire for long time.

  • @jesustommy4009
    @jesustommy4009 Жыл бұрын

    👏🏻👏🏻✍🏻✍🏻✍🏻

  • @JumpermanTech

    @JumpermanTech

    Жыл бұрын

    🙏🙏🔧⚡️

  • @salvenezia1817
    @salvenezia18178 ай бұрын

    My control only lights burner if I disconnect my 24vgnd. Then the burner light then shuts off after a sec

  • @MB-zk7pz
    @MB-zk7pz8 ай бұрын

    I'm sure I'll still forget when the homeowner is standing behind me slurping coffee w anxiety of wondering if I know what I'm doing n how much it's gonna cost n then his brother n dad come in too.

  • @JumpermanTech

    @JumpermanTech

    5 ай бұрын

    😂😂😂 Stay tuned for new videos every week🔧⚡️

Келесі