How to Upgrade an Electrical Panel to 200-Amp Service (Part 2) | This Old House

Тәжірибелік нұсқаулар және стиль

Master electrician Scott Caron installs a new panel to complete a service upgrade.
Watch part one here: • How to Upgrade an Elec...
#ThisOldHouse #AskTOH
SUBSCRIBE to This Old House: bit.ly/SubscribeThisOldHouse
Steps:
1. Use diagonal-cutting pliers to sever all wires inside existing electrical panel.
2. Unscrew and remove old electrical panel from the wall.
3. Screw a large ¾-inch-thick plywood panel to the wall for mounting the new electrical panel. 4. Feed the SE cable through the top of the new electrical panel, then screw the panel to the plywood. Use a torpedo level to ensure the panel is level.
5. Make all the electrical connections inside the electrical panel.
6. Feed the house circuits into the panel, making sure each cable passes through a cable connector.
7. Connect the bare-copper ground wires and white-insulated wires to the ground and neutral bar inside the panel.
8. Plug new circuit breakers into the bus bar.
9. Run the main ground wire from the bottom of the electrical panel to the copper water main.
10. Have the utility company reconnect the electrical cables to the exterior of the house.
11. Label each breaker with the correct house circuit.
About This Old House TV:
This Old House is the No. 1 multimedia home enthusiast brand, offering trusted information and expert advice through award-winning television, a highly regarded magazine, and an information-driven website. This Old House and Ask This Old House are produced by This Old House Ventures, LLC and are presented on PBS by WGBH Boston.
Follow This Old House and Ask This Old House:
Facebook: bit.ly/ThisOldHouseFB
Twitter: bit.ly/ThisOldHouseTwitter
bit.ly/AskTOHTwitter
Pinterest: bit.ly/ThisOldHousePinterest
Instagram: bit.ly/ThisOldHouseIG
Tumblr: bit.ly/ThisOldHouseTumblr
How to Upgrade an Electrical Panel to 200-Amp Service (Part 2) | This Old House
/ thisoldhouse

Пікірлер: 1 300

  • @derewreck
    @derewreck3 жыл бұрын

    Legend says the breaker panel is unlabeled to this day.

  • @guygrotke7476

    @guygrotke7476

    3 жыл бұрын

    That is something a homeowner can do with no danger of electrocution. It really helps to have two people and radios or cell phones so you can talk to each other.

  • @Bremend

    @Bremend

    2 жыл бұрын

    Yea, I probably should label mine, but I usually just off the power to the entire panel instead...

  • @gophersgirl

    @gophersgirl

    2 жыл бұрын

    I call that shitty customer service, as an electrician I always label the panel with a printed label, not a handwritten squiggly notes...and Canada has very different rules too!

  • @Vanilla_Icecream1231

    @Vanilla_Icecream1231

    2 жыл бұрын

    @@gophersgirl true also in Canada you can’t use pvc with a few c clips you must use a mast made of rigid conduit with bolts holding it in place it also must go through the roof for more support also only th hydro can pull meters

  • @impoppy9145

    @impoppy9145

    2 жыл бұрын

    @@gophersgirl I call that waste of expensive time which adds to the expensive bill.

  • @atkgrl
    @atkgrl7 жыл бұрын

    For all general people watching you do NOT just cut the wires regardless. You mark them all first along with current Breaker size unless you want to rip out all the dry wall and trace every single line. Remember this is for TV purposes. Keep in mind you also need GFCI and AFCI now to meet the safety codes.

  • @leonardholt5311

    @leonardholt5311

    4 жыл бұрын

    PlayGirl hahahaha! Do what?! You can determine the breaker size needed by the gauge of the wire. No marking needed. Jackwagon

  • @dr.cupcakes626

    @dr.cupcakes626

    3 жыл бұрын

    @@leonardholt5311 no you can't. Just because there's a 12 awg wire at the panel doesn't mean there isn't a 14 awg somewhere in the circuit

  • @electricaf365

    @electricaf365

    3 жыл бұрын

    @@dr.cupcakes626 so when you do a panel change, or replace a breaker, you should go throughout the whole house and trace down every wire to make sure the wire size doesn’t change?

  • @dr.cupcakes626

    @dr.cupcakes626

    3 жыл бұрын

    @@electricaf365 ideally yes. But if this isn't possible the only truly safe solution is to downgrade the breaker ampacities

  • @electricaf365

    @electricaf365

    3 жыл бұрын

    @@dr.cupcakes626 bullshit. If you get hired to change out a panel, then you change out a panel.

  • @robbitt
    @robbitt6 жыл бұрын

    He dumped the hardest part onto the homeowner. Labeling the breakers!!!

  • @zibp7090

    @zibp7090

    6 жыл бұрын

    He said "All I need to do...". The 'I' was short but distinguishable

  • @robbitt

    @robbitt

    6 жыл бұрын

    z ibp, maybe he did. Regardless, it was a joke.

  • @Mookaton

    @Mookaton

    3 жыл бұрын

    What's hard about it? Shut it off and see what shuts off, test the sockets in that room to be sure....done.

  • @ryanshannon7703

    @ryanshannon7703

    3 жыл бұрын

    Dude was so giggity he'd be happy to do it himself.

  • @thomasreedy4751

    @thomasreedy4751

    2 жыл бұрын

    @@Mookaton How many outlets and light switches are in your house? How far from your breaker box are your outlets? Let’s multiply the number of outlets by the number of circuits and then we can get the number of possible combinations. It can take hours to do this. Sure, you can start the process of elimination to save some time, but then you have the one outlet in the living room that is not on the same circuit as the other living room outlets. Or you have the recently installed bath fan hooked into the room next door and not with the bathroom lights. If the breaker box isn’t properly labeled, it’s likely because over the last 30+ years some handyman playing electrician didn’t take the time to think out your upgrades.

  • @dukdgr8
    @dukdgr88 жыл бұрын

    No long talks. All informative and straight to the point. This is how a video is done!

  • @andrewmeinders5712

    @andrewmeinders5712

    4 жыл бұрын

    @Yo Mama but to the home owner that watches these to DIY he looks genius...lol

  • @user-bh3cz9lm9j

    @user-bh3cz9lm9j

    3 жыл бұрын

    @@andrewmeinders5712 But to the rest of us, he looks like an arrogant buffoon.

  • @jefftickleschitz1265

    @jefftickleschitz1265

    3 жыл бұрын

    Yea, if you want a bunch of morons electrocuting themselves and starting electrical fires.

  • @darrengibson1115

    @darrengibson1115

    3 жыл бұрын

    If you think this a good work I have a bridge to sell you

  • @buggsy5

    @buggsy5

    3 жыл бұрын

    @@darrengibson1115 At least the wiring was fairly neat. I have seen some real squirrel nests created by a sloppy/lazy electricians.

  • @Rob-nd6eb
    @Rob-nd6eb11 ай бұрын

    Master electrician. He did a fantastic job keeping it simple and neat. I need that man here for my 200 amp service install. Excellent work. 👍

  • @jamedlock83

    @jamedlock83

    Ай бұрын

    It ain't that hard. I'm not an electrician and I could do it.

  • @Rob-nd6eb

    @Rob-nd6eb

    Ай бұрын

    @@jamedlock83 Same. I do most of my own work. Time is more what I need these days.

  • @cumminsman6896
    @cumminsman68966 жыл бұрын

    This guy does an awesome job at keeping it simple and to the point. Well done. This is how (HOW TO) videos should be.

  • @seanjuth

    @seanjuth

    4 жыл бұрын

    Well said

  • @darrengibson1115

    @darrengibson1115

    3 жыл бұрын

    Should be careful: he left a lot information out .

  • @mattrob15

    @mattrob15

    3 жыл бұрын

    Its nice to watch, but not a guide on how to do it yourself. Not enough details.

  • @paladro

    @paladro

    3 жыл бұрын

    @@darrengibson1115 rudiementary 5-6 minute overview... you gotta pay for more knowledge ;)

  • @darrengibson1115

    @darrengibson1115

    3 жыл бұрын

    @@paladro true .For those diy be careful check city and county codes all free information . Also purchase a NEC code book.

  • @SusceptiblexMe
    @SusceptiblexMe7 жыл бұрын

    I wanted to see the part where he's figuring out which circuit goes to what 20 times.

  • @lexluther8370

    @lexluther8370

    7 жыл бұрын

    + SusceptiblexMe - outlets are pretty easy, you just move a vacuum from circuit to circuit. The lights in the basement are easy. You turn on a light and when the person upstairs tell you it went off you got it. Dryer and range is 240, pretty easy.

  • @ERLong-ww7yn

    @ERLong-ww7yn

    7 жыл бұрын

    Some of us use a circuit tracer. You plug a transmitter into a circuit and the "sniffer" runs over the breakers a couple of times. Once calibrated it'll beep on the breaker linked to the circuit the transmitter is plugged into.

  • @lexluther8370

    @lexluther8370

    7 жыл бұрын

    +E.R.Long - they have really wide price range. Are they all the same? Are you an electrician and use your's a lot?

  • @ERLong-ww7yn

    @ERLong-ww7yn

    7 жыл бұрын

    I have the Ideal Circuit Tracer. I paid around $100 for the kit, Canadian dollars. It has the adapter for plugging the transmitter into a light socket as well as the alligator clip adapter for tracing light switches. I find it very handy. I went on a service call awhile back and the homeowner told me he had an electrician and an apprentice spend three days mapping the circuits in his house. I could have done the whole house in 4-5 hours with the tracer.

  • @gragor11

    @gragor11

    7 жыл бұрын

    And add a radio in what you assume is a different cct then the vacuum and bring the end of an extension cord down to the panel with a light on it plugged in somewhere else and there you go. More indications about what is going on w/ the ccts.

  • @professordanfurmanek3732
    @professordanfurmanek37322 жыл бұрын

    Outstanding video! This shows that great electrical work is always clean and neat. Leaving extra length in the wires is also important for future work. Metal gas lines are also often grounded. Well done Ask This Old House!!!

  • @lcaphotoboothcanada2486
    @lcaphotoboothcanada24866 жыл бұрын

    Just seeing the guy using a torque wrench on the electrical box means he does take care.

  • @jefftickleschitz1265

    @jefftickleschitz1265

    3 жыл бұрын

    I saw a regular socket wrench, not a torque wrench. But even if it was a torque wrench, hes on TV. He should be doing things properly.

  • @jimeneazy5999

    @jimeneazy5999

    3 жыл бұрын

    Are you talking about the dewalt impract driver? If so, that’s not a torque wrench 🤣

  • @cammy729
    @cammy7293 жыл бұрын

    Johnny Sins is an electrician too? Man this guy does everything!

  • @TheSpud1129

    @TheSpud1129

    2 жыл бұрын

    He loves his 200 Amp wire...

  • @electriciandallastx9182
    @electriciandallastx91827 жыл бұрын

    Thanks for the suggestions you have contributed here.

  • @Guardducks
    @Guardducks2 жыл бұрын

    Miss Scott , he was good.

  • @DBJ99_
    @DBJ99_3 жыл бұрын

    “This should never be done by homeowners” *proceeds to show homeowners exactly how to do it*

  • @anvilhead59

    @anvilhead59

    2 жыл бұрын

    But some homeowners know how to do this already. ;)

  • @susanc6828

    @susanc6828

    2 жыл бұрын

    he was not showing him how to do it, he was just throughly explaining what and why he was doing what he was doing

  • @BestLittleStudio

    @BestLittleStudio

    2 жыл бұрын

    Proceeds to double lug the grounds, not trim tags, and make the water meter nearly impossible to service and work with.

  • @gophersgirl

    @gophersgirl

    2 жыл бұрын

    @@anvilhead59 it only voids your house insurance when they find out you did some electrical yourself and the house burns down...that's why us sparkies pay a lot in licensing and insurance...

  • @emreduygun

    @emreduygun

    2 жыл бұрын

    Homeowner's should never go down there ! lol

  • @Miguelcoolio
    @Miguelcoolio3 жыл бұрын

    Its 4am I go to work in 2 hours Idk why youtube suggested this........ But now I want to change my breaker box

  • @tomsmith3045
    @tomsmith30454 ай бұрын

    Most concise service upgrade video I've ever seen. Nice work!

  • @ericstandefer9138
    @ericstandefer91386 жыл бұрын

    I like how clearly you speak, well done.

  • @denisrhodes54

    @denisrhodes54

    4 жыл бұрын

    tommy is better

  • @Squarehead45
    @Squarehead454 жыл бұрын

    Important to note, Bending the wire in a loop ALSO gives you the ability to Reattach into a new lug if by chance you have a Bad Connection and it burns up. If not for the "Extra Wire" in that loop, you would have to replace the incoming cable OR install a "J-Box" above the breaker panel to splice in longer wire. Good Idea here.

  • @walterbrunswick

    @walterbrunswick

    2 жыл бұрын

    Yes! Always leave slack!

  • @gophersgirl

    @gophersgirl

    2 жыл бұрын

    I was also explained that if there is a surge like implosion there is slack in the wire so not everything gets ripped out from under the lugs....

  • @brandonreyes5567

    @brandonreyes5567

    Жыл бұрын

    On god thow

  • @thomasfrye313

    @thomasfrye313

    Жыл бұрын

    That's why it's called a service loop...

  • @shaystern2453

    @shaystern2453

    Жыл бұрын

    capt obvious welcome to the chat

  • @southstreetbarbecue7875
    @southstreetbarbecue78754 жыл бұрын

    Thank you for helping me understand that this is NOT something I'm going to do myself.

  • @youarehere1251

    @youarehere1251

    3 жыл бұрын

    How about 3 outlets and no appliance, easy job.

  • @viralpatel5338
    @viralpatel53389 ай бұрын

    Very well professionally explained...the guy is real pro

  • @beardedelephant3023
    @beardedelephant30232 жыл бұрын

    Learned a lot watching this guy. Hope to find an equally knowledgeable electrician in my area

  • @auletjohnast03638
    @auletjohnast036383 жыл бұрын

    I would label all the circuits before replacing the panel.

  • @micw8422

    @micw8422

    2 жыл бұрын

    my existing panel has some 15a, 20a, dual 15, dual 20, 240. So, I would want to map it over to the new panel with the proper amp breaker. figuring out the exact label would be secondary to that.

  • @mattsabeast5

    @mattsabeast5

    2 жыл бұрын

    No reason to most times. If the panel is well labeled it's most likely not in need of an upgrade as it's been addressed in a remodel or addition to the home. And if you know what your doing you can keep things well organized enough to land conductors in the proper breakers and phases. Also its a great well-paid day to shut every breaker on and off to locate and label after.

  • @nityking1
    @nityking15 жыл бұрын

    electricians are the most critical of each others work than any other profession

  • @linuss5958

    @linuss5958

    3 жыл бұрын

    Yes and its an International thing.

  • @backdoorwolf666

    @backdoorwolf666

    2 жыл бұрын

    For good reason. Smallest mistake could be deadly.

  • @johndavies2949

    @johndavies2949

    3 ай бұрын

    Maybe cause bad wiring kills people.

  • @samuelayalaelcasanova9893
    @samuelayalaelcasanova98933 жыл бұрын

    This guys makes it look so easy

  • @jfarinacci0329
    @jfarinacci03293 жыл бұрын

    Good explanations. Good video. Thank you.

  • @danbasta3677
    @danbasta36773 жыл бұрын

    You know what, I love this program, Ask This Old House. Great information here about just about everything you need to know to maintain your home from landscaping, to electricial to plumbing, carpentery, masonry projects, just EVERYTHING! sad though that in the Pittsburgh region, WQED channel 13 fell off the radar screen and you can't get it anymore on over the air broadcasts like in the good old days.

  • @meltormee6771

    @meltormee6771

    2 жыл бұрын

    GROUNDING TO THE COLD WATER SUPPLY IS A BAD IDEA AS WELL.

  • @wastedyouth191985
    @wastedyouth1919854 жыл бұрын

    In my Area it takes 6-8 months for the power company to come out and when you do get an appointment, it's a 3 week window and a 50/50 crapshoot if they actually show up.

  • @paulksefvwefvwefvwerv6767

    @paulksefvwefvwefvwerv6767

    3 жыл бұрын

    Pull the meter at the entrance..

  • @johnnyboy13642

    @johnnyboy13642

    3 жыл бұрын

    @@paulksefvwefvwefvwerv6767 Can't do that, that's tampering. You need to have your service disconnected first or you're actively messing with the meter.

  • @socommaster
    @socommaster6 жыл бұрын

    Very descriptive video! Awesome!

  • @omardiaz3539
    @omardiaz35397 жыл бұрын

    great video. well explained!!!

  • @jimeneazy5999
    @jimeneazy59993 жыл бұрын

    Part 3: Labeling a mismanaged circuit breaker.

  • @canyoncrow11
    @canyoncrow118 жыл бұрын

    This why if you have the chance to go get the training and the license, you can save a lot of money if you need this done.You will always have work like HVAC and Plumbing.You will always have a skill that you can use anywhere.

  • @RoastBeefSandwich

    @RoastBeefSandwich

    3 жыл бұрын

    True these trades will never be outsourced and will always be in demand.

  • @johnpachner9236

    @johnpachner9236

    3 жыл бұрын

    How do get the training if the union doesn’t have openings and no shops around me have any openings? Is there a better way than going through the ibew?

  • @RoastBeefSandwich

    @RoastBeefSandwich

    3 жыл бұрын

    @@johnpachner9236 I don't live in a Union state so I may be the wrong person to ask, but here you can get trained to be an electrician or plumber at a local community college. I don't know if it's any different or not in a Union state.

  • @ryanshannon7703

    @ryanshannon7703

    3 жыл бұрын

    @@RoastBeefSandwich I was looking into it last night and there's a vocational school that has an electrician program. Not sure how much it is, but probably pretty cheap compared to an associates degree, let alone an undergrad or higher. I work in I.T. and make near as makes no difference to 6 figures, but this looks quite fun and you know it's more than enough to pay the bills and can definitely help with any future real estate property investments. It's really a no brainer if you have an interest in it.

  • @Ratkill9000

    @Ratkill9000

    3 жыл бұрын

    @@ryanshannon7703 When I went to college for welding between 2011 and 2012, it was $6500 for the year. So it's close to that for HVAC and electricians. I know here in Lincoln, NE, there's a couple companies that'll train both fields that are not union. Which is a benefit.

  • @weelgunny
    @weelgunny2 жыл бұрын

    Thoroughly explained.

  • @HungNguyen-gg9xe
    @HungNguyen-gg9xe3 жыл бұрын

    Excellent instructions part 1 & 2

  • @garrythompson4132
    @garrythompson41323 жыл бұрын

    There is a difference between using a 200 amp panel on a 100 amp service and upgrading your 100 amp service to a 200 amp service. Besides using larger service entrance conductors for the 200 amp upgrade, you most likely will need to have it inspected by the city. Many utility companies require a passed inspection when they come out to change out the meter. You will also need to upgrade the meter socket as well. And I ALWAYS trace out the circuits and label them before disconnecting so I know what neutrals are sharing what breakers.

  • @gophersgirl

    @gophersgirl

    2 жыл бұрын

    They probably didn't show that the NS cable was also upgraded...

  • @gusc6785

    @gusc6785

    2 жыл бұрын

    I don't think which neutrals are sharing what circuits shouldn't matter since they are all getting connected to same bus bar . What I do is mark which leg they are on so as to make sure the circuits are all on the same shared leg as previously.. Also he is double tapping the ground s into the 1 screw on buss bar , should be 1 wire per 1 screw

  • @jaycahow4667

    @jaycahow4667

    Жыл бұрын

    @@gusc6785 i saw the double grounds as well but I see that all the time.................

  • @jblyon2

    @jblyon2

    Жыл бұрын

    @@gusc6785 Neutrals should only matter if GFCI/AFCI breakers are getting installed. Otherwise they all just go to the same bus bar anyway. You are permitted to double tap neutrals on the bus bar, at least provided the label inside the panel door lists it. My Siemens panel allows 2 neutrals per screw. Of course it is possible for local codes to override panel ratings.

  • @MarkoSpeaks

    @MarkoSpeaks

    10 ай бұрын

    So which of the 2 did this video do? What the point of doing a 200amp panel on 100amp service?

  • @doraannekey5228
    @doraannekey52282 жыл бұрын

    Wow, this man knows his work! Wish he could upgrade my electrical system to a 200 amp breaker box! Great video!

  • @petr7856
    @petr78563 жыл бұрын

    Great video. Like how he just cuts those wires to simply match to the appropriate breaker later and, voila, all back in action again!

  • @jimeneazy5999

    @jimeneazy5999

    3 жыл бұрын

    I mean if you only have 3 different amperage breakers, it’s easy to identify which one is what since the positive and neutral are together.

  • @petr7856

    @petr7856

    3 жыл бұрын

    @@jimeneazy5999 Quite so, indeed.

  • @guygrotke7476

    @guygrotke7476

    3 жыл бұрын

    @@jimeneazy5999 Did you mean hot and neutral? There is no positive on AC circuits. And them being together means nothing since all neutrals go to the neutral bar.

  • @averyearwood
    @averyearwood6 жыл бұрын

    Thanks guys!

  • @orlandob9958
    @orlandob99586 жыл бұрын

    IM JUST HERE to read the comments on every sin the electrician committed by the youtube community.

  • @frontcentermusician

    @frontcentermusician

    5 жыл бұрын

    LOL...exactly.

  • @sansar44

    @sansar44

    4 жыл бұрын

    @assassinlexx Yea but living in the area I know this company ain't cheap

  • @andrewmeinders5712

    @andrewmeinders5712

    4 жыл бұрын

    That job was done as cheap as it gets I hope they don't charge out the you know what for what he did. The sins that popped out to me he should be more specific on actually wire size to breaker size not small, medium, big. Also those really old 2 conductor cables need to be GFCI protected if going to a regular 3 prong receptacle instead of a 2 prong

  • @cantcomeupwithausern

    @cantcomeupwithausern

    4 жыл бұрын

    @@andrewmeinders5712 well doesnt everyone who would understand gauge know already? They are obviously 14, 12, 10..

  • @andrewmeinders5712

    @andrewmeinders5712

    4 жыл бұрын

    @@cantcomeupwithausern to the average homeowner that watches these videos to do it their self it is not obvious from what I've seen the last 20 years

  • @TheFSBO
    @TheFSBO9 жыл бұрын

    Just to clear up some confusion with grounding(GEC), neutral and equipment grounding conductors. First of all this is not the whole video so there may be some confusion because of that. The neutrals can not be doubled up or paired with an EGC(NEC 408.41), but the EGC's can be doubled up, depending on the listing of the panel manufacturer.(NEC110.3(B) The system grounding connection(GEC) was code compliant. NEC(250.24(A)1. He used two ground rods outside and connected it to the meter can, which is permitted by the NEC. However the local utility has requirements on this so it can vary. The bonding of the water pipe is compliant. NEC250.53D(1) The reason the neutral and EGC's can share the terminal block is because this is the main disconnect. At 2:31 you can see a black looking bar that ties the two terminal blocks together and you can also see the MBJ(copper piece with green screw) is tied to the enclosure. NEC 250.24B, 250.28A, B, C

  • @simplestatic3751

    @simplestatic3751

    4 жыл бұрын

    This will probably be the most important, yet least viewed comment of the video.

  • @Johnnybgood24

    @Johnnybgood24

    3 жыл бұрын

    One thing I never and will never understand is why people are so critical of a 5 min video clips from this channel. They don't show one lil thing and everyone is "well in MY area you aren't suppose to do THAT". Do they not know things are different from city to city? Freaking idiots.

  • @MWorsa

    @MWorsa

    3 жыл бұрын

    Two ground rods are not required on a house with city water supply, the underground water service system is considered the main ground. Only one auxiliary rod required.

  • @MWorsa

    @MWorsa

    3 жыл бұрын

    @Tbone McShittles $2300?!? I need to up my prices 🤔 How high was the point of attachment?

  • @MWorsa

    @MWorsa

    3 жыл бұрын

    @Tbone McShittles I’m truly sorry that happened to your girlfriend, did it even get inspected? Sounds like about $1300 with inspection, maybe $1500 because of the sub.

  • @ericlocke8119
    @ericlocke81195 жыл бұрын

    Good job on the white phase tape.

  • @michaelquillen2679
    @michaelquillen2679 Жыл бұрын

    Good video. I've watched both parts (1 &2). Piece of cake...I could do this myself. However, the video doesn't show any of those unexpected problems that could (and do) occur and require a solution. That's the reason we hire a pro, who has been there and done that. Thanks for the video.

  • @johndoe6032

    @johndoe6032

    4 ай бұрын

    If you watched part 1 then you know he said right up front you ALWAYS hire a professional to do this kind of work. He's only showing the steps involved, For me it was very helpful because I'm thinking of upgrading to a 200 amp circuit and wanted to know how much work is involved and get an idea of roughly how much it would cost. Now that I know it requires all new panel and wiring all the way back to the meter I know it will not be a cheap or fast job for any electrician, and I don't need to have anyone come all the way to my house to tell me that now.

  • @roetemeteor
    @roetemeteor5 жыл бұрын

    Oh God, the wire management. I'M FOAMING. HELP.

  • @chriss6356
    @chriss63567 жыл бұрын

    soul patch on fleek

  • @k3mikal
    @k3mikal2 жыл бұрын

    Jesus, I hit 00:18 and almost had a heart attack. i didnt know there was a Part 1 to this video

  • @evilskull093
    @evilskull0932 ай бұрын

    very nice work its clean it neat thanks for sharing keep up the great work

  • @jameshawkins809
    @jameshawkins8096 жыл бұрын

    Great video! Only thing I saw wrong was having all the breakers on before turning on the main.

  • @whiteknightcat

    @whiteknightcat

    6 жыл бұрын

    It didn't matter. In Part 1, it was shown the service line to the house had been cut so everything in the house was dead behind a visible open point.

  • @jefftickleschitz1265

    @jefftickleschitz1265

    3 жыл бұрын

    @@whiteknightcat You misread the comment. You should have all the breakers off before you throw the main on, less likely to have a surge happen.

  • @wizard3z868

    @wizard3z868

    3 жыл бұрын

    @@jefftickleschitz1265 agreed but up here in the ne are lights go out and on so often our electronics are used to the surges lol

  • @daveb495

    @daveb495

    2 жыл бұрын

    I always face away from the panel when first turning on the main breaker, with all branch circuits off. Just in case...

  • @whiteknightcat
    @whiteknightcat6 жыл бұрын

    I know this is just clips from a full episode, but ... right off the bat he created more work for himself by cutting all the perfectly good leads. How many seconds would it have taken with the drill to back out each of the screws and just pull the leads out? How long did it take to re-strip all those leads which are now shorter?

  • @wakejake3299

    @wakejake3299

    3 жыл бұрын

    It takes as long to put the right gauge for the right circuit

  • @ctbt1832

    @ctbt1832

    2 жыл бұрын

    I guess if he use the drill to back all of the screws out it would probably take the same time to restript the ends

  • @brandonreyes5567

    @brandonreyes5567

    Жыл бұрын

    We’ll sometimes the leads are oxidized or just deteriorating from past probably loose connections or overloading so I always just cut them hows and strip back anyways

  • @unclefreddieDied

    @unclefreddieDied

    8 ай бұрын

    I replaced a panel once.. and even without cutting them.. most of them were short.. the guy that did it before me had it so nice and neat.. looked like art work. By the time I was done, it looked like a jungle

  • @fnhwk

    @fnhwk

    Ай бұрын

    Lol who cares. Stripping that wire takes no time.

  • @Caniksigboy78
    @Caniksigboy782 жыл бұрын

    Great video. The homeowner is your cousin🦾🦾🦾🦾

  • @Shane23Armada
    @Shane23Armada3 жыл бұрын

    Well explained.

  • @jenimbusy6765
    @jenimbusy67653 жыл бұрын

    Can I please have him come to my 168 year old family farm? I still have KNOB & TUBE 🥺. And FUSES😭 I'm desperately trying to learn how to do this, but dang.... I love how he just, does it. I enjoy learning from actual, ethical, professionals ❤️

  • @TechHowden

    @TechHowden

    3 жыл бұрын

    How many circuits does your place have? just curious

  • @guygrotke7476

    @guygrotke7476

    3 жыл бұрын

    Any electrician could do it, since they would never use any of the existing stuff except maybe for pulling romex down walls. They really would just go all new like they were wiring a new house.

  • @jenimbusy6765

    @jenimbusy6765

    3 жыл бұрын

    @@TechHowden well, there are still 3 fuses, and then a mess of a panel. My father and I are tackling it, starting today. I've researched an awful lot, and found that my previous family, well, just "did their best" to put it kindly. So, we are going to sort it all out, run new Romex/Southwire, and put it into a brand new 40 space 80 circuit panel I bought. Now, my biggest problem is, running wire in this old beautiful Victorian Farmhouse ❣️. I flat out refuse to remove the horsehair plaster walls, as the insulation it provides is stellar! And it's just stunning to boot. But, I will find my way, doing research with the help of good folk like this❣️ Thank you. You never know how much you help someone with mere words and videos 😘❤️

  • @flat-earther

    @flat-earther

    Жыл бұрын

    @@jenimbusy6765 Did you succeed?

  • @RobFos
    @RobFos7 жыл бұрын

    I love this show. And love how the guy teaches. Awesome, just awesome. Thank you

  • @danmostacciuolo3204
    @danmostacciuolo32049 жыл бұрын

    Thank You.

  • @adayinthelife5496
    @adayinthelife54966 жыл бұрын

    Great comments with electricians pointing out the code violations. Also, we need AFCIs on all recepticles now.

  • @dobsonmartin

    @dobsonmartin

    2 жыл бұрын

    @Brian Uehlein In some markets, you do. The "Grandfathered in" rules typically get removed of this permission once you make a change to the service. Here, if you upgrade the service, you then need to upgrade the rest of the items you're installing to current codes. This includes putting those old circuits on AFCI or GFCI breakers as required.

  • @johndavies2949

    @johndavies2949

    3 ай бұрын

    Yep. Unless your AHJ exempts it.. Some counties in my area have. Too many complaints of nuisance trips.

  • @Clint_the_Audio-Photo_Guy
    @Clint_the_Audio-Photo_Guy6 жыл бұрын

    My house has random outlets and appliances tied to the same breakers. I want to separate them on to their own breakers. Looks like fun.

  • @hadesoao2092

    @hadesoao2092

    6 жыл бұрын

    Call a licensed Journeyman Electrician, don't do it yourself.

  • @hadesoao2092

    @hadesoao2092

    6 жыл бұрын

    Where I live, adding circuits, doing anything in a panel, or upgrading services must be done by a certified electrician.

  • @araibirshad8294

    @araibirshad8294

    6 жыл бұрын

    hehe where i live there are no codes and restrictions and i do shit like this most of the time. it also helps that ive been diy'ing electrical wiring since I was like 10 yrs old. Its mind blowing how much protocol and proper technique you have to follow while doing stuff according to code or with safety regulations. though i guess doing this code regulated stuff would be fun. no one likes shoddy unsafe third world electrical work.

  • @Elfnetdesigns

    @Elfnetdesigns

    6 жыл бұрын

    "hehe where i live there are no codes and restrictions" - Where? in India where they give fuckall about health and safety?

  • @guygrotke7476

    @guygrotke7476

    3 жыл бұрын

    @@araibirshad8294 I live in California and electrical work requires a licensed electrician OR the home owner can do it. You just can't sell your electrician services without a license. Then it has to be inspected, and if you screwed up the inspector will usually tell what to do to fix it. Unless he sees you are an idiot, and makes you hire an electrician for your own safety. I upgraded my breaker box and installed solar with a grid-tie inverter myself. The inspector complimented my work.

  • @matthewguralsky
    @matthewguralsky3 жыл бұрын

    What year of apprenticeship do you get your soul patch?

  • @sylviaisgod6947

    @sylviaisgod6947

    3 жыл бұрын

    It's not based on years, it's how many times you get shocked by 440v and survive.

  • @ixcancel
    @ixcancel6 жыл бұрын

    Nice video.

  • @abrahamvaro1637
    @abrahamvaro16375 жыл бұрын

    very good video ,thanks.

  • @kingofl337
    @kingofl3374 жыл бұрын

    A lot of places have trouble getting the power company to come out in a timely manner. Also, the new service needs to be inspected before reconnection. Electricians will install everything and back feed the new panel with the old one until the inspection. Then call the power company for the move.

  • @brendasnow6024

    @brendasnow6024

    4 жыл бұрын

    Exactly! In Maryland, you make temporary connections to the existing SEU cable on the load side of the meter, and let the power company come out after you pass your inspection.

  • @not1but2and37

    @not1but2and37

    3 жыл бұрын

    Mine took over eight months for the whole process.

  • @Phormify
    @Phormify9 жыл бұрын

    Great - another video where the KZread commenters tell us how much smarter they are than the licensed electrician and pointing out how many mistakes they assume he made due because they assume their local codes must apply everywhere. Get a grip. They aren't about to show every detail as the process would take several hours. It isn't meant to be a tutorial... it is just to give the typical homeowner a basic understanding of how involved the process is so they don't balk at the $1200 cost to upgrade a small residential panel. I'd trust Scott to work on my home, and his presentation and customer service skills are top notch. Some of you self-proclaimed "experts" could learn a thing or two here.

  • @cooldog60

    @cooldog60

    9 жыл бұрын

    Phormify $1200 wow that is crazy. I had a fuse box replaced with circuit breakers. I bought the parts about $125 the electrician put it in for $65. Since the house is a rental house I have to have it inspected every time I get a new tenant. Which is about every year. Never had a problem with it passing inspection.

  • @Phormify

    @Phormify

    9 жыл бұрын

    I'm well aware of the NEC, but I'll disagree with you that he is violating code or doing anything illegal. Thanks for proving my point about the comments though. You may return to your regularly scheduled trolling of KZread comments now... I'm sure you have a long day ahead of you.

  • @Phormify

    @Phormify

    9 жыл бұрын

    If you are going to call someone stupid it helps to use the proper version of "you're". Ironic isn't it? Keep trolling Phil... You may not be much of an electrician but at least you have this KZread thing working out for you.

  • @erictold

    @erictold

    7 жыл бұрын

    I agree with you. Scott did it correctly 100%. Trolls here are all wrong.

  • @mattlowery8267

    @mattlowery8267

    7 жыл бұрын

    Phormify well I'm not a troll I bought an older home last year and the box needed to be upgraded I was scared it was gonna cost out the ass ....i bought the box at Lowe's and the electrician came ( a real place not bobs repair service) and he charged me 75 to put it in

  • @buiminhtuan12
    @buiminhtuan122 жыл бұрын

    It's very helpful

  • @tooold8318
    @tooold83186 жыл бұрын

    Great job

  • @MS-in3sl
    @MS-in3sl4 жыл бұрын

    I want to see the part where he’s figuring out the bill.

  • @ekop1778

    @ekop1778

    4 жыл бұрын

    .14 WET PAPER OR A GOOD TIME INSIDE THE DOOR

  • @sansar44

    @sansar44

    4 жыл бұрын

    Had these guys give me an estimate to rewire my kitchen remodel and almost crapped my pants

  • @00.0O

    @00.0O

    4 жыл бұрын

    Anyone have an estimate on the cost of this total job I need this exact same thing done asap

  • @sansar44

    @sansar44

    4 жыл бұрын

    depends on where you live

  • @cantcomeupwithausern

    @cantcomeupwithausern

    4 жыл бұрын

    @@00.0O at least 2000 to have done, only a few hundred if u do it yourself though bc the only costs are the outside weatherhead and box, wiring and breaker box inside - and it should be easy enough to get a new breaker box that can reuse your existing breakers - assuming your house uses breakers..

  • @ThePudgie123
    @ThePudgie1232 жыл бұрын

    Would have been helpful to hear what gauges the wires needed to be for the upgrade.

  • @danf769

    @danf769

    2 жыл бұрын

    14awg for 15 amp breaker, 12 for 20amp, 10 for 30, 8 for 40…

  • @addminusDIY

    @addminusDIY

    Жыл бұрын

    Then #6 for 50amp breaker😊

  • @jaycahow4667

    @jaycahow4667

    Жыл бұрын

    @@addminusDIY #6 for 60amp breaker as well.............

  • @brianherren9222

    @brianherren9222

    Жыл бұрын

    Pretty sure he means the service conductors 😂

  • @DennisMilesEVprofessor
    @DennisMilesEVprofessor9 жыл бұрын

    Randy, exactly right! The grounds on the two wire circuits? They were on the neutral and ground busses in fairly equal number so I'm thinking they all had grounds. I didn't see any GFCI breakers however...Nor did I see a building electrical permit and hear of the final inspection and certificate of occupancy we have to have before the electric utility will hang the meter ... Also, an important part of a service upgrade to change to larger feeders from the street, to the meter base and then into the CB Panel, his was installed before they started recording the video or by another contractor...And that B.S. of having the homeowner 'have the honor' is pure Hollywood as you said....

  • @sheet-son

    @sheet-son

    9 жыл бұрын

    Thanks :) Im not a know-it-all but I do know when its done wrong.

  • @sam111880
    @sam1118808 жыл бұрын

    nice very professional looks really good do you always for the most part connect large size wires by bolting them down i don't think you really want to uses large wire nuts based on it being to ridged but you could probably uses large spade connectors or push closed mechanisms

  • @kevinthorson4662
    @kevinthorson46623 жыл бұрын

    First the main wire has to be upsized to 200 amp, work has to be inspected and in most states done by a licensed electrician.

  • @gilbertdare5921
    @gilbertdare59213 жыл бұрын

    The "gel" should have been used on the meter socket connections.

  • @shawnbroswick1272

    @shawnbroswick1272

    3 жыл бұрын

    Copper doesn’t need the gel. Just aluminum oxidizes

  • @Spectre302011

    @Spectre302011

    3 жыл бұрын

    @@shawnbroswick1272 copper does oxidize. Oxidization happens when you use two dissimilar metals. If the wire is copper and the lug is not you should still use the gel.

  • @shawnbroswick1272

    @shawnbroswick1272

    2 жыл бұрын

    @@Spectre302011 yes. When you mix the 2 then you need it. Thanks

  • @supremelawfirm
    @supremelawfirm6 жыл бұрын

    Scott, you make this look SO EZ! You've done this a few times already, YES!! :)

  • @T-Jones17
    @T-Jones172 ай бұрын

    This Old House on a budget using beer can wire for your main run…how nice of them

  • @guygrotke7476
    @guygrotke74763 жыл бұрын

    Most homes also include a 50 amp 240 VAC circuit for an electric stove, even if you are using gas. So there are usually four sizes of wire, not three. It also would have been nice to show how to use an inch-pound torque wrench to properly tighten those breaker screws, and to use separate ground and neutral buss bars with a bonding screw or pigtail.

  • @chipdayton1625

    @chipdayton1625

    2 жыл бұрын

    No need to separate the grounds and neutrals in the main panel, only in a subpanel.

  • @micjam1986
    @micjam19867 жыл бұрын

    two questions.. first. is the wire coming off the telephone pole always big enough to handle 200 amp service? second... do electrician use different size wires coming into the house from the meter? so if you jump up to 200 amp , a home owner might have to change to a bigger wire? thx!!

  • @alexjohnson8840

    @alexjohnson8840

    7 жыл бұрын

    to answer the first question, it is not a problem to upgrade a service. the power company wires that feed your home are capable of handling a 200a service. however the wiring from your meter needs to be adjusted to handle a service upgrade. a 100a service only requires #2 awg aluminum. however when you upgrade to 200a you will need to step your wire up to 4/0 aluminum.

  • @micjam1986

    @micjam1986

    7 жыл бұрын

    Thanks Alex, I appreciate your input!

  • @ianbelletti6241

    @ianbelletti6241

    7 жыл бұрын

    Alex Johnson's response is the typical condition. There is no guarantee that your local power company has installed wire large enough for a 200a service from their transformer. The electric company has their own set of codes that are different from the NEC and they often engineer their wire to much closer tolerances than what the NEC requires of electricians wiring buildings. The only way to be absolutely sure would be to contact your electric company to verify the capacity of their existing service conductors to your building prior to doing a service upgrade.

  • @luisLopez-uz3mv

    @luisLopez-uz3mv

    7 жыл бұрын

    mic jam yes if you are doing an upgrade yes. you need new cable coming from outside .

  • @Engineer9736

    @Engineer9736

    6 жыл бұрын

    If you have to ask this question then don't mess with your incoming power line at all. You could easily have found out the rating of that cable yourself. It's much more reliable to find it out the truth yourself than asking such a thing on KZread. This all concludes that you should just call professionals to get things done on your electric system.

  • @XroorX
    @XroorX Жыл бұрын

    I remove each breaker wire versus just snipping the wire like this electrician. Better to have too much wire than not enough

  • @Americanman2000
    @Americanman20002 жыл бұрын

    This guy is good!

  • @danielg803
    @danielg8033 жыл бұрын

    This electrical installation looks like its from the 50’s 😄

  • @jimeneazy5999

    @jimeneazy5999

    3 жыл бұрын

    Why’s that?

  • @jakesully5402

    @jakesully5402

    2 жыл бұрын

    @@jimeneazy5999 I saw some ungrounded circuits.

  • @lorenvankrieken220
    @lorenvankrieken2203 жыл бұрын

    How much would this work and materials cost from licensed electrician?

  • @gregmartin1757

    @gregmartin1757

    2 жыл бұрын

    Depends on your location but roughly between $2500.00 - $3000.00 Could be more or less depending on how many existing circuits, if you need a 30 or a 40 circuit panel Underground or overhead service etc . Lots of other factors.

  • @dwoodog
    @dwoodog3 жыл бұрын

    After changing out a main panel front those crappy stab-lok breakers to Square D, it wasn't too hard. Very satisfying just pulling all the wires (AKA: the mess) out and starting over from what the last guy did. Only thing I would have done different here is not just go on small medium and larger wires to know whats what, but taken the time to label all the wires first before I took everything apart.

  • @alexkaspo5246
    @alexkaspo52463 жыл бұрын

    I absolutely gaurentee that most electricians don’t do all this work which is sad cause when it’s done right it acts right! No weird issues down the line

  • @santaclaus179
    @santaclaus1793 жыл бұрын

    this electrician is destroying the whole main cabinet only in order to see where the cables are going to , incredible

  • @linehandibew6205
    @linehandibew62053 жыл бұрын

    “Mok” the wires????

  • @mmarczuk1976
    @mmarczuk19764 жыл бұрын

    Agreed. Well done instructiional video now i can piss around with my panel ⚡⚡⚡

  • @charlieblue8946
    @charlieblue89462 жыл бұрын

    Super nice

  • @MatthewWeiler1984
    @MatthewWeiler19846 жыл бұрын

    I never understand when people don't trace all of their breakers and create an easy to follow list. But I'm a little OCD so that must be why :p

  • @MatthewWeiler1984

    @MatthewWeiler1984

    6 жыл бұрын

    Glad I'm not alone on that :)

  • @anthonyc1883

    @anthonyc1883

    6 жыл бұрын

    Junior Mudd I agree wholeheartedly, JM. I'm just a homeowner but I've gotta admit that properly organized wiring is a thing of beauty. I have a 1953 house in which we had a panel upgrade done by an electrician a couple years ago, with several new circuits run to modernize the kitchen. The thing looks great inside!

  • @buggsy5

    @buggsy5

    6 жыл бұрын

    Panels often start out properly labeled then, over the years as circuits are changed or added to accommodate additional electrical needs, the labels become inaccurate. When I bought my house in the 85's (built mid-60's) about half the circuits were mislabeled.

  • @davidmiller9903

    @davidmiller9903

    4 жыл бұрын

    @Junior Mudd typically the existing panel legend is either not there or so far off. I find it is way easier and faster to do one after ward with a circuit tracer. Also noticed the expansion above the meter, not required, the conduit will move. The riser does not go there the roof so it is allowed to be PVC, but not going thru the roof depends on the overhead drop being the proper height above yard sidewalk etc. The dressing of a panel is thing of pride for a good electrician.

  • @DavidBerquist334
    @DavidBerquist3348 жыл бұрын

    i would keep a square d qo panel and breakers for a small house

  • @gragor11

    @gragor11

    8 жыл бұрын

    +David Berquist lots of good breakers junked there as well. I like Sq D's enclosed bus bars. Way safer than this brand.

  • @danielmarone5757

    @danielmarone5757

    7 жыл бұрын

    I do that whenever I rip out a service. I must have $2,000 worth of circuit breakers that I took out of people's houses LOL

  • @CompGuy66

    @CompGuy66

    7 жыл бұрын

    I agree Square D all the way. The QO series panels are one of my favorites. At home I have a 60 slot 200 amp Square D panel as my main panel and for sub panels I have an 8 slot square D and some old 60 amp fuse box. I also have a 100 amp federal pioneer panel in the garage but I just don't like it as much as the Square D QO. Hopefully that panel in the video did not go to waste

  • @gragor11

    @gragor11

    7 жыл бұрын

    Unfortunately many of those good branch cct breakers will go to waste as the rules now require Arc Fault breakers on most plug ccts.. Way to go regulators - turn an $8.50 cent breaker solution into an $85 expense for each cct. I'm surprised that there is anybody left alive in other countries that use electricity considering their lack of self serving, profit centered, safety mechanism regulation.

  • @CompGuy66

    @CompGuy66

    7 жыл бұрын

    Yeah I completely agree. AFCI on every circuit is just overkill. I think It used to only be required for bedrooms until recently. I have NEVER had AFCI breakers in any house or apartment I have lived in. In fact most of the apartments I lived in until I moved into a condo built in 1994 only had fuse boxes. Hell as far as I know no body in all of those buildings ever got killed from electrocution. I think electrical code has become a little rediculous in the past few years. Don't even get me started on tamper resistant outlets. I absolutely hate them. In fact when we bought our house the newly added bathroom had 2 of those nasty TR duplex receptacles in it and they drove everybody in the house mad. The day I ripped them out and threw them in my junk pile just felt so good. Too bad many big stores such as home depot only carry the TR crap now. I am just keeping my eyes peeled for used and new non TR receptacles. Many of the decomishined ones I find are either so worn out they don't hold plugs in or the plastic is all cracked and covered in paint. Hopefully I can get enough to last me a lifetime. Btw I am only 17 years old.

  • @Esnara2085
    @Esnara20853 жыл бұрын

    Resi electricians love putting the loops in the feeder.

  • @TheJuanPreciado
    @TheJuanPreciado9 жыл бұрын

    This videos are grate.

  • @billw1044
    @billw10445 жыл бұрын

    Why would you "mock" the wires before you cut them? Surely it would give them an inferiority complex and cause a short circuit.

  • @zmonkeymadness
    @zmonkeymadness7 жыл бұрын

    not allowed by nec code book to land two wires on yhe same terminal

  • @GhostHostMemories

    @GhostHostMemories

    7 жыл бұрын

    What section?

  • @zmonkeymadness

    @zmonkeymadness

    7 жыл бұрын

    Shades921 110-3b mentions about it can only be if it's specifically labeled. The best termination tho would to splice the wires together and then screw one wire down. tighten a wire to much that it puts a cut in it creates resistance and a hotspot is potential. having two wires doesn't allow the screw to be tighten properly as well... and potential for a faulty circuit.

  • @GhostHostMemories

    @GhostHostMemories

    7 жыл бұрын

    zmonkeymadness well, it's not really "illegal" just only allowed when it says it's allowed. i.e. the terminal has to be rated for 2 wires. Just about every terminal i use (i work in a control panel shop) is rated for 2 terminals.

  • @SkilledEddie

    @SkilledEddie

    7 жыл бұрын

    Wrong if it's listed you can use two wires on a breaker or bus bar

  • @gragor11

    @gragor11

    7 жыл бұрын

    is that a square D standard to be rated for 2 conductors on the terminal lug?

  • @xsniperplx
    @xsniperplx5 жыл бұрын

    good video , i think you should have all the breaker off when turning on the main and turn them one one by one .

  • @daoudisofiene4588
    @daoudisofiene45882 жыл бұрын

    Very well work, I appreciate this man that he give us a lot of ideas about the importantly upgrade

  • @cattigereyes1
    @cattigereyes13 жыл бұрын

    I thought tying the ground wire to the water system was a no no?

  • @Willard_guy
    @Willard_guy7 жыл бұрын

    OK that is not how you turn on a main breaker on at all you should never look at a breaker when turning it on. You look away take a deep breath and use your non dominant hand to turn it on. This is so if there is an arc flash from a short you don't breath in the molten metal from the arc flash.

  • @buggsy5

    @buggsy5

    6 жыл бұрын

    However, proper safety procedure is to make sure all circuit breakers are off, then turn on the Main Breaker. After that, circuits are turned on one at a time.

  • @PhillyMotoXTS

    @PhillyMotoXTS

    5 жыл бұрын

    I guarantee they did a test run and made sure everything worked fine before they filmed the home owner "turning it on" for the first time, probably before they even installed the cover.

  • @eksine

    @eksine

    5 жыл бұрын

    Use a broom stick

  • @warrenmichael918

    @warrenmichael918

    5 жыл бұрын

    wrong and wrong ,the correct way is to tell the ol lady to go throw it on !! LOL

  • @FirstNameLastName-fu8ml
    @FirstNameLastName-fu8ml3 жыл бұрын

    So did u change all the 14gauge wires or the 12gauges wires going into any of the outlet? I asked that because some of them will need a bigger wire to support heavier machine. Or did u change it for some other reason?

  • @congreet_universa
    @congreet_universa2 жыл бұрын

    Question. When main service breaker was turned on, were other breakers on or off? Some articles claim that home breakers should be off, and should be turned on one by one once service main breaker is on position.

  • @alext9067
    @alext90676 жыл бұрын

    Saw a water main become totally perforated and turn a woman's front yard into a mud pie because of the ground connection to the main and the fact that the neutral in the trans moved and was therefore not neutral anymore, but feeding a current directly to ground. After fixing the main, I called the electric company and the next day they were there w/ a truck and changed out the trans. Don't connect earth ground to a water pipe or anything but a sacrificial ground rod buried in the earth. Still an excellent video. Thank you.

  • @Scorpiomaj27889

    @Scorpiomaj27889

    6 жыл бұрын

    alex tworkowski Using the water line is illegal here, probably slow be illegal everywhere - not hard to stick a rod in the ground.

  • @Elfnetdesigns

    @Elfnetdesigns

    6 жыл бұрын

    In the UK they are allowed to ground to gas FFS.. GAS!.. I never ground to plumbing, I do the extra labor and drive a propper ground rod..

  • @JonPalmerMusic

    @JonPalmerMusic

    6 жыл бұрын

    in the Uk thats called bonding and its there to stop electric shock. Have a read on it.

  • @Elfnetdesigns

    @Elfnetdesigns

    6 жыл бұрын

    Grounding to gas is EXTREMELY dangerous, You people are morons period. I guess it's a game of natural selection over there though..

  • @johnnyyankee8604

    @johnnyyankee8604

    6 жыл бұрын

    Apparently it's legal wherever they filmed this. But as a home owner I would feel more secure if the main ground was connected to a rod outside into the ground.

  • @FoodOnCrack
    @FoodOnCrack9 жыл бұрын

    Wait the ground and neutral go under the same strip? That causes the GFCI's to trip doesn't it? OR is it an TN-C system? I'm confused as an European electrician.. Don't you have GFCI's required on all your groups? And do all of your groups (circuit breakers) have only thermal protection and not magnetic protection? (overheating on the thermal and short circuiting on the magnetic) Someone explain to me...

  • @ristomladich246

    @ristomladich246

    9 жыл бұрын

    FoodOnCrack no the 2014 nec states that GFCI (210.8) must be in place for Bathrooms, garages or any located floor below grade level not intended for habitable rooms and limited to storage areas, work areas, and ares or similar use, outdoors, crawl space at or below grade level, unfinished basements, kitchens where receptacles are installed to serve the counter top surface, sinks where receptacles are installed within 1.8m 6ft of the outside edge of the sink, boathouses, bathtubs shower stalls same thing like the sink.

  • @centerstagela

    @centerstagela

    8 жыл бұрын

    +Risto Mladich Still didn't really answer his main question, you just simply stated where GFCI's are required by code, in the US...

  • @andysmith8789

    @andysmith8789

    8 жыл бұрын

    +FoodOnCrack the N and G bars are actually separated and only touch at one spot in the middle, kinda hard to see

  • @thereynolds2725

    @thereynolds2725

    8 жыл бұрын

    The utility provides a 3-wire service which consists of two "hot" wires and a neutral. Between the two hots there is 240 volts. between either hot and neutral is 120 volts. The ground begins at the first disconnect and is the point where the ground wires in the circuits connect to the neutral. Nowhere else is the neutral allowed to be grounded within the building. Since GFCIs are "downstream" of this connection, they do not trip.

  • @kookiedabear

    @kookiedabear

    8 жыл бұрын

    +FoodOnCrack I too would like to know if inspection passed this improper installation: neutral and ground tied via common service bar (the black band in the middle) which makes him think it's ok to mix neutrals and ground on both bars...AND, worst of all, he has the box grounded to this neutral/ground bar, which should give someone a mild tingle if the panel powder coating wears to bare metal.

  • @dynoesaur
    @dynoesaur4 жыл бұрын

    What a story!!!

  • @chrislafayette8730
    @chrislafayette87303 ай бұрын

    Question..Does it matter to have a different brand meter box when your hooking it to the new main breaker box??

  • @YouTubehndl
    @YouTubehndl3 жыл бұрын

    All you need to do is spend 1 whole day turning off breakers and chasing circuits around your house. No problem!

  • @tictac-nscale
    @tictac-nscale3 жыл бұрын

    All I heard is this gets connected to the neutral zone lol.

  • @infotechyeti
    @infotechyeti4 ай бұрын

    when is the right time to do this? all seems okay for now and no issues with power going out but curious when its best to do this?

  • @Bear_83
    @Bear_832 жыл бұрын

    Wondering how much this cost to do a upgraded to your house?

Келесі