How to resolve an i-smile R410a aircon not cooling | Daikin inverter

Brand : Daikin ismile
model : MKS80QVMG/FTKS(25/35)QVM
Symptom : not cooling.
(off coil temperature around 20 to 23°c cooling mode)
error : no error and no blinking.
(indoor work as per normal)
Diagnosis : Indoor Thermistor reading abnormal.
(around 22 to 30 K ohm, ambient temperature around 30°c)
action : replace indoor thermistor.
please subscribe my KZread channel
/ bonmj
#bonmj #daikin #Daikin #airconditioning

Пікірлер: 83

  • @kle830
    @kle8302 жыл бұрын

    谢谢你,无私的教导和分享。

  • @BonMj

    @BonMj

    2 жыл бұрын

    谢谢

  • @ngtaiwei1220
    @ngtaiwei12202 жыл бұрын

    Learn a lot, thank you.

  • @BonMj

    @BonMj

    2 жыл бұрын

    Welcome

  • @Didik-cq8wy
    @Didik-cq8wy Жыл бұрын

    Trimaksih tuan

  • @BonMj

    @BonMj

    Жыл бұрын

    👍

  • @karimchiu7527
    @karimchiu7527 Жыл бұрын

    thanks sir Bon

  • @BonMj

    @BonMj

    Жыл бұрын

    👍

  • @zhalfemarcotoco1146
    @zhalfemarcotoco11462 жыл бұрын

    I like your manifold guage nice video yow

  • @BonMj

    @BonMj

    2 жыл бұрын

    Thanks

  • @charltech1421
    @charltech14212 жыл бұрын

    Very good trouble shooting sir mj.

  • @BonMj

    @BonMj

    2 жыл бұрын

    Thanks bro

  • @Zamani_Hidayah
    @Zamani_Hidayah Жыл бұрын

    Great sharing sir 👍

  • @BonMj

    @BonMj

    Жыл бұрын

    Thanks

  • @alanwong2761
    @alanwong27612 жыл бұрын

    Bon是一个有专业水准的技师👍👍👍

  • @BonMj

    @BonMj

    2 жыл бұрын

    您过奖了,谢谢。

  • @alanwong2761

    @alanwong2761

    2 жыл бұрын

    Bon what's the fault Daikin RZR125MVMG outdoor h3p led on?

  • @BonMj

    @BonMj

    2 жыл бұрын

    @@alanwong2761 error code only can check at indoor unit using remote control .

  • @alanwong2761

    @alanwong2761

    2 жыл бұрын

    @@BonMj no error code at indoor and feel a little bit cold only

  • @BonMj

    @BonMj

    2 жыл бұрын

    @@alanwong2761 oic..the gas pressure ok?

  • @JuanTodoli
    @JuanTodoli2 жыл бұрын

    Good one 👍

  • @BonMj

    @BonMj

    2 жыл бұрын

    Thanks

  • @koksengcheong8862
    @koksengcheong88622 жыл бұрын

    老角 真的👍👍👍

  • @BonMj

    @BonMj

    2 жыл бұрын

    谢谢

  • @alonsoacosta8545
    @alonsoacosta85452 жыл бұрын

    Muy buena amigo

  • @BonMj

    @BonMj

    2 жыл бұрын

    Thanks bro

  • @mac0pod
    @mac0pod2 жыл бұрын

    Hi. What is the value of the thermistor in the device: FCAHG125F? Thank you for your help!

  • @aus_aircon_ref_mech6671
    @aus_aircon_ref_mech66712 жыл бұрын

    Very good video. Just a quick question. If we have the same problem. That compressor is not able to ramp up. Could the problem be with the inverter PCB? How to diagnose that on a wallhung split though?

  • @BonMj

    @BonMj

    2 жыл бұрын

    For this model,suggest you check indoor thermistor first.already happen few case. When we do checking,the symptom similar like a inverter pcb or inverter compressor got problem ,actually is indoor thermistor got problem.

  • @kruk-tv
    @kruk-tv10 ай бұрын

    sir, my daikin ftkg28qv1l7 indoor thermistor reading 10k ohm is that a normal reading or abnormal and require replacement?

  • @kelvinlim0409
    @kelvinlim04092 жыл бұрын

    Thank you Bon MJ for sharing this scenario. May i check where can i buy Daikin thermistor to troubleshoot and replace?

  • @BonMj

    @BonMj

    2 жыл бұрын

    Only Daikin.

  • @kelvinlim0409

    @kelvinlim0409

    2 жыл бұрын

    @@BonMj i buy a new thermistor, it is 8k ohm. After replacing, the aircon can work and become more cooler. Will it cause any side effects because you recommend thermistor at 17k ohm?

  • @BonMj

    @BonMj

    2 жыл бұрын

    @@kelvinlim0409 suggests you replace the original parts.(16k - around 30°c)

  • @thefoodrider
    @thefoodrider2 жыл бұрын

    Hi. I have a 3 aircon unit at home. Master bedroom has it’s own pipeline and the other 2 bedrooms share the same pipeline to the main condenser. Aircon is a Fujitsu. Over 10 years. The two units sharing the same pipeline takes minimum 30minutes to blow cold air. It was working fine all along. The main master bedroom unit doesn’t have this problem as it runs on another pipeline. Complete and thorough chemical wash for all 3 units done 6 months ago. I believe gas was topped up too. Any idea what could be the problem? TIA!

  • @BonMj

    @BonMj

    2 жыл бұрын

    Your AC should be conventional aircon system 3 .(2 compressor type) Master FCU is under individual compressor and another 2room is sharing one compressor. Suggest u to check off coil temperature and gas pressure. If off coil temperature higher than 16°c May insufficient gas.

  • @Zamani_Hidayah
    @Zamani_Hidayah Жыл бұрын

    Sir, for mitsubishi mr.slim invertor thermistor resistant checking reading is also same as this daikin?

  • @BonMj

    @BonMj

    Жыл бұрын

    No

  • @MrRandyj72
    @MrRandyj722 жыл бұрын

    How old was that unit? I don't see many failures of thermistors here on our Daikin Equipment but we afe still new to Ductless products compared to your region.

  • @BonMj

    @BonMj

    2 жыл бұрын

    4

  • @realcartoongirl

    @realcartoongirl

    2 жыл бұрын

    4 what days? months? years? very helpful

  • @corals8192
    @corals81922 жыл бұрын

    Hi, i hv Diakin system 3 model 4MKS80ESG supplies to 2 rooms and a living hall. If i turn on either one of the rooms the air will not be cool. I hv to turn on both rooms at the same time then they will be cool. The living hall fan unit is working well and has cool air even only it is turned on itself. The technicians hv tried to replace thermistor for one of the rooms and also for outdoor unit thermistor, check gas pressure but not able to solve the problems. Adviced me to change the whole outdoor condensor unit but cannot find because no more in production. Could it be valves not working? Seeking your advice please.

  • @BonMj

    @BonMj

    2 жыл бұрын

    Maybe, the room 1 and room 2 signal wires are wrongly connected. You can test it out yourself, On the aircon in room 1, go to room 2 and touch the room 2 evaporator coil, if room 2 evaporator coil is cold and room 1 is not, most likely is due to the signal wire wrongly connected.

  • @corals8192

    @corals8192

    2 жыл бұрын

    @@BonMj Will check. Thank you for your reply.

  • @BonMj

    @BonMj

    2 жыл бұрын

    @@corals8192 morning,how is the result.

  • @corals8192

    @corals8192

    2 жыл бұрын

    Hi, mine is ducted unit, evaporated coil above the ceiling, a bit difficult to check. After turning on 1st room for an hour which is not cool , i touched the 2nd room casing but seems not cool. I turned off 1st room, immediately turned on 2nd room in fan mode, trying to feel whether air is cool but not. This may not be ideal way to check. Anyway when only one room is on, the temperature seems to lower by 1 or 2 degree for about 30mins then it gets warm again. Switch on the room and both can get cool air till i off it.

  • @BonMj

    @BonMj

    2 жыл бұрын

    @@corals8192 if ducted unit,you can on room 1 and roon 2 set at fan mode. Or may be if the LEV or pcb problem

  • @karlmapanao5137
    @karlmapanao51372 жыл бұрын

    Sir i want to order coil thermistor but i dont know what is my coil resistance for daikin ftkc35qvm. Is it 5k 10k 15k 20k? Thanks in advance.

  • @BonMj

    @BonMj

    2 жыл бұрын

    15k

  • @janshaw5472
    @janshaw54722 жыл бұрын

    我前几天check一个ftks 50一直不可以full coil ...out doir current 最多走4个!

  • @BonMj

    @BonMj

    2 жыл бұрын

    有可能是这个问题

  • @goparismail9727
    @goparismail97272 жыл бұрын

    teknisi indonesian selalu hadir sukses selalu bos ku

  • @BonMj

    @BonMj

    2 жыл бұрын

    Terima kasih master.

  • @BonMj

    @BonMj

    2 жыл бұрын

    Kalau master tak faham,boleh tulis bahasa indonisia dalam comment.

  • @goparismail9727

    @goparismail9727

    2 жыл бұрын

    bisa bahasa idonesia juga master bon MJ he he he

  • @goparismail9727

    @goparismail9727

    2 жыл бұрын

    sy penggemar cenel Bon Mj konten bermanfaat berkualitas tinggi prefesional buat semua orang yg baru belajar di ac seperti sy

  • @BonMj

    @BonMj

    2 жыл бұрын

    @@goparismail9727 terima kasih master sokong KZread Channel saya.

  • @ngkeekeong9639
    @ngkeekeong9639 Жыл бұрын

    Mr Bon.. my ismile indoor Aircon has no error code, suspect one of the outdoor compressor thermistor faulty. Please do contact me if you happen to read this. Thanks

  • @BonMj

    @BonMj

    Жыл бұрын

    May be you are right

  • @janshaw5472
    @janshaw54722 жыл бұрын

    Mr bon 今天我做一台service dakin ctks18 k 我拆了水盘一下然后装回去 内机pcb 一直滴滴响???头大......是要赔indoor pcb

  • @BonMj

    @BonMj

    2 жыл бұрын

    Aircon 可以走车吗

  • @BonMj

    @BonMj

    2 жыл бұрын

    电板下面就是fan motor后面有一个盖,有没有该盖好。

  • @janshaw5472

    @janshaw5472

    2 жыл бұрын

    @@BonMj 很奇怪,systerm 3 我拆过的那台一直滴滴响 erro code uA 其他两台没有滴滴声音,但是blinking u4 我最后从CU把滴滴响的FCU 电线断开,其他两台才可以正常走 !

  • @BonMj

    @BonMj

    2 жыл бұрын

    @@janshaw5472 很怪!

  • @janshaw5472

    @janshaw5472

    2 жыл бұрын

    @@BonMj 我今天去dakin 问一下,如果是pcb还要买了赔人家

  • @Kyleas12345
    @Kyleas123452 жыл бұрын

    Why are some of the words in the interview, in English?

  • @BonMj

    @BonMj

    2 жыл бұрын

    Sorry bro ...that is how we speed usually.

  • @nurazhanshaffeeie6734
    @nurazhanshaffeeie6734 Жыл бұрын

    Hi Mr Bon, how do i contact you?

  • @BonMj

    @BonMj

    Жыл бұрын

    bonmj81@gmail.com

  • @karaors8970
    @karaors89702 жыл бұрын

    🇹🇷✋🍻🤳🛠️👍

  • @BonMj

    @BonMj

    2 жыл бұрын

    Thanks bro

  • @hasanmdkamal1010
    @hasanmdkamal10102 жыл бұрын

    ur voice not clear bri

  • @BonMj

    @BonMj

    2 жыл бұрын

    Thanks.

  • @realcartoongirl
    @realcartoongirl2 жыл бұрын

    i hate this brand