How to Replace a Reversing Valve on a Heat Pump. EP75

Тәжірибелік нұсқаулар және стиль

So we're on this unit again. The previous tech diagnosed a bad reversing valve which was causing the unit to not heat properly. I got sent out to change out the reversing valve. This is my first reversing valve replacement, I've been able to avoid it until now. Here's the process on replacing the reversing valve on my favorite heat pump. Enjoy!!!
Follow me on Facebook and Instagram
nighthawkhvac
nighthawk_hvac
Intro and Outro Music
"Alive" by CHOIX
Free Realistic Snow Overlay by Kosmos Motion Graphics
• [Free Download] Fallin...
#nighthawkhvac #hvac, #hvaclife, #airconditioning #maintenance, #heating, #cooling #refrigerator, #refrigeration #refrigerationcycle #airflow #refrigerant #techlife #installation, #hvachacks, #tools, #furnace, #tech, #electric, #residential, #commercial, #heat, #comfort, #ac, #hvacservice, #hvactools, #repair#toolreviews #fieldpiece #aircon #zoning #honeywell #zonedamper#packageunit #howto #VAV #exhaustfan #Ignitor #trane #TXV #expansionvalve #Intellipak #Trane #Self-contained #Boiler #Coolingtower #noisyinducer #noisyidm #failedIDM #condenserinattic #failedinducerdraftmotor #howtocleancoils #condensercoilcleaning #sparkignitor #nospark #minisplit #mitsubishi #ductless #powerboard #powerboardreplacement #short #outdoortxv #watersourceheatpump #highpressuretrip#bloweralwayrunning #reversingvalve

Пікірлер: 40

  • @chrissipple1018
    @chrissipple1018 Жыл бұрын

    Use the Carrier method of reversing valve replacement. Cut it out and use couplings to install.

  • @chrisbruzon811

    @chrisbruzon811

    2 ай бұрын

    How does that work?

  • @nothankyou5524
    @nothankyou55242 жыл бұрын

    Left HVAC for a new trade 15 yrs ago.Never saw a heat pump til I went south. My first RV is soon. You made it look too easy. I'll be watching your videos, even if just for fun. Great stuff.

  • @juliorodriguez8863
    @juliorodriguez88632 жыл бұрын

    Thanks for sharing an excellent wor!!

  • @joeziti7787
    @joeziti7787 Жыл бұрын

    A rose bud would of made sweating the reversing valve in much easier. Highly recommend

  • @sunshinel5975
    @sunshinel5975 Жыл бұрын

    Good video. Thank you for all of the info.

  • @jericosha2842
    @jericosha28422 жыл бұрын

    Thanks for sharing man

  • @Bretware904
    @Bretware904 Жыл бұрын

    We have done a lot of reversing valves mostly large commercial though 1 1/8, 1 3/8, that was extremely painful to watch, get a pair of cable cutters from harbor freight tools and cut the 4 pipes at the body, if needed remove the condenser coil. We did two at a church last month, From the time the first pipe was cut until the last braze was less than thirty minutes. Also with the larger ones we use two torches, a guy with a turbo and a guy with oxygen acetylene doing the brazing. If your supply house has any warranty reversing valves I suspect most of them are going to be cut off with cable cutters, seeing one cut at the supply house is actually how I learned the trick.

  • @1mpishskillz
    @1mpishskillz Жыл бұрын

    Good job man

  • @DLEngle
    @DLEngle2 жыл бұрын

    Nice!

  • @davee6727
    @davee67275 ай бұрын

    Great video. Thanks for putting this together.

  • @tonydelgrego2906
    @tonydelgrego29062 жыл бұрын

    Nice professional repair

  • @themrmoy40
    @themrmoy402 жыл бұрын

    what about the heat blanket , you think that would work better.?

  • @Adamn7210
    @Adamn7210Ай бұрын

    Why flip the recovery tank? Can’t you just go back with the liquid port?

  • @2purplemartin1
    @2purplemartin1 Жыл бұрын

    Yeah cut the valve out next time. Makes it way way easier. Unsweat the discharge and cut the rest out with your yellow or greens.

  • @hectormendoza993

    @hectormendoza993

    5 ай бұрын

    Way to go, nice

  • @dimaslespier2688
    @dimaslespier26882 жыл бұрын

    Curious question? Between replacing the compressor,outdoor TXV, and the three way valve. Wouldn’t it been cheaper and better for the customer to just replace the entire condenser? Between all that labor parts had to have been less expensive to just put a new condenser? and customer get a new 5 year on the compressor plus new labor warranty.

  • @NighthawkHVAC

    @NighthawkHVAC

    2 жыл бұрын

    This was discussed with the client but they opted to make the repairs. You haven’t seen the air handler. That’s another headache.

  • @AJ-ox8xy

    @AJ-ox8xy

    Жыл бұрын

    Some people either can't afford a new one or don't care to use financing.

  • @chrismyers5758
    @chrismyers5758 Жыл бұрын

    That recovery bottle has a spout that goes to the bottom for the liquid you don’t have to turn those upside down I think that was counter productive

  • @NighthawkHVAC

    @NighthawkHVAC

    Жыл бұрын

    I’m aware of that. That’s why my hose was attached to the vapor side.

  • @caru3257

    @caru3257

    Ай бұрын

    When charging on heat, aren’t you supposed to hook to the true suction line?

  • @hvactechwanttobe1499
    @hvactechwanttobe14992 жыл бұрын

    Did you double check to make sure the value is bad Nice work

  • @jacobbell1934

    @jacobbell1934

    Күн бұрын

    Most the time people don’t do that. It’s a good idea and makes customer very happy when they end up not needing something expensive

  • @avtarsingh7598
    @avtarsingh7598 Жыл бұрын

    Very good Experience Avtar singh virdi(India)

  • @68dnell
    @68dnell2 жыл бұрын

    What’s the name of that swager?Thanks

  • @NighthawkHVAC

    @NighthawkHVAC

    2 жыл бұрын

    It’s a Hilmor Compact Swage Tool Kit 3/8" To 7/8”. www.trutechtools.com/1839015?gclid=EAIaIQobChMIsMHe17Lx9QIVdh-tBh0aGgvvEAQYASABEgIn6PD_BwE

  • @68dnell

    @68dnell

    2 жыл бұрын

    Thanks Bro!

  • @Charlie-hb9ic
    @Charlie-hb9ic Жыл бұрын

    What should the thermostat setting be set on for the reversing valve? Cool or heat?

  • @NighthawkHVAC

    @NighthawkHVAC

    Жыл бұрын

    It depends on the brand. Most heat pumps are default heat which means when the reversing valve is not energized it’s in heat mode. Requiring a call for Y for heat. In cooling the reversing valve is energized setting it to cooling mode. This is requiring a call for Y and O. Other brands are default cool which is opposite of this. Rheem and Ruud are default cool. Meaning for cooling only a call for Y is required. For heat Y and B are required. That’s why some heat pumps have a O and others have a B. O= default heat energized for cooling B= default cool energized for heat. Y= Compressor calls for compressor. Hope this helps. Thanks for watching.

  • @s550wulf9
    @s550wulf9 Жыл бұрын

    Makes me sad watching this, dude cut the damn valve out, and do the work outside of the unit

  • @nothankyou5524

    @nothankyou5524

    Жыл бұрын

    Outta AC pre-2010. Asked 2 swap a 4 wy vlv. Many outside da box swaps in NC. No good? Never thought bout it til just now? PS: No N2? Never tuched a unit w/out it. Any thoughts. Appreciate it. Best wishes/Best of luck.

  • @natehicks8939
    @natehicks89392 жыл бұрын

    Next time use your recovery machine and push the refrigerant into your equipment.

  • @NighthawkHVAC

    @NighthawkHVAC

    2 жыл бұрын

    I thought about that but I have never tried it. Would there be any negative effects to the system?

  • @natehicks8939

    @natehicks8939

    2 жыл бұрын

    @@NighthawkHVAC it is the opposite of what you did to recover the refrigerant. Now it is the cylinder that you are pulling from and your system is what you are pushing too. Nothing negative about it. So you would not need to use your torch like you did to build the pressure (just view it as you recovered your system you didn’t need to increase the pressure from it), you would just need to keep your cyclinder on the scale to read what you pushed back into your heat pump.

  • @NighthawkHVAC

    @NighthawkHVAC

    2 жыл бұрын

    Nice. I’ll try that on the next one. Thanks.

  • @marccook44

    @marccook44

    Жыл бұрын

    @@NighthawkHVAC Just make sure you do not fill up your accumulator when you push freon in the system with your recovery machine unless you are just going to weigh it in and not look at your pressures. I could not tell if your bypass port was before or after the accumulator. We like to push the freon in the liquid line to prevent this. Nice work.

  • @garygrey650

    @garygrey650

    11 ай бұрын

    R410 should be charged in Liquid state. Recovery machine does vapour

  • @gemmrk
    @gemmrk13 күн бұрын

    You should have covered the painted surface before you used the torch, by torching the paint, the customer will now have a rust issue very quickly. This is why you guys have a bad rep because too often you are not careful and cause issues as you fix others.

  • @dannygonzalez5844

    @dannygonzalez5844

    5 күн бұрын

    Kind of details that almost any customer will see after that hard work , , all customer are more worried about to get the house cooled or heating , not the surface paint....CO