How To Recharge and Check an Expansion Vessel - Combi Boiler - Plumbing

Тәжірибелік нұсқаулар және стиль

How to Check and Repressure an Expansion Vessel on a Boiler Service. Plumbing Tips.
Combi Boiler Service. How to check and pump up the expansion vessel on a boiler service.
Plumber showing how to recharge a boiler expansion vessel with a foot pump and also showing what the correct charge should be and how you find out what pressure it needs to be.

Пікірлер: 259

  • @AllenHart999
    @AllenHart9993 жыл бұрын

    facebook.com/groups/Gas999/

  • @ashrafalimansoor7569

    @ashrafalimansoor7569

    3 жыл бұрын

    Fantastic explained on how to pressurise system.well done

  • @johncollins347

    @johncollins347

    3 жыл бұрын

    👍

  • @rainsnow9174

    @rainsnow9174

    2 жыл бұрын

    Allen does vessel need to be empty of water before repressuring it, and if so how would I go about emptying mine. Baxi ecoblue 28

  • @marcinrybski9075
    @marcinrybski90753 жыл бұрын

    I called specialist to recharge and service my boiler but seeing how does it work from this video is absolutely priceless. Thanks for sharing your knowledge.

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks.

  • @map747
    @map7473 жыл бұрын

    Great video. This is the sort of information and tips that can give you confidence in the fact that you now know the workings of the expansion vessel.

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Glad it was helpful!

  • @mad-dog
    @mad-dog Жыл бұрын

    Had this problem with my combi , checked the pressure in my expansion vessel and after following all the procedures in this video . Found no pressure in expansion vessel and found the valve has a very slight leak with the spit on valve test . Put 1 bar in vessel as per sticker on vessel and all runs perfect . Will get a valve tool and new valve and fix it . You’ve saved me a lot of money …… thanks 👍👍👍👍👍👍

  • @Midahed
    @Midahed2 жыл бұрын

    What a brilliant, clear and comprehensive tutorial - thank you!

  • @rapido2962
    @rapido29623 жыл бұрын

    What a clear and comprehensive tutorial! After living with a high pressure gauge for months I thought I had better do something about it before the cold weather really arrives. Before I shelled out for a new boiler, I thought I'd browse KZread and came across this 'How to'. I followed the tutorial and it is now fixed! The boiler is a Worcester Bosch 24i Junior - 11 years old. It just needed the expansion vessel re-pressurising. Subscribed!

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Great to hear!

  • @rogermunns9206

    @rogermunns9206

    2 жыл бұрын

    Me too! Thanks, very clear instructions, unlike some others .......

  • @pgtips9236

    @pgtips9236

    5 ай бұрын

    I have the 28i Junior & this fixed my issue aswell, the factory vessel pressure on both models is 0.75 Bar but the suggested 1Bar in this video isn''t significantly more

  • @guerillacity
    @guerillacity3 жыл бұрын

    This was brilliant, as a complete novice who has no clue about boilers this helped me fix my boiler, thank you!!

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    If you have removed the case please have it checked by a gas safe engineer. Thanks.

  • @khanyekhanye7490
    @khanyekhanye7490 Жыл бұрын

    I am so grateful for this video! Thanks for the clear explanation on this aspect that other videos could not explain half as clearly as you did here! 3 cheers for that!

  • @namesanmanname297
    @namesanmanname2972 жыл бұрын

    Excellent . Very Detailed Video. Thank you Allan. This guy is very much a good technician .

  • @AllenHart999

    @AllenHart999

    2 жыл бұрын

    Thank You

  • @alanmabey2144
    @alanmabey21442 жыл бұрын

    Alan,where ever you live I would like to buy you a beer!4 visits from British Gas and they still left the boiler over pressured.My original fault was a faulty diverter valve.They came back several times ,re pressurised the expansion vessel,totally incorrectly as watching this video they didnt de pressure the system full!they then replaced pressure switches,heat exchanger and they basically condemned the boiler.This was costing me time and lost wages.Following the guidance here and modifying a bike pump from Halfords (£40) I have sorted the problem. I will be sharing this video to British Gas as there engineers clearly haven’t a clue.More interested in selling boilers than fixing them.Thanks once again I am totally in your debt.

  • @robi4387

    @robi4387

    Жыл бұрын

    There is another video going around where a plumber said the two boiler in a house had to be replaced and it needed extra pressure vessels too £££££. I wonder if they did a volume expansion calculation or just went by 1L per kW or maybe saw the person get out of they Porsche.

  • @plumbdog1964
    @plumbdog19643 жыл бұрын

    Allen good video mate. One thing worth talking about is a possible blockage to the expansion vessel, more likely on the ones with flexy hose connections.

  • @Mad4plumbing-ltd
    @Mad4plumbing-ltd3 жыл бұрын

    Great explanation as always on this great Channel! Never get enough of all this shared knowledge. Many thanks to Alan and all who participate ❤️

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thank You

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @michaelrose5040
    @michaelrose50403 жыл бұрын

    Great video for newly qualified engineers. Thankyou

  • @andycollins4453
    @andycollins44532 жыл бұрын

    Done the job …got it in …well 2 …heating on …no water down the wall outside …all’s good thank you soooo much would happily pay ..of course cheaper then the plumber ..Lucky for me mine is the same boiler - Brilliant tutorial

  • @AmigaA-or2hj
    @AmigaA-or2hj Жыл бұрын

    Thanks for the tip! I’ve pumped up my Sime iqe 35 simplicity after following your video. The problem is that I couldn’t find drain tap. So I had to loosen the nut under the expansion vessel to drain the water out.👍👍👍

  • @Bisher1967
    @Bisher19673 жыл бұрын

    Thanks very much for sharing this knowledge, really much appreciated.

  • @MrChriswelch80
    @MrChriswelch802 жыл бұрын

    Thanks for that Allen. That was the most informative video on expansion vessels I could find👍.

  • @AllenHart999

    @AllenHart999

    2 жыл бұрын

    Glad it was helpful!

  • @tonygreen4896
    @tonygreen48962 жыл бұрын

    Thanks for this. Just successfully pumped up my Vaillant having carefully followed the steps you showed. A very easy job in the end.

  • @AllenHart999

    @AllenHart999

    2 жыл бұрын

    If you have had to break the combustion seal please make sure you have it tested by a Gas Safe registered Engineer. Thanks.

  • @tonygreen4896

    @tonygreen4896

    2 жыл бұрын

    @@AllenHart999 Thanks but The expansion vessel was easily accessed by taking off the front cover only. Currently running at 1.8 bar cold and 2.2 full heat. Previously was heating the house but display blinking and pressure 3.2 bar.

  • @Pagetsgarage
    @Pagetsgarage6 ай бұрын

    Followed this video to a T! Very easy to follow for a Baxi boiler! Thank you again! I’ll let you know if the pressure drops over the next few days!

  • @johnboy1232
    @johnboy12323 жыл бұрын

    Another very clear and concise video.I used to find at least 10% of the expansion tank valves leaking and used to carry the short core valves ( perchased from a motor factor, ) I had not seen this valve tool before ,I used to use the cross shaped valve tool with two off the pertusions cut down so I could get the thing in the more challenging positions say down the back of the boiler but leave the stubs so I could turn it,could be quiet difficult sometimes.

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks for watching and commenting.

  • @incorrect1844
    @incorrect18443 жыл бұрын

    The best video on KZread!thanks guys for taking the time to make this!

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Glad you enjoyed it!

  • @ChristianBHough
    @ChristianBHough3 жыл бұрын

    Thoroughly explained, thank you.

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Glad it was helpful!

  • @andrewbeer9525
    @andrewbeer95255 ай бұрын

    What a great detailed video with clear explanations and fantastic tips too. Well done

  • @Pablo-mu5yl
    @Pablo-mu5yl Жыл бұрын

    I just finish the job. Thanks for the help with that video.

  • @guinnessdublin4669
    @guinnessdublin46693 жыл бұрын

    Very good clear walk through, thank you!

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Glad you enjoyed it!

  • @brianwood5220
    @brianwood52203 жыл бұрын

    Loads of great info and tips for those learning. 👌👌

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks for watching.

  • @rumanuddin2282
    @rumanuddin22822 жыл бұрын

    Thank you paul well explained Allen your vids are blessing thanks.

  • @plumbdog1964
    @plumbdog19643 жыл бұрын

    Good video, thanks for tip about pushing diverter motor down to drain it

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thank You

  • @leecoombes8540
    @leecoombes85403 жыл бұрын

    Always Excellent video(s). 👍

  • @aeko
    @aeko3 жыл бұрын

    Thanks for this detailed video!

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Glad it was helpful!

  • @ryandow3954
    @ryandow39543 жыл бұрын

    That is a brilliant video!

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks.

  • @jimmyclark8229
    @jimmyclark82293 жыл бұрын

    Great video well detailed on correct procedure .👍

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks.

  • @chohanchohan8208
    @chohanchohan82083 жыл бұрын

    OMG! Wicked Video Thanks So Much Allen and Team WB

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Glad you enjoyed it

  • @yoogeebearproductions4581
    @yoogeebearproductions45813 ай бұрын

    Excellent video. Any videos on how to charge, discharge check etc expansion vessels on a unvented system? There are two one on my system one is white which is for the hot water and there is one red one for the radiators. If radiator expansion vessel has been charged to higher static pressure than manufacturer specification (recommendation) would this put extra pressure on the boiler heat exchanger. Causing heat exchanger to eventually fail?

  • @chriscollins508
    @chriscollins508 Жыл бұрын

    A really useful and well presented video. Thank you.

  • @AllenHart999

    @AllenHart999

    7 ай бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @SK-Cambridge
    @SK-Cambridge Жыл бұрын

    Very extensive and helpful. well done👍🏼🙏🏻

  • @AllenHart999

    @AllenHart999

    7 ай бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @davidr4533
    @davidr45333 жыл бұрын

    Excellent video Allen. But I cannot work out how to drain my Ideal Logic Plus C35 combi boiler. I find the black plastic plastic part under the boiler with the slot in it. My boiler is new but the pressure fluctuates between 1 and 2 bar (1 bar when cold and 2 bar when central heating on). On my last combi (Worcester Bosch) the pressure hardly moved when the expansion vessel was correctly pressurised. I want to check the new boiler expansion vessel pressure as I suspect installer never did that. Thanks for your excellent videos.

  • @roybatty2030
    @roybatty20304 ай бұрын

    Great video, thanks but how do you get the condensation out of air side of the vessel?

  • @dron4147
    @dron41472 жыл бұрын

    Great video, very informative. Thanks.

  • @AllenHart999

    @AllenHart999

    2 жыл бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @mahmoudayoubi3683
    @mahmoudayoubi36833 жыл бұрын

    Alen you are the best

  • @Rucio88
    @Rucio882 жыл бұрын

    Amazing video! Thank you!

  • @AllenHart999

    @AllenHart999

    2 жыл бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @SuperBlackguard
    @SuperBlackguard Жыл бұрын

    fantastic video and very good knowledge to have cheers!

  • @AllenHart999

    @AllenHart999

    7 ай бұрын

    Thank You

  • @naturelover_9211
    @naturelover_92113 жыл бұрын

    Very helpful video thank you.

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @michaelsly9180
    @michaelsly91802 жыл бұрын

    hi thanks for the info , my boiler pressure was increasing to 3.5 bar , drained out the boiler and checked the vessel pressure which was zero, repumped to 1 bar the boiler is now running at 1.5 bar , great help thanks allen

  • @raj080288

    @raj080288

    Ай бұрын

    Is that 1.5 when the heating is on?

  • @doggy55915
    @doggy559153 жыл бұрын

    Excellent video.

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks

  • @naeemchaudhary2654
    @naeemchaudhary26542 жыл бұрын

    Thanks Keep doing good work

  • @TheJSB007
    @TheJSB007 Жыл бұрын

    Amazing advice. I have a worcester greenstat cdi boiler that keeps losing pressure from 1.5 bar to 1 bar every two weeks approx. When it was installed the engineer set it up to 1.5 bar. I was always thinking the expansion vessel was at fault. Is it possible that the vessel is undercharged and is correcting itself somehow?

  • @jogamatudo
    @jogamatudo Жыл бұрын

    Allen, great video, thank you! What is the system telling me when, after pumping up the expansion vessel to 1 bar and opening up the flow & return valves the pressure doesn't go up to 1 bar and stays at around 0? The vessel seems to be holding charge at 1 bar (air mesaured). Should i just fill the system up? I am pretty sure the system is full!

  • @robertarnold549
    @robertarnold5492 жыл бұрын

    Excellent, thank you.

  • @cyril4892
    @cyril48923 жыл бұрын

    thanks allen from France

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks for watching

  • @shazadkhaliq
    @shazadkhaliq Жыл бұрын

    I just had a Bosch engineer fix this issue on mine. Same Bosch boiler as in video. Pressure dropping then when you put it up would jump to 3 bars. He recharged the vessel. Was curious this explained why he did in more detail. Thanks

  • @jezsmithx
    @jezsmithx2 ай бұрын

    Excellent explanation. Job done

  • @MrCrazycool85
    @MrCrazycool853 жыл бұрын

    Great video sir. What else might it be if not a punctured vessel? I lost complete pressure on my boiler after hearing a weird noise while the boiler was on and when i try to re pressurise the boiler the water goes straight through the over flow pipe outside is this the expansion vessel?

  • @trusay8338
    @trusay83382 жыл бұрын

    this is a good video .. thanks for this

  • @farukadam1696
    @farukadam16963 жыл бұрын

    Excellent video both of you Regards Faruk

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thank you

  • @thanasisKrispis
    @thanasisKrispis Жыл бұрын

    thank you for the excellent lesson!!!

  • @AllenHart999

    @AllenHart999

    7 ай бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @Jamespaintsplastic
    @Jamespaintsplastic3 жыл бұрын

    Thanks, I really enjoy these videos. Would you also use the same method on an additional remote expansion vessel? Or would you charge it live?

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    You cannot charge one live really. Thanks.

  • @naveedhashmi4897
    @naveedhashmi48974 ай бұрын

    Very informative Thanks

  • @Mandmcr
    @Mandmcr Жыл бұрын

    Very helpful thank you!

  • @AllenHart999

    @AllenHart999

    7 ай бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @mickwalker4225
    @mickwalker42253 жыл бұрын

    Great video

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thank You.

  • @grahamvickers1552
    @grahamvickers15523 жыл бұрын

    Great video 👌👍

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @nevergiveupever1069
    @nevergiveupever1069 Жыл бұрын

    Hi Allen. I pressurised a worcester 24cdi to 0.8bar but its not holding pressure. Initially the Schrader valve was letting by. I changed the Schrader valve and pressurised the expansion vessel according to the manufacturers spec. As soon as i turn the boiler on after setting the system pressure the pressure drops down to 0.2 bar . Could it be a faulty pressure gauge or leaking diverter diaphragm?

  • @ljudmillamihhalko3526
    @ljudmillamihhalko35263 жыл бұрын

    It's good lessons for all engineers, who instead of doing job simply capped at outlet gas supply & keep your family without heating & hot water by month or more to make safe faulty boiler.

  • @1984Scottyb
    @1984Scottyb Жыл бұрын

    Great video but after following the steps and turning the valves on, the pressure gauge didn't move to 1 like yours did. So what does this mean? Thanks

  • @YouSillyLittleBoy
    @YouSillyLittleBoy3 жыл бұрын

    Great video Allen, when fitting external expansion vessels does it matter what rotation they are connected for example can they be piped into the bottom instead of the top (can it be fitted upside down) ?

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @freefilms10000
    @freefilms100002 жыл бұрын

    must I drain the central heating section of the boiler before testing the expansion vessel pressure and if necessary it topping up ? I am confused as I understand that when the system is working properly it is quite acceptable to test the pressure in the vessel and get an accurate reading.

  • @maxxwest842
    @maxxwest8422 жыл бұрын

    Hello, Allen - After watching this video, I checked the Schrader valve in the expansion vessel on my Worcester bosh 24 junior boiler and found it was leaking. I cannot find a replacement valve this small. Do you know where I can get one from? Thank you, Maxx

  • @richardhunt304
    @richardhunt3043 жыл бұрын

    Very interesting video-thanks.

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Glad you enjoyed it

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @ArcanePath360
    @ArcanePath36017 күн бұрын

    My vessel valve is leaking slowly over time. Can I just replace it, pump it back up until the needle on the boiler goes back up to it's 1 bar where it should be? I don't understand having to isolate, drain down etc unless you are also putting water into the system, is that right? Thanks for the detailed video. I've ordered that valve replacement tool with some new valves which should come tomorrow

  • @trevorangieellis7497
    @trevorangieellis74973 жыл бұрын

    Excellent video

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks for the visit

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @luv2jive
    @luv2jive3 жыл бұрын

    brilliant. thanks so much

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @ianbirch5811
    @ianbirch58113 жыл бұрын

    Great video , my boiler is at 1bar when its cold & goes between 1-2 bar when the heating is on , however when the pump starts from cold the pressure drops to 0.75 bar the rises slowly ! Is this normal ?

  • @lastchance8142
    @lastchance81423 ай бұрын

    Should the pre-charge be adusted for multi-level residences?

  • @mohammedarif9453
    @mohammedarif94533 жыл бұрын

    Hi I just want to ask if there is no charge on the vessel but you can see water coming from the shredder valve what is the cause thanks

  • @raul835
    @raul8353 жыл бұрын

    When you think you know it all then realise you don't.. ha ha.. good vid

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Everyday is a school day. Thanks for watching.

  • @fagen2222
    @fagen22223 жыл бұрын

    Good one mate sorted for me

  • @user-hm9fg6jl8t
    @user-hm9fg6jl8t7 ай бұрын

    Very good video.

  • @AllenHart999

    @AllenHart999

    7 ай бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @MrNigelbell
    @MrNigelbell2 жыл бұрын

    Thank you.

  • @k20aa
    @k20aa3 жыл бұрын

    Great Vid 👍👍👍

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks.

  • @Supergreene36
    @Supergreene362 жыл бұрын

    Hi, great tutorial, just one question, when isolating the flow underneath the boiler am I correct in saying thats the flow of the central heating? Thanks

  • @robi4387

    @robi4387

    Жыл бұрын

    Isolate flow and return, drain the boiler and pump via Schrader, to vessel label pre-charge pressure. Check the vessel holds charge. Test the Schrader valve itself. Close the drain. Open the flow and return. Bleed or let the boiler run its auto-bleed cycle. Re-pressurise the system to vessel pre-charge plus 0.2 to 0.5bar. If you are a Gas Safe registered engineer that is. If you are not and you wondering why there is contradictory advice out there regarding whether your boiler expansion tank is even big enough never mind what pressure the boiler gauge should run at then you'll just have to ask someone who is, who will then charge you explanation time if you are lucky.

  • @sunnybeachwalks4k2022
    @sunnybeachwalks4k20225 ай бұрын

    Got a a question how do you re charge an expansion vessel on a hidrotank expansion vessel with pump for mains water pressure

  • @asif530
    @asif5303 жыл бұрын

    Nice explanation. I thought the water expands and pushes against the air balloon inside. Unless I heard it wrong it was mentioned the other way in the video?

  • @SalimKhan-gk1fh

    @SalimKhan-gk1fh

    3 жыл бұрын

    Yes it does asif, But it only pushes on the balloon membrane when it’s heated when it’s cold the air pressure would be one bar

  • @samjones3106
    @samjones31068 күн бұрын

    Jumping up to 3 bar is exactly what my boiler does. Then it makes a loud banging noise a few times and shuts off giving an error code followed by a hissing sound. I thought it was the pump but now I think it might be this expansion vessel. It is a Saunier Duval F25.

  • @iancampbell582
    @iancampbell5823 жыл бұрын

    Most uk and Irish oil boiler manufactures recommend 0.5 bar or 0.75 max (Grant boilers for one).All the oil systems i work on get cold charged to half a bar and never an issue.Ive noticed some oil boiler safety valves rated at 2 or 2.5 bar to lift rather than the usual 3 bar .Makes sense. I get a lot of customers over charging there oil systems because of the information on KZread some gas guys recommending as much as 1.5 bar which starts the cycle of losing water via the prv.Then the custard is convinced they have a leak and spend hours trying to source it.lol. Which can be difficult to explain to some clients.

  • @johncollins347
    @johncollins3473 жыл бұрын

    Hi Allan, can you do a video with more in depth info on expansion vessels. Particularly when adding an additional vessel to an existing system. I'm not sure exactly what effect the pre pressure and increasing the pressure will have on the existing system. Many thanks

  • @b1h2u3p4
    @b1h2u3p4 Жыл бұрын

    Can u hold open prv and pump up vessel that way if no drain off 🤔

  • @michaelprobert3607
    @michaelprobert36073 жыл бұрын

    Hi really detailed video very good! Just wondering if the reason water comes out when you are charging with air is the balloon is expanding and pushing water out the expansion vessel?

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Yes it does

  • @raj080288

    @raj080288

    Ай бұрын

    I believe it's the condensation that has built up

  • @waynehorne2459
    @waynehorne24593 жыл бұрын

    Brilliant 👍👍👍

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @EasyToDIY
    @EasyToDIY3 жыл бұрын

    excellent

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thank you! Cheers!

  • @stewartharrod8562
    @stewartharrod85623 жыл бұрын

    Hi guys I have a system boiler Red Expansion vessel is on the airing cupboard its constantly losing pressure but nothing coming out of the PRV No leaks on the system (rads/pipes) at all

  • @rainsnow9174
    @rainsnow91742 жыл бұрын

    Does expansion vessel have to empty of water before repressurising it to 1 bar

  • @richardhodgson7443
    @richardhodgson74433 жыл бұрын

    Awesome 👍

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Thanks 🤗

  • @EdenTan7368
    @EdenTan73687 ай бұрын

    Hello Allen Thank you so much for your video, it is great helpful, but would you like to answer my question please? That’s after I repressurise expansion vessel to 1 bar and a few minutes later, the pressure keeps going up until 3 Bar, ( expansion vessel and prv are new). This caused by main cold water keeps going into the boiler, even I isolated flow and return pipe , then open drain valve, the slight water keeps going out from the boiler. So how can I stop slight water going into the boiler? Thank you

  • @AllenHart999

    @AllenHart999

    7 ай бұрын

    kzread.info/dash/bejne/imiD1dWmhaisn5c.html

  • @AllenHart999

    @AllenHart999

    7 ай бұрын

    Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @Carzineeeeeeeeeee
    @Carzineeeeeeeeeee3 жыл бұрын

    My tech installed a amtrol st-5 for my Viesman boiler (Radiant Heat only). I looked at the specs and it looks like it is pre-pressurized at 50psig. Would that cause issues with my Viesman boiler loosing pressure after a few days? (I think the pressure release valve is triggering because the Expansion vessel is over pressurized)

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    Happy holidays!

  • @kjhi98
    @kjhi983 жыл бұрын

    great video!. Anyone any idea what should the expansion vessel charging pressure of the Worcester 28i junior (mk v) be ? many thanks

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    i normally set the just less than 1 bar. 0.8 ish. Give the manufacturer a call to double check though. Thanks.

  • @kjhi98

    @kjhi98

    3 жыл бұрын

    ​@@AllenHart999 ,yeh you're right fella, worcester say 0.75,so spot on .thanks alot!

  • @andy9962
    @andy99622 жыл бұрын

    thank you sir ,this's a great help. but draine the boiler isn't easy for me since I don't want to mess up , so for get the pressure out of the boiler, instead can I draine the whole lot system water out which I know quite well

  • @AllenHart999

    @AllenHart999

    2 жыл бұрын

    You should only remove the case on this boiler if you are gas safe registered or competent to do so. Thanks.

  • @andy9962

    @andy9962

    2 жыл бұрын

    @@AllenHart999 thank you Allen, my boiler is the Worcester greenstar 28i junior, which the Expansion Vessel is outside the case,so I don't need to remove the case. please tell me would it be the same if I draine the whole lot system water out which I done it before.

  • @tsankotsankov9772
    @tsankotsankov97722 жыл бұрын

    I do everything how you explain and the boiler still run on 3.5 bar

  • @practicalvoice1220
    @practicalvoice12203 жыл бұрын

    You should run ads to get more views your videos are great!

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    How do you do that?

  • @Sniperworks

    @Sniperworks

    3 жыл бұрын

    @@AllenHart999 you have to go to youtube monetization on your youtube setting and apply to be a partner. Before you can be a partner you have to have 1000 subscribers and 4000 hours of watch time within a 12 month period. Once they accept you I think there are several way of getting paid for your video. One of them is having adverts on your videos.

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    @@Sniperworks Thanks.

  • @AllenHart999

    @AllenHart999

    3 жыл бұрын

    @@Sniperworks Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @Sniperworks

    @Sniperworks

    3 жыл бұрын

    @@AllenHart999 going to subscribe. Thanks for the videos

  • @paulbootle3263
    @paulbootle3263 Жыл бұрын

    Hi Allen, what does it mean when your boiler is working fine all pressures ok when just using hot water but when heating has been on the pressure drop after? Thanks

  • @khanyekhanye7490

    @khanyekhanye7490

    Жыл бұрын

    This was my exact problem! It’s likely the expansion vessel needs a recharge . But drain the boiler thoroughly first as described on the video. I am so happy I learned from here and yesterday I resolved the problem!

  • @mrmehuddin8036
    @mrmehuddin803610 ай бұрын

    I have a baxi 630 combi and it has a flexi pipe fitted for the filling of the tank, the main tap that supplies water from the main is always off, as always. The second tap I have left open, can this cause the boiler to drop it's water?; which I suspect it is doing with my boiler.

  • @AllenHart999

    @AllenHart999

    7 ай бұрын

    its better to close them both