How to Fit a Type 2 SPD Remote from the Consumer Unit with Correct Conductor Lengths (Crabtree)

How to fit a type 2 SPD and keep the line and earth conductors at 0.5m or less. We fit the SPD remote from the consumer unit proving how hard it is to keep conductors short enough to comply with BS7671. This Crabtree SPD eventually has to be fitted inside the consumers unit to ensure the conductors do not exceed 0.5 of a metre.
Videos are training aids for City and Guilds (C and G) and EAL courses Level 1, 2, 3 plus AM2, AM2S and AM2E.
You can follow me day by day on Facebook, Instagram, Twitter and TikTok lookout for "GSH Electrical”.
▶️ FACEBOOK / gshelectrical
▶️ INSTAGRAM / brihzmraygdtmjmdb9lunq...
▶️ TWITTER / gsh_electrical
▶️ TikTok vm.tiktok.com/ZMRBLFdhe/
#GSHElectrical #Electricaltrainingvideos #spd

Пікірлер: 101

  • @horatiofluffytop
    @horatiofluffytop5 жыл бұрын

    Hello Gaz, I’m a (very) mature learner and find learning from books hard work so your videos are a Godsend to me, your presentations are so clear and easy to understand. A massive thanks to you and everyone at GSH. Paul.

  • @GSHElectrical

    @GSHElectrical

    2 жыл бұрын

    Thanks for the great comment 👍🏻

  • @MyNameWasTecho
    @MyNameWasTecho5 жыл бұрын

    Informative and entertaining as always. Can’t beat a bit of torque driver action 👍

  • @earlyyearslearningisfun
    @earlyyearslearningisfun5 жыл бұрын

    Your learners have many wonderful opportunities at your college. Keep up the great work lads 👍

  • @vievlogs589
    @vievlogs5895 жыл бұрын

    Thanks for the content SPD’s very helpful team Electrical 😁👍

  • @stephengreen909
    @stephengreen9095 жыл бұрын

    It can't get any better.. Can it... Amazing as usual lads.. 👍👍👍

  • @GSHElectrical

    @GSHElectrical

    5 жыл бұрын

    😊Thanks form Team Electrical 👍

  • @lsnogaming2893
    @lsnogaming28935 жыл бұрын

    Very helpful team Electrical 👍👍

  • @richardwash6678
    @richardwash66785 жыл бұрын

    Brilliant video guys, very informative. 👍

  • @ashmanelectricalservices4318
    @ashmanelectricalservices43185 жыл бұрын

    An all in one unit is definitely the way to go.

  • @frankhayes1135
    @frankhayes11354 жыл бұрын

    It's about time that screw heads in MCBs etc are torx heads, especially if manufacturers are requesting such high tightening torques.

  • @andrew7440

    @andrew7440

    Жыл бұрын

    I've got one of those Wiha drivers, good piece of kit. Never knew it went that high, don't think I've ever gone past 2.5Nm!

  • @artisanelectrics
    @artisanelectrics5 жыл бұрын

    Good idea for a video!

  • @protectiongeek
    @protectiongeek2 жыл бұрын

    The requirement of Reg 534.4.8 regarding connections being short and as straight as possible is VERY important and shouldn't be easily ignored. Any bends - especially loops - in the conductor will appear to any extremely fast-rising voltage 'spike' (in the order of a number of kV in microseconds) as a significant impedance. The danger is that some other part of the installation presents a lower impedance path to earth and is damaged while the SPD remains intact. Same principles apply to the earthing of surge diverters on HV overhead lines and terminations. I've seen flashovers from 90 deg bend 'elbows' in 70 sq mm earthing conductor, which looked great but ultimately defeated the purpose of the protective device.

  • @gc2electricalsolutions973
    @gc2electricalsolutions9735 жыл бұрын

    Great informative video.

  • @johnsimpson8263
    @johnsimpson82635 жыл бұрын

    My poor old arthritic wrists were aching in sympathy watching that tightening. Also I can think of a few larger switchboards that would exceed the 0.5-1.0m distance just within the board...

  • @delspark
    @delspark5 жыл бұрын

    Great video wrist strength test as well 💪

  • @GSHElectrical

    @GSHElectrical

    5 жыл бұрын

    Hence Joe did the torque setting 🙌thanks for commenting and watching GSH Electrical 👍

  • @flow5718
    @flow57185 жыл бұрын

    Great video, just one suggestion. As a rule of thumb, always install SPDs downstream of MCBs and upstream of RCCB (MCB --> SPD --> RCCB). There are exceptions of course, with certain types of RCCB's being able to be installed upstream of the SPD but follow the rule of thumb if you don't want to deal with that constraint.

  • @dsesuk
    @dsesuk5 жыл бұрын

    Top tippery as always chaps!

  • @GSHElectrical

    @GSHElectrical

    5 жыл бұрын

    Thanks friend of Tresham 👍👍👍

  • @dsbelectricaldavidbetterid8448

    @dsbelectricaldavidbetterid8448

    5 жыл бұрын

    the best you tuber sparky going nic to see you here you doing a longer gsh vid soon

  • @NicolasRaimo
    @NicolasRaimo11 ай бұрын

    Great Video, well presented by everyone

  • @GSHElectrical

    @GSHElectrical

    11 ай бұрын

    👍🏻 thanks Nick

  • @tigertooth4678
    @tigertooth46782 жыл бұрын

    I didn't realise that the 1 mtr rule includes both the live conductor AND the earth conductor. Thanks for that update. 👍👍 I assume then that the self contained stand along packages you can buy are fully conversant then.

  • @kint5ugee
    @kint5ugee2 жыл бұрын

    10:28 did I hear a fart? 🤣

  • @connordickens2617
    @connordickens26175 жыл бұрын

    Nice video

  • @thattoolguy9432
    @thattoolguy94325 жыл бұрын

    Great video guys.. looks like Wera need to step up the game, as my new torque set only goes as high as 3.0nm ... oh dear!

  • @miike_1m229
    @miike_1m2295 жыл бұрын

    Poor old spark following up trying to undo those terminals 😂 on a plus side the last guy said consumer unit, and not consumers unit 😁

  • @davidmanning5874
    @davidmanning58745 жыл бұрын

    THESE TORQUES SETTINGS ARE ALL O/K BUT WHEN YOU ARE JAMMED UP NEAR THE CEILING OR UNDER THE STAIRS NOT SO EASY I THINK THEY SHOULD MAKE THESE NEW DRIVERS WITH A TEE BAR RATHER THAN THE ORDINARY SCREWDRIVER HANDLE MIND YOU COULD MAKE YOUR OWN

  • @andybell6641
    @andybell66415 жыл бұрын

    A Tip with Whia drivers is that you can use a spanner on the handle to help with leverage

  • @GSHElectrical

    @GSHElectrical

    5 жыл бұрын

    Hi, fantastic tip 🙌

  • @buckshee
    @buckshee2 жыл бұрын

    I fit meters which are specific for solar, the torque setting for the terminals are 0.9nm. Had to buy another torque driver handle to go down that low, never seems tight enough but ours is not to reason why and I always do a tug test.

  • @DCMamvcivmEvony
    @DCMamvcivmEvony5 жыл бұрын

    Where does the initial seperate board and spd enclosure stand with regards to 521.5.1 (ferromagnetic enclosures: electromagnetic affects)?

  • @peterjones2761
    @peterjones27612 жыл бұрын

    I'm about to move my consumer unit position (fitting a new one in the process) and moving the cut out into the garage with a 80A switchfuse mounted adjacent to feed the house. I was looking at ready made self contained SPDs and read the instructions. I'm advised that SPDs are not suitable for an overhead fed property (which is my place, a rural position on a hill and exposed). Im puzzled, we have had a lighting strike a few years ago and it took out the TV, fridge and BT equipment (insured luckily) but I have been led to believe we MUST fit SPDs on new installations now. If I'm advised that they are not suitable in my property whats the point, Iwill therefore not be complying with the wiring regs. Im puzzled. What are your thoughts please.

  • @tigertooth4678

    @tigertooth4678

    2 жыл бұрын

    My guess is you need a Type 1 then, have a look at JW on his KZread channel - SPD part 3.

  • @serkansoylemez6685
    @serkansoylemez66854 жыл бұрын

    Install the SpD enclosure right next to the DB and use bush and locknut . All good

  • @cengiz246
    @cengiz2463 жыл бұрын

    How do you work out the size of the mcb feeding the spd? I have a 63amp and 100amp 3 phase db that needs a spd

  • @aawcy
    @aawcy2 жыл бұрын

    there was two earth terminal at SPD. Do we need to connect to both PE & E at the same time?

  • @OldFloatingSeaman
    @OldFloatingSeaman4 жыл бұрын

    4.5 Nm seems really excessive. Great Video especially on the relevant reg.

  • @markgilder9990

    @markgilder9990

    3 жыл бұрын

    Nobby Hall on some of then cheaper components they would most likely shatter.😂

  • @jam99
    @jam993 жыл бұрын

    9-slot DB reduced to 5-slots available. How about next week's regulations? Another two slots gone so another DB replacement. Those wires must be getting a bit work hardened by now with all the DB replacements... so let's rewire. Best just to ban electricity altogether. I mean, come on, it can kill! That's my risk assessment done.

  • @callimero2409
    @callimero24094 жыл бұрын

    could you maybe do a video abot SPD in TT system.. i would like to know more about it..as it is completely diffrent story on TNCS and TT many thanks

  • @stephenhurrell2773
    @stephenhurrell27736 ай бұрын

    Hello If you install a new ring main circuit does it have to have a surge device installed or can the customer refuse

  • @joopterwijn
    @joopterwijn2 жыл бұрын

    Question: Do I understand it correctly that spd has it own 15amp( b-curve?) “fuse”, in that case the cable length of the fase bare through the “fuse” need to be added to the total length (correct?)……

  • @ajaybalu5302
    @ajaybalu53023 жыл бұрын

    Hi there, quick question please. I’m looking to purchase a Proteus 100A DP Electricity Meter Isolator Switch with T2 Surge Protection for my house. Does the regulation still apply in regards to the tails being 0.5mtr-1mtr for this device as is an isolator switch and SPD combined?

  • @devlinmaguire8074
    @devlinmaguire80745 жыл бұрын

    If after a risk assessment it is decided a SPD is required and considering it would then be assumed that a TOV would occur then given that these are single use components it would therefore follow that the installer would likely be required to have on hand a replacement so it is highly likely that the cost would need to include said spare, and in the event of a TOV occuring post install a further SPD would need to be obtained ad infinitum, run that past joe public and I know what the result will be, personally if TOV,s are likely then it should be down to the DNO to provide protection to their customers and if that were indeed a requirement this whole issue would vanish without trace

  • @mowcius

    @mowcius

    5 жыл бұрын

    I think for that SPD you'd also need a risk assessment to cover the poor sod tightening the terminals up!

  • @seanpassant3174

    @seanpassant3174

    3 жыл бұрын

    They are NOT single use components. SPD's are tested to BSEN 61643-1 and this requires them to be tested with a minimum of 20 transient events and still be operational. A good quality, well installed SPD should last in excess of 15 years.

  • @clivejohnson6468

    @clivejohnson6468

    2 жыл бұрын

    They are not single use devices. But, they can degrade in a surge prone environment, hence the flag indicator window on the cartridge tells you if that has happened. Then, change the cartridge only.

  • @edmondhodaj5817
    @edmondhodaj5817 Жыл бұрын

    Could used bushes, that looks like one of my pj

  • @anelectrician
    @anelectrician Жыл бұрын

    If the torque screw driver manufacturers made the screw driver handle a T-bar type it would help the user terminate high torque settings.

  • @navarajmishra9772
    @navarajmishra97724 жыл бұрын

    how to specify the proper rating of SPD type one like maximum continuous operating voltage ,nominal discharge current and voltage protection level (Up) for the three phase four wire system (230/400) with TT earthing system ?

  • @andrew7440
    @andrew7440 Жыл бұрын

    It doesn't actually have to look good, it just needs to function properly! I'd argue that for such a short run between enclosures, there's not much need to leave masses of slack as the wire could be easily replaced if it ever needed to so.

  • @ashmanelectricalservices4318
    @ashmanelectricalservices43184 жыл бұрын

    When IR testing a consumer unit with integrated SPD, do you have to disconnect the SPD when applying 500 VDC?

  • @GSHElectrical

    @GSHElectrical

    4 жыл бұрын

    Hi, you sure do look at the section on IR testing in the On-Site Guide 👍

  • @ijazmasood27
    @ijazmasood2711 ай бұрын

    Dear sir u used spd near the main circuit breaker sum time hi surge in come spd spd is damag then all mcbs is damages ??????

  • @achrist1520
    @achrist15205 жыл бұрын

    Hey I'm from the UK and Im interested in an apprenaship in the USA. I was wondering if I could hrt your opinions on my situation. And what you might suggest

  • @tommytar222
    @tommytar2222 жыл бұрын

    think you could check that hight tourque setting

  • @philcross6037
    @philcross6037 Жыл бұрын

    At 3:46 you measure the length of earth, isn't that arbitrary as there is a length of wire from the earth bar to the Main fuse then to the neutral.....etc. I'm not sure what the 500mm is for and what is the effect of a longer path. Is it just the common earth point of the other circuits?

  • @leeward5576
    @leeward55765 жыл бұрын

    So are SPD’s required in a domestic dwelling? Or should we ask the IET?

  • @luismorelli3943
    @luismorelli39435 жыл бұрын

    👍🏼👍🏼👍🏼

  • @luckyal3963
    @luckyal39634 жыл бұрын

    so on a hager board with opre fitted spd the earth of the spd is pre wired and connected to the earth bar but the other terminal p/e is empty ???

  • @GSHElectrical

    @GSHElectrical

    4 жыл бұрын

    Hager 18th Edition Consumer Unit With Built in SPD, A Type 100 amp RCD’s to Comply With BS7671 kzread.info/dash/bejne/Z4Opy9SJe9K_YMY.html This might help. Thanks Gaz 👍

  • @markgilder9990
    @markgilder99903 жыл бұрын

    If I notice the customer has a high end computer like an Apple 27” I would recommend an spd on that alone.

  • @Vikingza
    @Vikingza4 жыл бұрын

    Why didn't you just mount the SPD box against the main DB and then use a bushing to mechanically join the boxes, you can then push your cables through the bushings. Easy as pie

  • @DerekHundik

    @DerekHundik

    4 жыл бұрын

    i wonder why you need this device anyway. It doesnt work . None of the youtube videos show how the unit actually works.

  • @Nyle95
    @Nyle952 жыл бұрын

    How much would it cost to have an SPD installed?

  • @dsbelectricaldavidbetterid8448
    @dsbelectricaldavidbetterid84485 жыл бұрын

    can you install a spd from an rcd supply i never thought you could the reason being the let thro current it trip before the spd see the transient a type ac or a does not offer 3ka/20micro seconds current wave a type akv,f,b,ev will tho

  • @GSHElectrical

    @GSHElectrical

    5 жыл бұрын

    I got sent this message today on LinkedIn Hi Gaz, I managed to speak to Ian today from surge, very helpful gentleman and he helped me expand the knowledge about the earth leakage through SPD. The earth leakage through the SPD durring fault will only be present for no longer the 25 nano seconds therefor considerably quicker than the operation time of the RCDs. This said he mentioned that as the devices get older and worn the during of the earth leakage CAN get longer, therefor potentially cause an upstream RCD issue.

  • @dsbelectricaldavidbetterid8448

    @dsbelectricaldavidbetterid8448

    5 жыл бұрын

    @@GSHElectrical thank you for your quick reply i have done a fair bit of re search into this and have some data that reflects the use of ac or a types being used and them triping before the transient gets to the spd (type 1 especially) my idea would be to have it on a mcb most i fitted so far require a 32 a cct good debate i do like a debate, also whilst i got you can you do a bit of a vid with dses electrical about spds and over head lines lol guys real funny

  • @andrew7440

    @andrew7440

    Жыл бұрын

    If you have dual RCD supply and, the RCD supplying the SPD is switched off at the time of the over voltage, SPD won't work anyway.

  • @grumpygit447
    @grumpygit4473 жыл бұрын

    Wonder how many heads will be destroyed at that torque

  • @Weaselspleen75
    @Weaselspleen754 жыл бұрын

    Maybe I’m missing something here but Wondering why spds on anything other than on tt systems do we need both line and neutral protection. In tncs and tns the neutral and earth are connected before entering the Cu. Some spds take up two modules in the cu where space is often precious . I’m thinking connecting the spd to neutral is basically already done. Thoughts please

  • @Weaselspleen75

    @Weaselspleen75

    4 жыл бұрын

    My point is Surely an spd device is only required on the line as the neutral is already grounded. Unless it’s on a TT supply

  • @MrKarlPrince

    @MrKarlPrince

    3 жыл бұрын

    TNS connections are not bonded together within a short distance of the installation, there is plenty of length of conductor (with inductance at high frequency) on which the voltage spike can be present

  • @supersparks9466
    @supersparks94665 жыл бұрын

    Bloody hell, these spds have opened a can of worms,I’m not going to bother until they are incorporated as standard, hopefully I’ll be off the tools by then.

  • @vievlogs589
    @vievlogs5894 жыл бұрын

    👍🌟🌟🌟🌟🌟

  • @davidmanning5874
    @davidmanning58745 жыл бұрын

    AM I OVER CAUTIOUS AS I HAVE 16 AMP IN MY SHED COME WORKSHOP AND HAVE ALWAYS USED 4MM CABLE AM I OVER DOING IT?

  • @mowcius

    @mowcius

    5 жыл бұрын

    If you're a quaified electrician, you should know the answer to that question! If you're not, you probably shouldn't be doing the work yourself. It's very likely that you're overdoing it with 4mm2 cable, but there are a lot of factors to consider which could require de-rating of the cable and *could* get you to a 16A figure on that 4mm.

  • @jamesaddis8726

    @jamesaddis8726

    4 жыл бұрын

    4mm2 is fine if limited to 20A if you want more power then 6mm2 on a 32A RCBO

  • @Zelahb2930
    @Zelahb2930 Жыл бұрын

    Should have used couplers to combine both enclosures, looks pant's using stuffers

  • @GSHElectrical

    @GSHElectrical

    Жыл бұрын

    It’s probably what we had to hand at college that day 👍🏻

  • @protectiongeek
    @protectiongeek2 жыл бұрын

    Can't help but think that the easiest way to compare the installed wiring to a 500mm or 1000mm length of conductor would've been to actually offer-up a 500mm or 1000mm length of the same conductor to the installation. Maybe it's just me but seeing metal tapes anywhere near electrical equipment - even equipment that's not-live - is a no-no!

  • @MM2009
    @MM2009 Жыл бұрын

    Why braker to spd? It doesn't carry any current..

  • @Bodragon
    @Bodragon4 жыл бұрын

    I always thought they were called *_consumer units_* rather than *_consumer's units._* Can they *_really_* be called *_either ?_* Please clarify, thanks. >

  • @GSHElectrical

    @GSHElectrical

    4 жыл бұрын

    Consumer Units

  • @namzy410
    @namzy410 Жыл бұрын

    Should have reduced the earth distance by installing a terminal block in the remote box

  • @andrewwise5277
    @andrewwise52775 жыл бұрын

    Why is it not good practice to clip it to the din rail inside the main DB, Surely that’s a better practice than exceeding the maximum length of run.

  • @shilks8773
    @shilks87735 жыл бұрын

    The torque screwdriver effort is "All in the wrist action" - Just like the game "Battling Tops" from the '70's. kzread.info/dash/bejne/n4t62dx9esTLe9o.html

  • @shilks8773
    @shilks87735 жыл бұрын

    Gaz - Heading miss spelt. "How to Fit a Type 2 SPD Remote form the Consumer Unit" - Should be FROM not form. Cheers.

  • @GSHElectrical

    @GSHElectrical

    5 жыл бұрын

    Sorted 👍 thanks Gaz

  • @mdabul7130
    @mdabul7130 Жыл бұрын

    May

  • @Stabby666
    @Stabby6664 жыл бұрын

    Why the hell does it need to be so tight? It's not like there's any weight or tension on those units. Seems ridiculous!

  • @grumpygit447
    @grumpygit4473 жыл бұрын

    He hasn’t answered the question do we need an sod in a normal household

  • @GSHElectrical

    @GSHElectrical

    3 жыл бұрын

    Why is my electrician suggesting we have a surge protection device fitted? kzread.info/dash/bejne/fmZtz8l-p5OYfrw.html

  • @mdabul7130
    @mdabul7130 Жыл бұрын

    May Eceltical pattycall

  • @dmcolemanmarc647
    @dmcolemanmarc647 Жыл бұрын

    There can't be possibly any good reason the conductors have to be so short other than pushing people into have a board change with an integrated device.

  • @lifter98
    @lifter982 жыл бұрын

    Does anybody really have a clue about these SPD's? It's seems to be mass confusion all round, and hardly any information.. Upstream or down stream of the mcbs, rcds..? One module or two?.. Different for TT/TNCS?.. How the efffing things actually work..? Different types of spd?.... Remotely or in the board?.. but no spare ways? Perhaps some decent wiring diagrams might help, but there aren't many about..

  • @GSHElectrical

    @GSHElectrical

    2 жыл бұрын

    www.efixx.co.uk/Know%20How/BS7671SPD Free CPD on SPD’s 👍🏻