Generac Generator Not Testing! See Why

Ойын-сауық

I ran a service call for this Generac generator a year earlier for issues involving it not starting. Last time it was battery issues and mice, this time it's something else. My videos are made for people in the field not for the homeowners. If you have problems, please call your authorized Generac generator dealer. Be sure to see my video on how to service your generator and how to choose a dealer that is going to have the ability to do your work above and beyond what you're looking for.
- Purchase your tools at www.trutechtools.com/?AffId=13 and use the offer code SURVIVAL to save 8% on your total purchase (exclusions may apply) -
- TOOLS I USE -
FULL LIST ON THIS PAGE - kit.co/hvacrsurvival
💥 Amazon Store: www.amazon.com/ref=as_li_ss_t...
SHORT LIST IS BELOW
Ideal Industries Inc 34-001 - Fuse Puller - amzn.to/3sjaCB7
RIDGID 31305 Model E-110 9.5" Offset Hex Jaw Pipe Wrench - amzn.to/3Bar08y
Klein Tools Ratcheting Box Wrench 1/4 x 5/16 amzn.to/3GOpBrG
KNIPEX Tools - 10" Pliers Wrench amzn.to/3U7RRJf
KNIPEX Tools - 10" Cobra Water Pump Pliers amzn.to/3Wje8Wn
Knipex Tools - Mini Pliers in Belt Pouch amzn.to/3WguyyH
KNIPEX Tools - 4" Cobra XS Water Pump Pliers amzn.to/3UaQiKA
Bahco -6" Wide Mouth Adjustable Wrench amzn.to/3sHIsMV
Bahco - 8" Big-Mouth Adjustable Wrench with Rubber Handle - amzn.to/3SPhDB7
Knipex - 9.5-Inch Ultra-High Leverage Lineman's Pliers amzn.to/3DTLJ2h
Klein Tools Diagonal Cutting Pliers with Angled Head - amzn.to/3zuBVJb
Klein Tools Stripper, Crimper Tool - amzn.to/3gQQ6Su
Klein Tools Wire Cutter and Wire Stripper - amzn.to/3Fs627W
Klein Tools Kurve Wire Cutters, Heavy Duty Wire Stripping Tool - amzn.to/3FseIuW
Klein Tools Heavy Duty Automatic Wire Stripper - amzn.to/3SQdZab
Klein Tools Crimping and Cutting Tool - amzn.to/3TPIgXU
Klein Tools Screwdriver Adjustable 4 to 8-Inch amzn.to/3Nl6KWz
IDEAL INDUSTRIES Digital Circuit Breaker Finder - amzn.to/3DoBFwm
Fluke 376FC AC/DC Clamp Meter with iFlex - amzn.to/3UaNyx2
Fluke 62 Max Industrial Infrared Thermometer - amzn.to/3SNdwWg
Fluke 902 FC HVAC True-RMS Clamp Meter - amzn.to/3Ws7OfB
Fluke 87V MAX - amzn.to/3U6Rlv9
Fluke Networks Pro3000 Tone Generator - amzn.to/3WedklG
Fluke - FLUKE-52 Dual Input Digital Thermometer amzn.to/3zwFdf1
Ideal Safe-T-Grip Fuse Puller - amzn.to/3zsw2w4
Klein Tools Canvas Zipper Bag - amzn.to/3WgnJxq
Uni-Paint PX-20 Oil-Based Paint Marker - amzn.to/3sE3R9T
5 Gallon Bucket Topper and Organizer - amzn.to/3sGi2Ll
Stabila Magnetic Pocket Level PRO with Holster - amzn.to/3FtYLo0
Clip & Carry Kydex Multitool Sheath for LEATHERMAN SURGE - amzn.to/3TPJfHA
Kydex Multitool Sheath for LEATHERMAN WAVE & WAVE + PLUS - amzn.to/3sJlhlg
Cooper Atkins Thermistor Thermometer - amzn.to/3DLeHkC
GEARWRENCH Internal/External Ratcheting Puller 7 Ton 2 or 3 Jaw - amzn.to/3FxTU5l
- CONTACT INFO -
hvacrsurvival@gmail.com
- FOLLOW ME -
Instagram - / hvacrsurvival
Facebook - / hvacrsurvival
Warning Notice Disclaimer - Video content listed on the channel HVAC*R Survival is for entertainment purposes only and not meant to be a substitute for not contacting a competent HVAC/R PROFESSIONAL. Do not attempt anything said or seen on my videos, The tasks that are shown are dangerous and deadly without proper training.
This page contains affiliate links, which means that if you click on the link and make a purchase, I’ll receive a small commission. HVAC/R Survival is a participant in the Trutechtools, Amazon Services Associates Program.
#hvacrsurvival #hvaclife #hvacservice #hvacr #refrigeration #troubleshooting

Пікірлер: 69

  • @bradmironik6137
    @bradmironik613711 ай бұрын

    Every time you have one of these generator videos, I am glad i don't own one. Thanks for sharing the HF tool. I will check it out.

  • @peterking1134
    @peterking113411 ай бұрын

    Miss these gen vids!!

  • @nathanhurst5155
    @nathanhurst515511 ай бұрын

    The genny vijayos are for some odd reason, some of my favorites that you do. 👍

  • @johnwalker890
    @johnwalker89011 ай бұрын

    Good job Rick, They should, the manufacturer, should make some kind of shrink tube or insulation to cover the grounded conductor, so it doesn't come in contact with any other circuits, or the installer or customer, it just doesn't look safe, with raw wire sticking out, I know a person could tape it, but it would look a lot better with it insulated or safer.

  • @HVACRSurvival

    @HVACRSurvival

    11 ай бұрын

    I agree, that's kind of why I unhooked the ground before I pulled it out. The new generators have a side panel that comes off. All these old generators I keep showing are all problematic but they have made improvements since then.

  • @johnwalker890

    @johnwalker890

    11 ай бұрын

    You're right, I've seen those new panels, but haven't installed them yet.

  • @nspro931

    @nspro931

    5 ай бұрын

    @@HVACRSurvival That has been the mantra with Generac as long as I have been in the business, "They are not as bad as they used to be!" Heard it for decades now.

  • @danpresson
    @danpresson11 ай бұрын

    Awesome video always look forward to your video

  • @HVACRSurvival

    @HVACRSurvival

    11 ай бұрын

    🙏👍👍🤜🤛

  • @frankspliff7037
    @frankspliff703711 ай бұрын

    I like the veto bag

  • @FPHA697
    @FPHA69711 ай бұрын

    Good informative video.

  • @sheepdog3828
    @sheepdog38282 ай бұрын

    Oh BTW, place a few ear tags in there to keep critters out or to a minimum!

  • @InsanePacoTaco
    @InsanePacoTaco11 ай бұрын

    Dude on the tractor was like "I have a need for speed!"

  • @HVACRSurvival

    @HVACRSurvival

    11 ай бұрын

    🤣👍👍

  • @fshn76
    @fshn7611 ай бұрын

    Great video as always Rick! Glad I don’t work on generators.

  • @dougking7592
    @dougking759211 ай бұрын

    Hay brother generator work is not as simple has you make seem, lately I have had a few gensets that have overcrank due to not getting fuel bad regulators and air pockets in gas lines for some odd reasons, and couple controllers nice video brother

  • @HVACRSurvival

    @HVACRSurvival

    11 ай бұрын

    No it's not that easy, it'd be nice if I did them everyday, most of this I'm going off memory. I hardly work on these things anymore. I had a lot of issues in the beginning of learning three because it wasn't the greatest training. I hate reading a book trying to figure things out.

  • @fernandogonzalez6617
    @fernandogonzalez66176 ай бұрын

    Nice video info. How you did that took fuse out main breaker on ats still in on position and generator transfers power to home. How is that never seen that?

  • @HVACRSurvival

    @HVACRSurvival

    6 ай бұрын

    Because it’s likely not the safest thing to do.

  • @Enitii
    @Enitii11 ай бұрын

    I didn't know there was a commercial at the beginning because I use KZread premium

  • @HVACRSurvival

    @HVACRSurvival

    11 ай бұрын

    Me too 😃👍👍

  • @joeshearer1247

    @joeshearer1247

    11 ай бұрын

    @@HVACRSurvival me three

  • @jeffsignore7953
    @jeffsignore795311 ай бұрын

    Hey Rick. What type of fuse holder is that? Looks like it grips perfectly on those fuses. The one I have is to loose. Thanks!

  • @HVACRSurvival

    @HVACRSurvival

    11 ай бұрын

    I posted a link in the description.

  • @Minitrucker231
    @Minitrucker23111 ай бұрын

    Just a random tractor hauling ass in the middle of a job 😂 Gotta love it!

  • @HVACRSurvival

    @HVACRSurvival

    11 ай бұрын

    That's my side of the county where I grew up 🤣👍👍

  • @craiggcrefrigeration8537
    @craiggcrefrigeration853711 ай бұрын

    Great video Rick, I must ask why is there a need for a generator for a home where you are? Just interesting as we only use them for back up power in the UK. My guess is seasonal extra power for the A/C etc.

  • @HVACRSurvival

    @HVACRSurvival

    11 ай бұрын

    For when the power goes out. ? If you're in the country you don't have heat, water, etc

  • @joeyf504327

    @joeyf504327

    11 ай бұрын

    back-up generators, are used for back-up. No to run the a/c in the summer. Standard house service in the US is 200A 240V or 48kW. Most back-up generators are under 20kW.

  • @craiggcrefrigeration8537

    @craiggcrefrigeration8537

    11 ай бұрын

    Ah thanks guys, makes sense, just don’t see any on domestic properties over here. Usually just light some candles and suffer 😂

  • @comp20B

    @comp20B

    11 ай бұрын

    ​@@craiggcrefrigeration8537For work from home and for refrigerators. We went 7 days one year after a snow storm.

  • @sandy1653

    @sandy1653

    7 ай бұрын

    @@craiggcrefrigeration8537 Candles and suffering are all well and good, but when it's 90f (32c) and 80% humidity, and there's no hope of power for 2+ weeks, you'll be glad you've a backup generator.

  • @sheepdog3828
    @sheepdog38282 ай бұрын

    No matter what make, of a genset, TLC is a must. But common sense is not so common.

  • @harrydickson4575
    @harrydickson457511 ай бұрын

    👍👍👍

  • @robertconville6269
    @robertconville62696 ай бұрын

    Does not look like the owner ever does any up keep on the unit! I open mine at least once a month to clean and look around!

  • @countryside8122
    @countryside812211 ай бұрын

    It's not surprising, the way Generac treats it's employes, The people see problems and bring it to the attention of leads and they ignore the problem. I worked there for awhile.

  • @HVACRSurvival

    @HVACRSurvival

    11 ай бұрын

    Awesome, thanks for sharing! Feel free to vent😃👍👍

  • @deepsleep7822

    @deepsleep7822

    6 ай бұрын

    Always boils down to money.

  • @gtpforever
    @gtpforever11 ай бұрын

    The three LEDs on a generac generator are simple and they're listed like this as a caveman...... Green= good Yellow= good-maintenance Red= bad

  • @gtpforever

    @gtpforever

    11 ай бұрын

    There's also a dealer code to get into it further if you need it.

  • @gtpforever

    @gtpforever

    11 ай бұрын

    Shut down was normal. The squeakiness is a read valve inside the valve covers or as generac calls them the head. It always makes a squeaky noise when they shut down.

  • @gtpforever

    @gtpforever

    11 ай бұрын

    Also everyone be very careful with any of the micro-spades when plugging them in on the micro switches because the micro switches are brittle. Lol

  • @kcMan7938
    @kcMan79385 ай бұрын

    That tractor was crusin at WOT !!!

  • @BOB12349307
    @BOB1234930710 күн бұрын

    highly abused best generators ever made!!

  • @btomas225
    @btomas2255 ай бұрын

    6:47- Diode drop.....

  • @HVACRSurvival

    @HVACRSurvival

    5 ай бұрын

    Usually that’s a half volt drop

  • @KgiMedia601
    @KgiMedia60111 ай бұрын

    Dude im over wrenching these things, there so annoying to deal with at this point 😂

  • @HVACRSurvival

    @HVACRSurvival

    11 ай бұрын

    I feel exactly the same way, why do you think I'm so negative in the generator videos. I asked the office to get someone else trained and it still hasn't happened.

  • @CM-ou4zr

    @CM-ou4zr

    11 ай бұрын

    @@HVACRSurvival how do you get certified to work on these? I remember you talking about a generac class. Curious because I do HVAC for a big college and we have a million of these things and hate subbing out the work. What steps would you recommend to actually get good at them? I have the manual for every different one on campus and will read front to back and can play with the ones that are on buildings not being used.

  • @KgiMedia601

    @KgiMedia601

    11 ай бұрын

    @@CM-ou4zryour employer will pay for it and set it up(atleast thats how it was for me) and then you take these pre reqs online which are like presentations then a quiz at the end, then theyll setup a school date at a certified dealer where youll go for 2 days get a manual for the generator ie aircooled, liquid cooled etc and youll fix problems the teacher sets up. Theyll also teach u how to use genserve and give you a tech id for warranty repair type stuff

  • @OverKillPlusOne
    @OverKillPlusOne5 ай бұрын

    Bet that controller has a coin cell for the clock that’s failed.

  • @OverKillPlusOne

    @OverKillPlusOne

    5 ай бұрын

    Whether or not that’s serviceable is a whole different question.

  • @AD17709
    @AD1770911 ай бұрын

    That thing needs a wipe down.

  • @joehead1294
    @joehead129411 ай бұрын

    Mighty grimy battery for only a year. 🤨

  • @HVACRSurvival

    @HVACRSurvival

    11 ай бұрын

    The whole generator was grimy. I can't believe the lady wasn't out there with her sweeper and Windex keeping it clean 😃

  • @BOB12349307
    @BOB1234930710 күн бұрын

    let me guess you charge like $500.00 for the $50.00 module?

  • @HVACRSurvival

    @HVACRSurvival

    10 күн бұрын

    Our cost on that module I think is somewhere around 400 bucks so it probably did sell for 500. If you can get it for $50 I’ll take 10 of those and for the comment down below about being the best generator built🤣🤣 Well, just look at all the other videos I’ve done on these…. The 2006 through 2014 generators were total shit. Generac no longer lets you go through the assembly plant because you’ll see how poorly they’re thrown together. I’ve had motors go bad in less than five hours. I’ve had bad coils, bad modules, bad regulators. I’ve had them blew everything up in the house because the voltage regular went bad. Everyone entitled their opinion but not their own facts.

  • @Eddy63
    @Eddy6311 ай бұрын

    I hate a generator you can't trust Thx

  • @HVACRSurvival

    @HVACRSurvival

    11 ай бұрын

    🤣👍👍

  • @BrianD-ds4dx

    @BrianD-ds4dx

    8 ай бұрын

    Then don’t buy a Generac! Simple solution! Generac’s focus is on marketing, not engineering. Their market share is dependent entirely on marketing volume not reliability. I’m in the generator business and rank as follows for air cooled units: 1) Cummins 2) Briggs and Stratton 3) Kohler 4) A guy on a bike like the WWII movies pedaling to make power 5) Literally anything other than a Generac The bottom of the list is a joke obviously but the top is not. We don’t do Champion in Texas due to their small size and our rather large AC inrush. Also for anyone watching this video out here please be aware that a lot of your generator run issues can be tied to a poor install. Just yesterday we went behind electrician originally only for the purpose of doing the low-voltage and the start up and commissioning of the Cummins unit the customer installed. Upon further inspection, the electrician had used the meter as a raceway and had also installed the ATS within three feet of the gas regulator, which is a big no no due to fire code. Good thorough video I especially like the discussion of the functional limitations of the air cooled unit here

  • @nspro931

    @nspro931

    5 ай бұрын

    @@BrianD-ds4dx Cummins are all Chinese air cooled now, had 3 fail this year out of a not very large population. Breaks and Scrappem build quality do not inspire confidence, their new stuff is all different than their old stuff which was really bad. Kohler is the only one with a heritage and actually a support system that helps when we call.

  • @BrianD-ds4dx

    @BrianD-ds4dx

    5 ай бұрын

    @@nspro931 I’m going to 100 percent disagree with you on the Cummins air cooled being made in China. I only know this because I had to dig real deep within company contacts to find out where they come from. You are on the right continent but a little far north. What area you installing in, out of curiosity? Not completely opposed to Kohler but I dislike the controller on them, and, like the Generac I find them loud AF

  • @BrianD-ds4dx

    @BrianD-ds4dx

    5 ай бұрын

    @@nspro931 oh and from a managed load perspective….Briggs load management design and the synchrony switch are so much better than Kohler and Generac. Cummins could be just as good but you have to hardwire that sh** in which makes it a way bigger pain installing than the Briggs load management devices