Fix / repair Worcester bosch primary heat exchanger / heat cell problems and servicing

A quick look at what goes wrong with the Worcester heat cell

Пікірлер: 20

  • @buxvan
    @buxvan4 жыл бұрын

    Good video, when I service these, if I'm not changing the burner seal & the flue is gettable attable , I use the customers watering can & give the h\ex a wash through the flue terminal.

  • @Newpark7
    @Newpark79 жыл бұрын

    Hi Sebastian I would second all of that. Great videos. Thanks

  • @VenomousBolt
    @VenomousBolt5 жыл бұрын

    Hi. If you put water in the flue sample point it’s only going to run straight into the siphon or partially clean out the very bottom of the sump. Best option is to pour your water into the top of the heat exchange or even better pour your sentinel into there if you’re getting sulphate blockage issues.

  • @funksoulbrother3620
    @funksoulbrother36203 жыл бұрын

    Good video. question for you: if you're having problems with a blocked outlet (the top outlet as you pointed out), how tdo you get the cleaner in the the heat exchanger to help clear the blockage? cheers

  • @marktree6400
    @marktree64006 жыл бұрын

    I take it you’d have to drain the entire central heating system down after using the cleaner? Would t not be quicker just to manually clean the cell? Great video BTW

  • @MichaelCassidyHeatin
    @MichaelCassidyHeatin8 жыл бұрын

    Nice video. Subbed.

  • @carlmoore6181

    @carlmoore6181

    5 жыл бұрын

    Michael Cassidy shacking what a clown this guy don’t know shit

  • @woodbine66
    @woodbine669 жыл бұрын

    Great vid - many thanks. Can you please do one on how to clean rust particles from a combi plate heat exchanger? Mine blocked up, so I put a new one, but want to clean the old one to keep for a spare. No other vids on KZread showing cleaning plate hexs. Thanks

  • @plumbteam

    @plumbteam

    9 жыл бұрын

    Got a scaled one today - will do video tomorrow - I've got a great trick using drain acid to clean it.

  • @woodbine66

    @woodbine66

    9 жыл бұрын

    Sebastian Hibbert Many thanks Sebastian. I think there will be some demand for cleaning plate hex's, as there's no info out on the web how to do it nor anything on KZread. It's quite a common problem having plates choked with rust from dirty old systems, and requests for info comes up quite a lot on forums. As you undoubtably know, plates are expensive. The Vaillant one for my Turbomax retails at over £100, but luckily I got an old stock genuine new one on Ebay for a tenner. Would be great to know how to properly clean them to restore performance. Also, any non-gas boiler repairs would have good demand, eg. div. valves, ex. vessels, NTCs, etc. Very little out there in Tubeland. Thanks again, and please keep the great vids coming. Ian

  • @rajpopat3384
    @rajpopat33842 жыл бұрын

    I can see ribs are visible and we need to change this ASAP can you help please

  • @Hamedfunnyboy
    @Hamedfunnyboy7 жыл бұрын

    can you tell me what type of heat exchanger this is?

  • @rayc1503

    @rayc1503

    4 жыл бұрын

    It's a primary heat cell( kebab heat exchanger) water within the central heating circuit is heated for either the CH or is sent to the plate to plate heat exchanger. There heat transfers to the incoming cold water via a different piping circuit to give you hot water.

  • @keitholiver7599
    @keitholiver75998 жыл бұрын

    my boiler seems to be building up way to much pressure when heating is on and then looses all its pressure after a day or two anybody any ideas

  • @londontrada

    @londontrada

    7 жыл бұрын

    Expansion vessel

  • @Bnabarro1989
    @Bnabarro19896 жыл бұрын

    I take it the white powder building up is aluminium oxide? Hence why certain boiler makes and models avoid aluminium and stick too stainless steel. Shame Worcester don't make videos like for this for all there installers. Would make sense all they would have too do i get people too register or make account using there gas safe number. Would stop people have too post videos on KZread for all the chances too see and think they can have a go them selfs.

  • @gaz7060
    @gaz70606 жыл бұрын

    I'm aware this video is old but I have to say... you run water through the flue sampling point? Well that will run down the silencer and out the sump. I agree taking the burner off and and running water through them is a great idea but just not through there.

  • @plumbteam

    @plumbteam

    6 жыл бұрын

    gaz7060 your correct - screwed that point up !

  • @dariusEMPEROR
    @dariusEMPEROR4 жыл бұрын

    1:49 3:00 :))))

  • @Moocow9991703
    @Moocow99917033 жыл бұрын

    Worcester aluminium 💩