Fire Pump and Jockey Pump explained (Low Zone) Part 1 || (Tagalog) Fire Protection System
What is the difference between a jockey pump and a fire pump?
What does a fire pump do?
What is the difference between a fire pump and jockey pump?
Part 2
• Fire Pump and Jockey P...
I really appreciate all the support from you Guys and thank you so much for watching this video. For more quality tutorials, don't forget to LIKE 👍 and SUBSCRIBE this channel.
#firepump
#jockeypump
#handyengineer
#electricalengineer
How to avail the Free Service Repair and Tutorial? Send me a DM thru the link below;
HandyEnginee...
Thank you very much!! 😊😊
Пікірлер: 134
7:05 alarm check valve to sir...non return valve to pero hindi niya main role ang pag prevent ng flow ng firewater pabalik sa reservoir...ito ang mag trigger ng fire alarm mo once tumaas ang flow sa system side ng fire pro mo...at pansin ko reverse un flow direction ng arrow nyo...
salamat may natutunan po ako sa actual ng video nyo.sa step by step
@Art_2000_HandyEngineer
2 жыл бұрын
Welcome po!! 😊😊😊 Thank you din po sa panunuod. 😊
Ayos idol
7:52 FDC to sir... normally may kasunod na check valve ang FDC kaya pwede na wala ka ng isolation valve... Kung required ng AHJ na may iso valve ka like sa system mo...dapat normally open siya at may tamper switch...
Amg linaw magpaliwanag..keep it up sir...
@Art_2000_HandyEngineer
Жыл бұрын
Thank you Sir!!! 😁😁
@macoytv9768
Жыл бұрын
@@Art_2000_HandyEngineer pahabol sir..baka pwede ka mag gawa or mag explain naman rrgarding po sa feedmain ..ung may butterfly valve..flow switch pati po ung system ng auxiliary drain nya..salamat.
@Art_2000_HandyEngineer
Жыл бұрын
@@macoytv9768yun lang sir 😅 ng resign na po kasi ako sa property na yan. Ibang work/company na po ako now. 😅 PM nyo po ako sa page ko sir. Dun ko nalang po subukan eh explain po or sagutin ang mga tanung niyo po. Thank you!
@macoytv9768
Жыл бұрын
@@Art_2000_HandyEngineer un lang..ano pong page nyu sir?.9 years napo ako sa plumbing an firepro..autocad operator..pero medjo nagguluhan pa po ako sa system nyan.dahil after shopdrawings ko nililipat ako ng project so hindi ko ho nakkita na gumagana or tinetesting man lang.
@Art_2000_HandyEngineer
Жыл бұрын
@@macoytv9768 nasa description po sir 😊😊 maganda ung work nyo sir. Ayos yan. 😊
thank you
@Art_2000_HandyEngineer
11 ай бұрын
Welcome po 😅 kahit di na po ako active dito.. 😅sorry po 😓
Nice lods!
@Art_2000_HandyEngineer
19 күн бұрын
Thank you so much po 😊 kahit magulo ung video 😅😅
Dapat po may valve para incase ng maintenance po sa Pressure Relief Valve ,sure to it dapat normally open sya po.
@Art_2000_HandyEngineer
9 ай бұрын
thanks po sa comment nyo Sir!!
Hi Sir, new subscriber here salamat sa tutorial video mo, sana madalaw mo rin ako sa aking tyanel salamat po
Sir pwidi mag tanong? May alam ka po bang makuhaan ng fire pump infiller ng Y-20 na fire pump
hello sir, ang standing pressure reading ba ng jockey pump and main pump sa panel screen dapat the same? Sa video mo nakalagay sa jockey pump, yung stanby pressure nya ay nasa 169psi, sa main pump kasi hindi napa kita kaya I asked. :) thank you sir Engineer!
buti nakita ko video mo sir, thanks sa info. pwede bang itanong pano mag program para sa setting nang pressure sa fire pump panel , same po kase springkler system natin sir. plano ko kase bagohin ang pressure ? salamat and more videos
@Art_2000_HandyEngineer
Жыл бұрын
Bakit gusto nyo baguhin sir? Hindi po kasi basta basta ung pg change ng pressure. Dapat approved din po muna ng Designer or Contractor. Para pg naka problema, hindi kayo ung magiging liable..
@jeremycorod2861
Жыл бұрын
@@Art_2000_HandyEngineer - approve nman po sir, bago na kase ang designed pressure .Wala na kami sa standard kaya pinapa adjust po .
Goodpm. Sir ask ko po saan naka connect ung piping ng mga panel para sa jockey at fire pump. Ung maliliit na pipe ba?
Ang suction pressure at discharge pressure po ba ay equal lng sir?
Pagmag drain sa isang palapag,kunyari 20th flr. Ano yung gagalawin sa pump room taz tapos na ang pag install ng droppings,ano naman ang gagalawin sa pump room pagmagkakarga na nang tubig sa 20th flr.
Boss, ilan hp ulit yun fire and jockey?salamat po
Bose ask q lng poh pano gumawa ng chart s fire pump. Pra poh s daily monitoring . S cut off at cut in n jockey pump.
Mabuti na lng bossing yung fire pump system nyo na approved! Kasi na observed ko parang walang diesel engine fire pump🤔 kasi incase of sunug at nawalan na ng electrical power supply ubus ang building🙈
@Art_2000_HandyEngineer
19 күн бұрын
Ayun po sa code po mismo. Approved naman po kahit hindi diesel fire pump. Kasi magastos po ung ganun. Alternative po is dapat meron reliable source lang po ng supply. Isa na po yan ung generator po ng building na yan. Dalawa pa ung genset po namin jan. Connected din po un sa ating fire pumps. Kaya gagana po kahit may sunog kasi may supply po. 😊 peru kung di nyo po kaya ung may diesel fire pump. As per sa code po pwd na eh connect nyo po directly ang inyong fire pump supply sa mismong service utility.
@Art_2000_HandyEngineer
19 күн бұрын
Hehe sorry din po. Medyo natagalan reply ko po😅
Good day. Need b namin ang WET Stand Pipe? Ang kompanya ng namin ay fabricator ng Dam -Irrigation Gate (all metal), may 20 katao at welding ang pangunahing trabaho, walang 2nd Floor at Basement. 5000sq meter area at 4000sq m ang may bubong na 12 to 15 M ang taas.. NOTE puro HUGE electrical machines ang gamit namin at puro bakal ang producto namin?? Need b namin ang WET Stand Pipe?
@Art_2000_HandyEngineer
Жыл бұрын
Ang alam ko Sir kapag more on electrical talaga, hindi advisable ang wet stand pipe.. nung kumuha po ba kayo ng business permit hindi po ba yan ni BFP? Double check rin po muna sa FiRE code natin kung need po. Balikan ko po kayo..
high pressure sprinklers ba gamit nyo o me PRV kayo sa itaas, hanggang 175 psi lang kasi ang sprinklers bagamat meron naman 300 psi
@Art_2000_HandyEngineer
Күн бұрын
Meron po kami PRV po jan lalo ung sa high zone po, 3 po. Hindi po kasi talaga okay ung sobra sobrang pressure. Samahan pa ng gravity.
If i isolating switch on electrical pump why motor running please reply me
Present
@Art_2000_HandyEngineer
2 жыл бұрын
Okay next..
sir un mga gate valve nyo di b dapat os&y. n may supervisory switch. ask ko lng if ever may supervisory switch pwde b ntin i tap sa control panel ng Fire pump
@Art_2000_HandyEngineer
Жыл бұрын
Ang alam ko po ung tapping lang ng mga Supervisory Switch natin is sa FDAS panel po. Ung nakakabit lang po sa Fire Pump panel is ung supply then sensing line po. Naka interface lang cya sa FDAS, para alam ni FDAS kapag may gumana na pump.
@Art_2000_HandyEngineer
Жыл бұрын
Supervisory switch po namin si naka kabait po mismo per floor..
Nice video sir, pang 5th flr yung 125HP na fire pump nuh? Panu po sir pag 3storey building lng, ilang HP po kaya yung need ko n fire pump
@Art_2000_HandyEngineer
Жыл бұрын
Ung 125 hp Sir. Kasama na po ang 5 na basements po. So bali 10 floors po un. For a 3 storey naman po, kung wala naman basement kaya na po un tingin ko ng 40 to 50 hp.
@therjm1476
Жыл бұрын
Thanks sa information engr., Wait mag.subscribe pla ako,haha, ty
@Art_2000_HandyEngineer
Жыл бұрын
@@therjm1476 thanks Sir!! 😁 have a nice day po. Ni edit ko pala ung reply ko. Na typo error pala 🥹
@therjm1476
Жыл бұрын
Anu ngapla area ng floor yung building nyo sir?
Posible ba makasira ng io board na syang nagmonitor ng current flow sa line kapag may open ct habang natakbo ang pump?
@Art_2000_HandyEngineer
9 ай бұрын
try ko muna alamin sir/ma'am. medyo hindi ako sigurado sa isasagot ko po. hehe sorry din po kung late reply hindi na po kasi ako active dito gawa iba na po ang field of work ko po now.
Hello dear , why jokey pump goes high pressure around 20 bars ( more than design pressures)during day time ?
@Art_2000_HandyEngineer
8 ай бұрын
Let me check
@mohammedalsubhi5028
8 ай бұрын
@@Art_2000_HandyEngineer Ok , Waiting for you reply. Thanx
electric driven po ba ung alarm bell nyo connected sa labas boss?
@Art_2000_HandyEngineer
Жыл бұрын
No Sir. Hydraulically operated po ung dito samin.
hi mat cut out po ba ang electric fire pump pressure thanks
@Art_2000_HandyEngineer
8 ай бұрын
wala po. cut out ang fire pump. manual po ung na pinapatay. although base sa settings po pwd mo lagyan. peru per advise po ng code dapat wala po.
Idol paki demo ng lahat ng valve ng pump room
@Art_2000_HandyEngineer
2 жыл бұрын
Sige Sir. Subukan po natin sa sunod na video. Kapag medyo di po busy sa site 😊
Sir Ilan allowable minutes Ng dropped of pressure Bago mg start Ang jockey pump sa normal operation
@Art_2000_HandyEngineer
2 жыл бұрын
Ang alam ko Sir hindi aabot ng minutes. 1 - 2 seconds lang sir gagana na dapat ang jockey once na umabot na sa cut-in nya ung pressure ng system. Automatic, as in mabilis na dapat gumana si Jockey.
Hi sir , pwede po mag ask about sa project namin about fire pumps ?
@Art_2000_HandyEngineer
Күн бұрын
Tapus na ata submission ng project nyo po.. hehe anu po sana tanung nyo??
Fire department connection tawag po dyan.Pwedeng wet or dry po.
@raymondsantiago475
11 ай бұрын
bawal na po ang dry ngayon boss
engr anong purpose ng Diesel pump?
sir paano magpaandar nang fire pump panel and jacke pump
idol. patutor naman ng pag dedesign ng fire protection
@Art_2000_HandyEngineer
Күн бұрын
hehe sorry po sir.. hindi ko po kabisado ung sa design part po...
Boss bkit laging umaandar yong fire pump namin kahit may jockey pump naman dati hindi naman siya ganon
di po ba dapat 5psi lang ang difference ng cut in ng jockey pump sa fire pump boss? i mean mas mataas lang ng 5psi yung cut in jockey pump sa fire pump?
@Art_2000_HandyEngineer
9 ай бұрын
yes po tama po kayo. dpat ganun lang po. un din kasi nakalagay sa fire code po. peru ung samin po ksi pinapaayos pa din namin yan sa contractor po since under warranty pa po yan that time.. now wala na po ako jan.. hehe resign na po kaya di na masundan :(
Ilang hp po yung jocket pump nyo?
goodnoon sir, anong building po ito at ilang storey po, sakamats
@Art_2000_HandyEngineer
4 ай бұрын
Confidential po. 😅😅
boss ... Anu po required na setting sa pressure switch ..sa jockey pump na 5hp ? ...at dn Ang fire pump nya is 40hp ..ilan Po setting nang fire pump ..? ty sa pag sagot boss ..God Bless
@torvicperalta4516
11 ай бұрын
Kalimitan po sa pagkuha ng pumps po nagbibigay ka ng psi requirements doon sa suppliers po tapos mag estimate sila ng curve pumps po basi sa Napili ngong capacity ng pumps,dapat po ang standard ay UL and FM po sya certified po.Kasama po kasi dyan iyon compliance ng NFPA.Mostly The newly designed specified po section 28311 It means Digital Addressable Fire Alarm system.😊
@Art_2000_HandyEngineer
8 ай бұрын
Very knowledgeable talaga si sir pg dating sa fire pro at fdas. thank you so much po sa pg comment at pg sagot sa query po..More power po sainyo!!
Sir gud pm ask ko lng po bakit hindi na po nag automatic umaandar ang main pump, pero yung jockey ok nman, ano po kaya problema nun sir, salamat po sa sagot
@Art_2000_HandyEngineer
Жыл бұрын
Ilan po ba cut-in ng Main Pump (Fire Pump) nyo po? Na aabot nya po ba? Baka po kasi cut-in lang ni jockey ang naabot. Better to off po muna ung jockey. Then bawasan po natin pressure ng system hanggang maabot ung cut-in ni Fire. Then pag hindi po gumana, need na po siguro ng cleaning sensing line n. Double check nyo din po if naka auto po talaga ang FP panel nyo po.
Nag se service ba kayo vertical turbine
@Art_2000_HandyEngineer
Жыл бұрын
Negative po Sir.. sorry po 😓
boss ilang HP po b dpat ang fire pump at jockey pump...thanks u god bless
@Art_2000_HandyEngineer
9 ай бұрын
depende po un sa lawak at taas ng building na pg lalagyan po. ma okay po kapag sa designer po kayo nakapag tanung po. may ready na po kasi sila na mga computation nun. PME or ME po pwd makasagot sa tanung nyo po.
@roydinnondon8915
8 ай бұрын
@@Art_2000_HandyEngineer thanks u
Then normal lang po ba na tunog nang tunog yong alarm ball during operation ni Jockey pump sir?
@Art_2000_HandyEngineer
Жыл бұрын
Normal lang po Sir. Kasi May pressure po. Much better kung testing lang naman pwd naman eh off nalng po. Para di maxado maingay. Masakit din kasi sa tenga. Wag lang kalimutan na buksan after 😅😅
@jeremycorod2861
Жыл бұрын
Tama , sige po sir at mraming salamat
ano pinagkaiba sa electical pump dun sa fire pump boss?
@Art_2000_HandyEngineer
8 ай бұрын
Medyo malabo po query nyo sir.. :)
Sir normal lang ba na hindi namamatay diritso andar ng jocky pump?
@Art_2000_HandyEngineer
9 ай бұрын
hindipo un normal.. dapat namamatay po yan automatic once ne reach nya na ang cut off pressure na nakalagay sa settings.
Idol anong problem sa fire pump na pag naka automatic namamatay tapos pag delta na nag ttrip ang primary beaker . Pero pag manual ok sya.
@Art_2000_HandyEngineer
Жыл бұрын
Hindi po dapat namamatay ung Fire Pump kapag automatic.. wala po kasi dapat un cut off, cut in lang.. jockey pump lang po ang automatic kapag na reach nya ang cut off pressure nya. Sa tripping ng breaker po, kaka energized nyo palang po ba nyan? Or matagal na operational peru ng ka problema lang?
@Art_2000_HandyEngineer
Жыл бұрын
Manual po na pinapatay ang Fire Pump once mg activate thru normal operation..or in case na may nasunog na nga.
@jhunluaton3306
Жыл бұрын
@@Art_2000_HandyEngineer nag ka problema lang Po pero dati ok Naman sya. Di Po kaya sa mercoid Ang problema?
@jhunluaton3306
Жыл бұрын
@@Art_2000_HandyEngineer manual na Po Ang pag pa andar at pag off
FDC PO? FIRE DEPARTMENT CONNECTION PO ? DRY PIPE SIR? 😊
@marvinpobocan1549
Жыл бұрын
yun po yung pipe na tinuro mo po kanina sir? tama po?
@Art_2000_HandyEngineer
Жыл бұрын
Yes po 😊😊😅
Bakit po ba need ng back to tank??
@Art_2000_HandyEngineer
Жыл бұрын
Need po kasi ng pg tatapunan ng excess na pressure po. Sobrang lakas po kasi ng fire pump natin and once na hindi ma release. Bibigay po ang mga pipe connection natin at mga sprinkler head..
Mag kano sir fire pump 10hp at jockey pump 3 hp
@Art_2000_HandyEngineer
2 жыл бұрын
Sa price sir. Hindi ko lang po kabisado 😅 sa installation po kasi ung mga ganun po. Peru try ko then sa kanila tanungin.
bro mali ka din sa 8:00 hindi mag supply ang Fire Pump papunta Fire department connection, test hose header un pinu point out m dyan pang test yan ng flow. Ang FDC ay connection pra mag supply ng tubig sa system
@Art_2000_HandyEngineer
Жыл бұрын
Thank you Sir!! Eh take note ko po yan. 😊😊
Bro medyo mali sa video mo 8:58 un PRV or pressure relief valve hindi pang sobra pressure ang function ng Pressure relief valve ay i release un pressure above ng churn ng fire pump, At un pressure relief ay hindi gnagamit gaya ng pressure regulating valve na kailangan m control un over pressure papunta sa mga sprinkler head
@Art_2000_HandyEngineer
Жыл бұрын
Thank you so much Sir!! Hehe sabi ko nga hindi ko naman alam at kabisado lahat. Maraming salamt po sa pg correct sakin. 😊
Pwede pahingi ng wye delta firepump diagram with pressureswitch .sir.?
@Art_2000_HandyEngineer
Күн бұрын
Sorry po Sir. nag resign na po kasi ako as Building Engineer po jan kaya di na po ako makapg upload ng kasunod.. sorry po ulit..
bro mali un nabanggit m sa 6:23 hindi mahina pressure ng jockey pump kundi mahina ang flow ng jockey pump kya bmabagsak un pressure pag may discharge na tubig. Rated same pressure or above ang Jockey sa Fire Pump
@Art_2000_HandyEngineer
Жыл бұрын
Salamat Sir 😊 tama nga po kayo..
sir magtatanong paano i normalize kung jockey pump is high pressure saan pwede i adjust
@Art_2000_HandyEngineer
Жыл бұрын
Sorry Sir, Now ko lang nabasa comment nyo. Panung high pressure sir? Hindi match ang system pressure sa pressure na nakalagay sa jockey pump panel?
@aljeansalvador5596
Жыл бұрын
@@Art_2000_HandyEngineer sorry late din reply hehe yes sir tumaas ang pressure saan pwede i adjust pra maging normal ang pressure.
Paano naman po mag back to tank
@Art_2000_HandyEngineer
8 ай бұрын
Thank you po sa pagnuod at pag comment!!! sorry po kung di ko na masusundan ung mga video ko po n yan. Lumipat na po kasi ako ng work at bawal na po ung ganyan sa nalipatan ko.. sorry po. kaya di na po ako active dito sa youtube. :(
Brad mali ang nilagyan m9 ng View glass. Yung sa PRV mo. Napansin mo concentric ang hugis nya at subra makapal ang bakal. Dapat nyan nasa dischrage ng fire pump. Kaya sya subra makapal na bakal. Doon mo makikita kubg nag hihigop ang pire pump mo sa view glass nya. Kaya malai ang location mo ngyon. Kasi after ng PRV mo . Doon sa discharge water ng over pressure mo hindi naman kailanagn lagyan ng concentric view glass device.
@Art_2000_HandyEngineer
Жыл бұрын
Thank you Sir!! Eh take note ko yan. Try ko eh raise kay Developer. Sa ngayon kasi yan po na approved na design ni Consultant kaya yan din ginawa ng fire pro contractor.
@johnpaulmasculino3222
Жыл бұрын
Yes brad.. yung sa amin kasi si supplier talaga nag pa arrange ng sequence. Kasi ayaw nila e permahan ang turn over clearance kung hindi masunod ang sequence nila. Kasi nga ayaw nila maging liable if mag fail ang system dahil hindi nasunod ang standard nila.
@johnpaulmasculino3222
Жыл бұрын
Split case lang sa amin. Parehas naman ang pannel natin. . Ibang PRV lang sa amin at may flow water rate na kasama sa package.
@johnpaulmasculino3222
Жыл бұрын
Nagkaroon n trap tuloy ang sa discharge ng prv mo dyan sa view glass mo na concentric. Lalo na ang return pipe mo pataas kasi ang water tank mo elevated. Fabricate nalang kayo falange paano mo na connect ang view glass na yan sa harap ng firepump nyo. Hopefully parehas ang size nila ng flange para mabilis lang ilipat.
@johnpaulmasculino3222
Жыл бұрын
Suggestion lang naman skin. If you want i can you a photo ng gawa namin.
Sir paano mag off s alarm ng panel ng fire pump low bat vdc ang disply maingay kasi
@Art_2000_HandyEngineer
2 жыл бұрын
Kahit eh PRESS po ang "Silence Alarm"? baka pwd niyo pa send sa FB page ko ang picture ng panel na meron kayo. Subukan ko po kung kaya ko kayo matulungan.
Installer kaba sir ng sprinkler?
@Art_2000_HandyEngineer
2 жыл бұрын
Hindi po sir 😊 Building Engineer po ako.
Sir,bakit walang nakainstall na diesel,dapat may diesel yan,at saka kulang2x yung mga paliwanag mo sir.
@Art_2000_HandyEngineer
8 ай бұрын
Thank you po sa pagnuod at pag comment!!! sorry po kung di ko na masusundan ung mga video ko po n yan. Lumipat na po kasi ako ng work at bawal na po ung ganyan sa nalipatan ko.. sorry po. kaya di na po ako active dito sa youtube. :(
@noelayosa5093
4 ай бұрын
Kaya nga dapat may diesel engine fire pump yan! Kulang ang system ng fire pump system pag ganyan🤔
Gud pm sir pwede humingi ng contact number.
@freddiecalo5954
Жыл бұрын
Mag order kami ni to asap po.