ECM Condenser Fan Motor Diagnosis and Replacement - Rheem RQPMA037

In todays video I return to a condenser fan motor that wasn’t working. I go through diagnosing and replacing what happened to be an ECM motor. #hvac #hvactech #hvactechnician #hvaclife #fieldpiece #makita #rheem #ecm #motors
Merch Store: www.bonfire.com/store/hvac-gu...
Here are links to the tools I use, And it costs you nothing extra to buy from this list:
Fielpiece SC680 Clamp Meter: amzn.to/33rhxvE
Fieldpiece SC480 Clamp Meter: amzn.to/33kfgCB
Fieldpiece SMAN 480 Digital Manifold: amzn.to/3twfVvA
Fildpiece SVG3 Vacuum Gauge: amzn.to/3udursu
Fieldpiece DR58 Leak Detector: amzn.to/3nt1TXw
Fieldpiece Blutooth Scale: amzn.to/3Gzveab
Fieldpiece SDMN6 Manometer: amzn.to/3qwk9RP
Fieldpiece 8CFM VP87 Vacuum Pump: amzn.to/3qC2wA2
Makita XDT16: amzn.to/3riXuaJ
Makita 18V Light: amzn.to/3Fw4GW4
Makita Wet/Dry Vacuum : amzn.to/3tw4dAL
Makita 18V Battery Mounts in Van : amzn.to/3GxpVID
Makita 18V Angle Grinder: amzn.to/3gskNd7
Grinder Quick Replace Locknut: amzn.to/32YZugb
Makita Jobsite Radio: amzn.to/3HuVp2u
DIY Vacuum Attachment for drains: amzn.to/3tDpfNU
Fieldpiece Smart Probe Kit : amzn.to/34NG3HL
Klein Heavy Duty Wire Strippers : amzn.to/3I8YNzT
Klein Needle Nose Crimpers/Stippers: amzn.to/3fuwXlw
Klein Journeyman Pliers: amzn.to/3tvB60w
Milwaukee Slim Packout On My Torch: amzn.to/3KeLm3j
Aluminum Packout Wall Mount on torches : amzn.to/3Kf9hQg
Milwaukee Tool Box: amzn.to/322iyK9
Veto Pro Pac Tech MCT: amzn.to/3nwwQdA
Milwaukee Hook Blade Knife: amzn.to/33F3m5T
Testo 300 flue gas analyzer: amzn.to/3IcS3Bd
Western Nitrogen Regulator: amzn.to/3rmdKrx
Klein Canvas Bucket: amzn.to/3FyzKVf
Flag Velcro Patch Kit: amzn.to/3K8Eswx
Supco Magnetic Door Switch Holder: amzn.to/34IcXcL
Milwaukee Magnetic Light: amzn.to/3FulCfF
Milwaukee Rechargeable Headlamp: amzn.to/3nuXsvf
SS2 Float Switch: amzn.to/3K7LJMW
3-Amp Breaker: amzn.to/3nxaSXJ
Appion Valve Core Removal Tool: amzn.to/33CFArw
Appion G5 Twin Recovery Machine: amzn.to/33Dvd6C
Yellow Jacket Large Tubing Bender: amzn.to/3qwJv1U
Similar Small Tubing Bender: amzn.to/3fJsziJ
Fluke Twist Guard Test Leads: amzn.to/3216R6j
Fluke 975 Air Meter: amzn.to/3GwD9oM
Honeywell T-4, 2-Heat, 1-Cool Programmable Thermostat: amzn.to/3qtIuaX
Kidde Carbon Monoxide Alarm: amzn.to/3qtIIyP
SolderWeld Flame Resistant Magnetic Blanket: amzn.to/3qtJ4Wb
Malco 1/4 - 5/16 flip bit : amzn.to/3nr67yU
Quick Check Acid Test: amzn.to/3GA2XAy
Aims Power Inverter: amzn.to/3qOSc87
Wiha Torqe Screwdriver : amzn.to/3u1swH6
Wiha Torqe Screwdriver 1/4” adapter: amzn.to/3IH22Pw
American Flag Gator : amzn.to/3rKBl5u
Compressor Tote: amzn.to/3H8xHst
Inspection Mirror: amzn.to/3r9PERV
Wiha TorqueVario-S 10-50 in/lb Torque Screwdriver : amzn.to/3GbKAku
1/4” adapter for Wiha Torque Screwdriver : amzn.to/3u8g0pq

Пікірлер: 77

  • @primusheating1
    @primusheating12 жыл бұрын

    You can't blame it on static pressure, you can't blame it on humidity getting into the motor..... I love it brother! Those are my sentiments exactly.

  • @flirjock
    @flirjock2 жыл бұрын

    My HVAC guy came Fri. because my heat pump wasn't working. Bad news, system totally dry of coolant R-22, and compressor had dumped some oil. It's a 3.5 ton unit 13 yrs. old. He recommended new system. I'm not too thrilled but I guess it has to be done. We've got emergency heat (split system) and gas log fireplace (LP) I want to make sure I have a good system before summer heat sets in.

  • @kyleglover2353
    @kyleglover2353 Жыл бұрын

    Just came across one of these yesterday. So glad you had made this video. Great advice thanks for the help man

  • @kennethrimestad5045
    @kennethrimestad50452 жыл бұрын

    I really like the way your present your diagnoses and fixing HVAC systems. You are so informative. Also just wanted to say take care of your health for yourself and family along with your clients too.

  • @thesilentonevictor
    @thesilentonevictor2 жыл бұрын

    Great troubleshooting and change out on this fan motor 👌

  • @johnwalker890
    @johnwalker8902 жыл бұрын

    Got yourself a workout there, Good job Curtis, I can tell your ribs getting better, you went at that motor at full steam.

  • @hwrdwlls
    @hwrdwlls7 ай бұрын

    Looked this up. Have a service call to go to tomorrow on 4 ton Ruud package heat pump most likely same issue from the description of the problem from my customer. Good video. Unit is only 1-1/2 years young. Crazy!

  • @Eddy63
    @Eddy632 жыл бұрын

    Good little fan motor changeout vid ... Thx ...

  • @mansourramzey7711
    @mansourramzey77112 жыл бұрын

    Great video, sometimes doing it all by yourself will make you tired and frustrated, but you got it under control. ✌

  • @donaldpainter956

    @donaldpainter956

    Жыл бұрын

    I always work alone I've tried to train a few guys and half don't care what kind of work they produce they won't get simple helper tools or they just plain won't work think they can keep a phone in one hand and work with the other so I've got my van set up where I can do anything by myself I can move package units by myself I can put furnace or airhandler in the attic or crawl space by myself my son used to help me but someone killed him in 2019

  • @mansourramzey7711

    @mansourramzey7711

    Жыл бұрын

    @@donaldpainter956 i am so sorry to hear that ,god bless his soul. I know exactly what you mean, i have to be on almost every job, (plumbing, electrical,....) because they leave a mess and i have to take the call from tenant so i go meet them at the site and once they are done and i don't see any issues i pay them. I hope you stay safe and again god bless his soul 🙏🙏🙏

  • @deanmartin1966
    @deanmartin19662 жыл бұрын

    Hate those intermittent problems

  • @tedhicks5431
    @tedhicks54312 жыл бұрын

    You are correct static pressure my foot in carrier folks in ga exscuse I've had 2 blower motor on one dual fuel gaspack go bad in 7 yrs glad I registered it for the 10 yr warranty

  • @abdullah_q8171
    @abdullah_q81712 жыл бұрын

    Tidy work 👍🏻

  • @timmalan3741
    @timmalan37412 жыл бұрын

    Saturday calls bring out max speed in a technician during nice weather. I found a bad heat exchanger today and your short sleeving on a.c.unit. Enjoy nice weather. Hope ribs are doing better.

  • @rhyoliteaquacade
    @rhyoliteaquacade Жыл бұрын

    Inside the round controller there is an $8 thermistor that limits inrush current. That is the likely failure mode.

  • @tims.5995

    @tims.5995

    Жыл бұрын

    How do you test the thermistor and is there different sizes if so how are they rated ?

  • @hwrdwlls

    @hwrdwlls

    7 ай бұрын

    Part is under warranty. Wouldn't be worth trying to repair a bad part.

  • @realestateservicessaleshea99
    @realestateservicessaleshea992 жыл бұрын

    Thanks for the videos 🥃🥃🍺🍺🍺⛳🎳 Stay safe. Retired (werk'n)keyboard super tech. Wear your safety glasses!

  • @orlandojohnson5742
    @orlandojohnson57422 жыл бұрын

    Few months ago I yanked out an indoor motor on an air handler!!! Same type … ECM!?!?! I installed a regular PSC motor! And put a relay in to work with the fan control board! I asked (the supply house) the difference in ECM vs PSC…. He said lower locked rotor amperage! So I asked what’s the difference if you run a PSC motor on continuous fan (run load amps are about the same!!!)🤔🤷🏽 So I’d really like to see the difference in a power bill when both are ran nonstop! I personally jus think it’s another high dollar addiction to what could be a more standard reliable operating system! With a satisfied customer & a service tech going where he’s really needed! “Keep it simple!” QUIT THINNING EVAPORATOR COILS FOR MORE EFFICIENCY TOO!!! More refrig leaks on da way in da process 🙅🏼🙅🏻‍♂️🙅🏽‍♀️

  • @bill944

    @bill944

    2 жыл бұрын

    I see what you're saying about the ECM but you can't run an indoor fan constantly. During cooling season you'll reintroduce the moisture on the indoor coil back into the living space and there will be an issue. It'll also feel like they're living in a cave, cold and wet. The blower must turn off after a call for cooling unless there's auxiliary dehumidification.

  • @bryansimon4072
    @bryansimon40722 жыл бұрын

    Those motors suck but they help me pay the bills. Thanks

  • @kylewells6871
    @kylewells6871Ай бұрын

    Right now we're seeing a wave ecm fan motors fail on 16 seers rheems all within 5yrs old. It's pretty upsetting, we've already had 8 warranties in the last 3 months. They're claiming is water related, but it's not just rheem, it's across the board. Also had our first compressor fail on a unit less than a yr old, (the new model).

  • @michaelhediger9088
    @michaelhediger90882 жыл бұрын

    There is a part in the module that causes that problem it is the choke

  • @Garth2011

    @Garth2011

    Жыл бұрын

    Thermistor...a $2 part.

  • @stephwaylonwells3218
    @stephwaylonwells32182 жыл бұрын

    👍

  • @jess8075
    @jess80753 ай бұрын

    What is the blue wire, what does it do, and where does it connect to. Thank you

  • @wanaraz
    @wanaraz Жыл бұрын

    Can you have a 50/5 Capacitor and install a condenser fan that says CAP10? Will it still work properly?

  • @kevinpowell9740
    @kevinpowell97402 ай бұрын

    Would you do a video on Rheem heat pump 2 ton condenser fan doesn't turn off and how to fix it.

  • @marcusdarnell3348
    @marcusdarnell33482 жыл бұрын

    If you are having trouble separating the fan blades from the motor could u tap on the shaft of the old motor with a mallet to dislodge it?

  • @amiatroll6347

    @amiatroll6347

    Ай бұрын

    No, that risks mushrooming the shaft and you won't be able to remove the blade without a lot more effort.

  • @kirkarnett1164
    @kirkarnett11642 жыл бұрын

    Please share how many years youve been doing this and where you got your training and education.

  • @aundrecook5462
    @aundrecook54623 ай бұрын

    Good video tho

  • @truearabhustla
    @truearabhustlaАй бұрын

    Recently bought my house. I noticed that my Rheem AC unit's outside fan will spin for 15 seconds and then shut off for 2 mins. It'll turn on again for 15 seconds and then shut off. Rinse and repeat over and over. Called a buddy of mine. He does some HVAC work. He says my unit has an ECM. He doesn't know to much about them. It appears to be similar to what's going on in this video. His buddy says that it's normal. I don't feel like it is. When it was 90 degrees here, my house was blowing hot air until night fell. Then the house started to cool down. So long story short, should the fan always be spinning when the AC is turned on? Thank you!

  • @DisEnchantedPersons
    @DisEnchantedPersons Жыл бұрын

    Always take the panel off, always do amps, always do pressure, subcooling, always calculate uF while running

  • @studyallthetimeallthetime8473
    @studyallthetimeallthetime8473 Жыл бұрын

    Whats the name of the last part installed ? Is that the module?

  • @carllungwitz5171
    @carllungwitz5171 Жыл бұрын

    On the condenser ECM motors, I assume they still do the 15 second run in each direction to determine proper rotation? Once they do the initial rotation procedure, is there any way to make them redo the initialize procedure?

  • @Garth2011

    @Garth2011

    Жыл бұрын

    Depending on the make of the motor. An OEM motor is programmed. The Evergreen motors self learn rotation at first startup but I'm unsure about the speed programming.

  • @justicebruno5249
    @justicebruno5249 Жыл бұрын

    Same issue.. my module..I think...😁

  • @sprockkets
    @sprockkets2 жыл бұрын

    I've never seen an outdoor fan motor save any energy by being ECM. I mean, they always pull .8 amp current for me. Unless I'm interpreting that wrong....

  • @douro20

    @douro20

    Жыл бұрын

    They have a higher power factor. They do use less energy but not a whole lot less.

  • @sprockkets

    @sprockkets

    Жыл бұрын

    @@douro20 yeah like what, .8 vs .97? Which saves on costs if you are a big commercial customer.

  • @biblebloopers946
    @biblebloopers9462 жыл бұрын

    I'm just curious. What do you do with all your bad parts? Where do you throw them away at?

  • @HVACGUY

    @HVACGUY

    2 жыл бұрын

    The metal I sell for scrap. I collect it and sell it in bulk to guys that break it down and sell it.

  • @MariosACandRefrigeration
    @MariosACandRefrigeration2 жыл бұрын

    what do you think about surge protectors ?

  • @HVACGUY

    @HVACGUY

    2 жыл бұрын

    If it has a VFD compressor They should be part of the install.

  • @Garth2011

    @Garth2011

    Жыл бұрын

    Those should be built into components since the industry is fully aware that power is never perfect.

  • @zacharyreed45
    @zacharyreed452 жыл бұрын

    Love the content, which Veto bag is that? & does that SC680 fit in it? I need to retire my current bag but, I loaf around that 680, just want it to fit. X13, you lose any benefits from cost saving measures of that motor the first time it breaks out of warranty.

  • @HVACGUY

    @HVACGUY

    2 жыл бұрын

    Tech MCT, and yes the 680 fits

  • @jamesbroomfield7799
    @jamesbroomfield7799 Жыл бұрын

    You should've explained what everything was like that round can that you replace inside the unit. Is that à control box for the fan motor?

  • @HVACGUY

    @HVACGUY

    Жыл бұрын

    it’s a module. but, yes it controls the motor

  • @jonleon9132
    @jonleon9132 Жыл бұрын

    I work on rheem/ruud and it's not as uncommon to have their ecm condenser fan motors that will thermally trip over and over. It's a clear symptom they are bad.

  • @aundrecook5462
    @aundrecook54623 ай бұрын

    I wish folks would get str8 to the point lol

  • @tims.5995
    @tims.59952 жыл бұрын

    So is the ECM condenser fan motor just on the heat pumps ?

  • @davidperry4013

    @davidperry4013

    Жыл бұрын

    They are often found in AC units and heatpumps with variable speed compressors in them but they are of higher grade materials since AC units with variable speed compressors are made to last longer than single stage units.

  • @michaelmorassi4953
    @michaelmorassi495311 ай бұрын

    Not your design, but what a wonderful place to tie any and all excess wires???

  • @ronaldphillips8750
    @ronaldphillips875010 ай бұрын

    Should fan motor be replaced when vibrating excessfully.

  • @cassiopeiaclark9260
    @cassiopeiaclark92602 жыл бұрын

    Is the typical for a Rheem unit to have the fan motor fail after 3 years?

  • @tedhicks5431

    @tedhicks5431

    2 жыл бұрын

    Don't matter rheem or other those motors give problems like he said if out of warranty go to psc motor

  • @jondoh3471
    @jondoh347111 ай бұрын

    It was prob struck by lightning.

  • @1werewolf
    @1werewolf2 жыл бұрын

    Every manufacturer has a bad part. Rheem its the cfm, Carrier its the run cap, Lennox has leaky evap coils..and on and on......

  • @caru3257
    @caru32572 жыл бұрын

    40° F here and you are doing no cooling.

  • @HVACGUY

    @HVACGUY

    2 жыл бұрын

    We get about 4 weeks of winter, and even then we run the AC during most of those days.

  • @kirkarnett1164
    @kirkarnett11642 жыл бұрын

    I would give anything to know half of what you know

  • @thogevoll
    @thogevoll2 жыл бұрын

    Have you ever run into a situation where an ECM fan motor would not run if the line voltage was slightly high? By that I mean 242 to 243 VAC. Do you have a video on swapping an ECM fan motor to a PSC motor?

  • @jonleon9132

    @jonleon9132

    Жыл бұрын

    Psc motor is simple. Wire it up to a capacitor and l1 and l2 on contactor. When contactor pulls in it will cut on. Just don't do that on a heat pump cause then it won't turn off in defrost

  • @geffreyacosta8821

    @geffreyacosta8821

    Жыл бұрын

    When my ECM fan motor went out, I feel like they put the wrong one. Right after my AC not blowing cold enough. Any ideas?

  • @mikewhittaker5984
    @mikewhittaker59842 жыл бұрын

    I’ve noticed in your last few videos you seem very rushed are you that swamped seems like you need to slow down just a bit

  • @HVACGUY

    @HVACGUY

    2 жыл бұрын

    Sometimes. Early in this video I was rushed because I didn’t want that compressor to overheat.

  • @Garth2011

    @Garth2011

    Жыл бұрын

    If you have plenty of business or work on the appointment books, it makes zero sense to rush any job or be in a hurry. And if you are not all that busy, why rush?

  • @jondoh3471

    @jondoh3471

    11 ай бұрын

    @@Garth2011 He wants his Lambo.

  • @classic287
    @classic2872 жыл бұрын

    Rheem a/c units are garbage. Too expensive to repair. I have that same unit. After 2.5 years air handler ecm motor quit. $800 just for labor. Motor is under warranty. Imagine if both Motors were ecm 😳🤔 The other motor has a capacitor.

  • @jonathansorise8797

    @jonathansorise8797

    2 жыл бұрын

    Damn 800 just for labor??? What company was it? Gonna go apply there since they must be paying good. 😅

  • @russelllieser4226
    @russelllieser42267 ай бұрын

    What a hack tech.