Dry Sprinkler Inspection

A dry sprinkler system is pressurized with air or nitrogen, rather than having the pipes constantly filled with water. These systems often cover unheated spaces like freezers, attics, or an outdoor loading dock.
The main control valve and riser are usually located in a heated space such as a maintenance room, or closet. The pressurized dry-pipe valve prevents water from entering the system until a fire activates one or more sprinkler heads.
Once a sprinkler head breaks, the system loses air pressure and the dry valve activates. The clapper then opens, filling the system with water which makes its way to activated sprinkler heads to contain and/or suppress the fire until emergency services can arrive on scene.

Пікірлер: 10

  • @dicko-200
    @dicko-2007 ай бұрын

    you had residual and static water pressures backwards. Static is no flow. Residual is 2" drain test water flow.

  • @thelovefamilymilitarypod
    @thelovefamilymilitarypod11 ай бұрын

    Thanks for the video

  • @silcofireandsecurity

    @silcofireandsecurity

    10 ай бұрын

    You're welcome! Thank you for commenting.

  • @robertobryk4989
    @robertobryk49893 ай бұрын

    Why do you disassemble the valve _after_ testing its function? This way there's no opportunity to notice that the reassembly is incorrect in a way that reduces flow.

  • @gerald3937
    @gerald393710 ай бұрын

    is there a way I can test the water flow switch without tripping the Dry Valve? thanks..

  • @silcofireandsecurity

    @silcofireandsecurity

    10 ай бұрын

    Yes, there is a way to test the flow switch and not trip the valve. Depending on where you live and the regulations in your area, we recommend to have your inspector there to perform the test.

  • @mikeandema6925

    @mikeandema6925

    10 ай бұрын

    1 Put the system on test call alarm company. 2 close the piv or backflow valve. 3 close the control valve. At the alarm valve Make note of the alarm panel readings for each supervised device ie. backflow or piv. Control valve. Close the air supply ball valve to the Alarm valve located at the compressor. 4 Open the water flow device/Switch with the key provided by the manufacturer. 5 manually engage and hold down the stick lever in the middle of the device for At least two minutes make note of the time detection is achieved. Revers the process. Clear the panel.

  • @anthonykellogg9332

    @anthonykellogg9332

    8 ай бұрын

    Many dry pipe valves have an alarm test valve. It comes from the bottom side of the clapper and goes into a tee that feeds the high pressure switch (water flow switch). It allows you to force water into the pressure switch with no risk of tripping the system.

  • @codydaniel8312
    @codydaniel83122 жыл бұрын

    Man that's an ugly Dry Valve.

  • @silcofireandsecurity

    @silcofireandsecurity

    2 жыл бұрын

    Unfortunately they are not all pretty unless it's brand new, even then - some are questionable.