Core Refrigeration: Refrigeration Wiring

Тәжірибелік нұсқаулар және стиль

Table of Contents:
00:00 - Core Refrigeration
00:17 - HVAC Commercial Ref
01:21 - HVAC Commercial Ref
01:44 - HVAC Commercial Ref
01:51 - HVAC Commercial Ref
02:44 - HVAC Commercial Ref
03:44 - HVAC Commercial Ref
04:13 - HVAC Commercial Freezer
04:35 - HVAC Commercial Freezer
05:04 - HVAC Commercial Freezer
06:14 - HVAC Commercial Freezer
06:23 - HVAC Commercial Freezer
06:28 - HVAC Commercial Freezer
06:58 - HVAC Commercial Freezer
07:04 - HVAC Commercial Freezer
07:08 - HVAC Commercial Freezer
07:36 - HVAC Commercial Freezer
08:15 - HVAC Commercial Freezer
08:39 - HVAC Commercial Freezer
09:03 - HVAC Commercial Freezer

Пікірлер: 25

  • @Pujari917
    @Pujari9175 ай бұрын

    V. V good 👍🙏

  • @rahmanyalshugaa3556
    @rahmanyalshugaa35563 жыл бұрын

    Really I will thank you again and again because I found what I'm looking for, I hope to get more information about mid -temprature and low temprature

  • @cmolnar65

    @cmolnar65

    3 жыл бұрын

    Let me see what I can do on the refrigeration side. I am pretty busy with air conditioning right now, but I have a few things in mind on the refrigeration.

  • @maintenancechef42
    @maintenancechef42 Жыл бұрын

    You are so good, you should have million of viewers

  • @kevinlester
    @kevinlester3 жыл бұрын

    Great video man

  • @teklesenbetgebreamlak7365
    @teklesenbetgebreamlak7365 Жыл бұрын

    Thanks great details explanation, easy to understand sir.

  • @michaelcostello6991
    @michaelcostello69916 жыл бұрын

    Thanks

  • @BLK-ICE
    @BLK-ICE2 жыл бұрын

    great video very help to someone like me that is still in school

  • @rahmanyalshugaa3556
    @rahmanyalshugaa35564 жыл бұрын

    Thank you so much is very helpful, and I hope to get more information about the wiring in the condeser and inside the box

  • @TheJoypool

    @TheJoypool

    3 жыл бұрын

    Interested in wire type inside fridge for fan and all internal too

  • @ramzg5402
    @ramzg54023 жыл бұрын

    Thanks Sir

  • @manuelitog6242
    @manuelitog62424 жыл бұрын

    Thank you Sr very nice of you

  • @hvac707
    @hvac7074 жыл бұрын

    Nice video sir

  • @MuhammadAmir-vz5yv
    @MuhammadAmir-vz5yv3 жыл бұрын

    Dear sir your video very helpful for me and God bless you sir،👍😊

  • @DiaperwiperDad
    @DiaperwiperDad2 жыл бұрын

    Thx

  • @TheJoypool
    @TheJoypool3 жыл бұрын

    If I need to rewire all the internals what kind of wire or insulation and specs should I go for

  • @adamsblanchard836
    @adamsblanchard8363 жыл бұрын

    👍

  • @hg2.
    @hg2.3 жыл бұрын

    Min 4:00 What is a pump down system?

  • @ranjitkarki1122
    @ranjitkarki11223 жыл бұрын

    Do you have a lab 10 video

  • @teklesenbetgebreamlak7365
    @teklesenbetgebreamlak73655 ай бұрын

    He suppose to have million views l don't understand why

  • @brianpan57
    @brianpan573 жыл бұрын

    this was amazing valuable information. especially for a starting refer tech. today i came across an old r12 cooler with a lpc used as a thermostat. and the unit was freezing all the beverages. i tapped the lpc and the unit shut off. can you show me the wiring diagram of a lpc as a tstat? there wouldn't be a llsv right? because there isnt anything that will energize the llsv

  • @cmolnar65

    @cmolnar65

    3 жыл бұрын

    Correct on the no LLS. Take L1 to the pressure switch out of pressure switch to condenser (compressor/compressor fan). Make sure you put any high pressure switches in series with that. L1 gets wired directly to evap fan (do not go through pressure switch). If evap fan does not run constantly this will not work properly. If no evap fans allow a little more of a differential between cut in and cut out. Does that help?

  • @brianpan57

    @brianpan57

    3 жыл бұрын

    So what allows the psi to go up and down? With it being off?

  • @brianpan57

    @brianpan57

    3 жыл бұрын

    This unit didn’t have an evap fan. Just coil. The cut in was like 35 and differential was 15

  • @cmolnar65

    @cmolnar65

    3 жыл бұрын

    @@brianpan57 when the compressor shuts off, the refrigerant pressures are determined by the temperature of the air surrounding the coil. Temp/pressure relationship. You just have to know the appropriate pressures. I will try to do a video on this Friday or Sat when I have some time.