705.11 Connections to a Service

Ғылым және технология

The rules for connecting parralellel power production sources (such as PV) to a service were clarified.

Пікірлер: 18

  • @iaov
    @iaov11 ай бұрын

    Since I found your channel Ryan I no longer watch Mike Holt. Your explanations are clear and fun!!

  • @danielbell4595
    @danielbell45952 ай бұрын

    Excellent Content! The examples are very helpful. Thanks for sharing your knowledge.

  • @jimmiegill3981
    @jimmiegill3981 Жыл бұрын

    Glad you can figure all this out!

  • @TheTubejunky
    @TheTubejunky2 күн бұрын

    Line side taps are usually connected via IPC s inside of the home's main panel. Those then feed a fused disconnect next to the panel then travel outside to an unfused disconnect for the fire department per NFPA required location with signage. That then feeds the solar combiner with the strings of each array of panels.

  • @TheTubejunky

    @TheTubejunky

    2 күн бұрын

    Those taps or IPC s ARE REQUIRED TO BE SERVICE RATED AS WELL AS UL LISTED. I DO BELIEVE THE SR LABELING on the IPCs STANDS FOR SERVICE RATED.*

  • @user-xc3jy5by6d
    @user-xc3jy5by6d6 ай бұрын

    Love watching your videos Ryan and have a lot of respect and admiration towards you. Being on the AHJ side of the fence we have always required the disconnects to be grouped per 230.72(A). I agree with everything except it being a separate service but for arguments sake we'll say it is. My question, would not every separate single family dwelling service require an emergency disconnect? If so 230.85(A)3 would apply correct? Please share your thoughts. Our whole reasoning is to direct a first responder to a single location to shut off all power to the structure.

  • @brianfisher6799
    @brianfisher679911 ай бұрын

    Good catch on 8 vs 4 aluminum

  • @AllAroundHnadyMan
    @AllAroundHnadyMan Жыл бұрын

    Thank you

  • @keything8487
    @keything84878 ай бұрын

    thank you for the info ! if i may ask; treating it as a separate service disconnect would mean bonding the disconnect as you stated, but also grounding it likewise. so another ground rod(s), grounding rod conductor, or would that tie into the "main"/original grounding electrode conductor? i hear the term ground(ing) loop thrown around all the time when it comes to inter-active solar installations. btw, im hooked on these videos !!

  • @saltyroe3179
    @saltyroe3179 Жыл бұрын

    Still trying to figure out how to add PV that doesn't ever feed the utility. My local utility makes it confiscatory to feed power to them when generating more PV than used. Is that covered in 690?

  • @keything8487

    @keything8487

    8 ай бұрын

    confiscatory = meaning what? they take your system away?

  • @TheTubejunky

    @TheTubejunky

    2 күн бұрын

    ​@@keything8487no they take the generated power you don't use and don't pay you for it. You're supplying them with free electricity (well actually your neighbors)

  • @jimmiegill3981
    @jimmiegill3981 Жыл бұрын

    I was just thinking that is backwards

  • @patrickg7569
    @patrickg7569 Жыл бұрын

    Audio is very low

  • @TheTubejunky
    @TheTubejunky2 күн бұрын

    Those line side taps HAVE TO BE FUSED and cannot extend further than Ten feet. Inspectors have said this.

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 күн бұрын

    @@TheTubejunky And they're wrong.

  • @TheTubejunky

    @TheTubejunky

    2 күн бұрын

    @@RyanJacksonElectrical Could you please advise on what to tell them in the future?

  • @RyanJacksonElectrical

    @RyanJacksonElectrical

    2 күн бұрын

    @@TheTubejunky There is no length limit, and they can be protected on their load side by a breaker or a fuse. You treat them like service conductors because they ARE service conductors.