Very informative video… sir pls upload a video regarding Trane chiller RTAC Communication how it’s works.
@manishgupta-ff4oj3 күн бұрын
Thank for nicely demonstrating.
@hectortorres5426 күн бұрын
Thank you for the video
@sujon313015 күн бұрын
Pleaee Mark the gas suction & Discharge point, & how does conimizer work
@UATechnicalSolutions15 күн бұрын
Thanks for your request. Click on the link for economizer function and operation. kzread.info/dash/bejne/i594l8pmldewgM4.htmlsi=IG83UbrMgWBuLvuU Share your email address for the suction and discharge point explanation
@IgorBond17 күн бұрын
Большое Спасибо за предоставленный материал!
@UATechnicalSolutions17 күн бұрын
пожалуйста
@IgorBond22 күн бұрын
Большое Спасибо за предоставленный материал!!!
@AliBekn178423 күн бұрын
🎉🎉🎉🎉🎉
@spicky296625 күн бұрын
nice...
@kevinmithnick9993Ай бұрын
I've seen some of those sensors can be calibrated. Have you tried that?
@UATechnicalSolutionsАй бұрын
Generally there is no need for Calibration. As they come factory calibrated. Incase there is doubt of wrong output from sensor it can be tested on calibration tool.
@kevinmithnick9993Ай бұрын
Nice videos! Keep the good work! Are you planning any future videos on vsd?
@UATechnicalSolutionsАй бұрын
Yes we are starting with carrier 30kav training course very soon.
@sonusomarajan1735Ай бұрын
How to check igbt York vsd chiller
@UATechnicalSolutionsАй бұрын
What is the chiller model?
@patrikreksa1063Ай бұрын
Yes .. normal useful video ... No blabols... Just data strict .. Nice vid
@avithamosi2061Ай бұрын
Very helpful, thank you
@mohsinelotfi5298Ай бұрын
Quantity of oil 30xa 902
@UATechnicalSolutionsАй бұрын
What is the tonage capacity of compressors?
@mohsinelotfi5298Ай бұрын
Medel number:06TUA483SW1C
@mohsinelotfi5298Ай бұрын
Reference oil of compressor plz
@UATechnicalSolutionsАй бұрын
Synthetic oil sw220
@mohsinelotfi5298Ай бұрын
@@UATechnicalSolutions thank you
@derekprreira32142 ай бұрын
Hi Sir, In a carrier 30 XA chiller, when is there a need to replace an oil level switch ( float switch), can you please explain exactly. Regards Derek
@UATechnicalSolutions2 ай бұрын
Hello. The oil level switch works ok dry contact principal. If the oil level is good in the chiller oil level switch contact should be closer. In case oil level is ok and oil level switch contact is open then replace the switch
@derekprreira32142 ай бұрын
@@UATechnicalSolutions Sir, I appreciate your prompt help. I'm dealing with a 30XA0302 carrier chiller. I can't figure out the chiller tonnage as I'm new to it
@ShakirKhan-kp9ny2 ай бұрын
Thanks for your help
@user-cs6ew2nn6d2 ай бұрын
😮
@user-cs6ew2nn6d2 ай бұрын
❤
@user-cs6ew2nn6d2 ай бұрын
+++ !
@Walkingrelaxing2 ай бұрын
can you go over understanding the prints on an AHU. How to know exactly where devices are going on the ahu by looking at the print
@UATechnicalSolutions2 ай бұрын
Sure, will upload a video soon .
@1shagg4203 ай бұрын
What about when you get the "unable to read from selected device" error on a new sensor and nothing seems to make it read? It says it's not communication but I can turn the LEDs on and off.
@cazuica3 ай бұрын
Tengo el servitool pero no logro conectarme a mi chiller, puedes ayudarme?
@UmarKhan-mb2lm3 ай бұрын
Please make more videos of full training of trane rtac and centravac centrifugal chillers thanks.
Sorry, please, how can I download Tech View version 17 and be grateful to you
@UATechnicalSolutions3 ай бұрын
You can only access it if you are a Trane representative
@user-yo8om6cv2j4 ай бұрын
if someone need KestrelView and Tracer TU, you can contact me.
@user-ze7tg8ch4v4 ай бұрын
Thanks a lot for the content
@UATechnicalSolutions4 ай бұрын
Always welcome
@whatyouwant76334 ай бұрын
How to remove copper winding
@md.shahid43055 ай бұрын
How many days does it take to change chiller oil?
@UATechnicalSolutions5 ай бұрын
The simple answer is between 1 to 3 days. Here is the detailed answer. It depends on the chiller size and type. For air cooled chillers oil separator is accessible. You can just pump down the chiller and drain oil. Change oil filter and change oil in just 1 days. But if the chiller doesn’t have valve to isolate or pumping down is not possible than you have to add 2 extra days for refrigerant recovery and vacuum.
@kevinmithnick9993Ай бұрын
Maybe you can recover refrigerant and change the oil in the first day, changing the oil at the beginning of evacuation phase, then left the vacuum pump overnight to pickup evacuation results next morning. Used to use two 12 CFM vacuum pumps whenever possible
@user-dd6eb9bo8r5 ай бұрын
How can we change cards of EEV.... when not find same type. Like we change it from danfoce to sporlan
@UATechnicalSolutions5 ай бұрын
As far the valve specifications i.e Volatge Steps Hertz Milli amps Are same as the old one you dont need to change the card Secondly its not possible to install another type of card . As the rest of the cards in the chiller will not communicate with new type of card. If you are replacing the card is must be same as old
@user-dd6eb9bo8r5 ай бұрын
Very good explanation
@UATechnicalSolutions5 ай бұрын
Thank you.
@MeandMyShadow-hg7xd5 ай бұрын
Can you please tell me the override error in 30xA080-501 Air cooled liquid chiller
@UATechnicalSolutions5 ай бұрын
Please confirm what is the alarm code showing in the display? Or its just showing override ??
@pravinsam82585 ай бұрын
👌
@user-jd9tm4mv9p5 ай бұрын
2
@AlMolhaqcom15 ай бұрын
Al-Molhaq company for HVAC solutions
@joseroa24145 ай бұрын
En español
@kevinmithnick9993Ай бұрын
A chillar a otra parte
@leetucker99386 ай бұрын
transistor is a current driven device . mosfet is voltage controlled
@josellesison3806 ай бұрын
You can access trane techview if you are a trane tech or rep.
Plz create the video in ism card faults and how to repair
@UATechnicalSolutions7 ай бұрын
please provide the actual name of the card and chiller model
@sanjayverma56716 ай бұрын
@@UATechnicalSolutions :- carrier 19xrv chiller ISM .
@_--_Iskandar58_--_7 ай бұрын
Change adapter 12v can use?
@UATechnicalSolutions7 ай бұрын
yes you can as far the voltage are not more than 12v
@kingdesmond39092 ай бұрын
I have a 1 HP inverter air conditioner with a faulty indoor board. Can I replace it with a universal AC control system?
@Ahmed.El-safty7 ай бұрын
Can it save chiller readings for a period of time for analysis?
@UATechnicalSolutions7 ай бұрын
Yes you can save file into your computer and view it anytime
@sureshkumar-fp8bl7 ай бұрын
30xa chiller what is setting MTAsetting it is FLA OR RLA.
@UATechnicalSolutions7 ай бұрын
MTA setting is for must trip amperes . In case compressor draw current morethan the mta setting it will trip the compressor Fla and rla are not controlled by MTA
Пікірлер
Very informative video… sir pls upload a video regarding Trane chiller RTAC Communication how it’s works.
Thank for nicely demonstrating.
Thank you for the video
Pleaee Mark the gas suction & Discharge point, & how does conimizer work
Thanks for your request. Click on the link for economizer function and operation. kzread.info/dash/bejne/i594l8pmldewgM4.htmlsi=IG83UbrMgWBuLvuU Share your email address for the suction and discharge point explanation
Большое Спасибо за предоставленный материал!
пожалуйста
Большое Спасибо за предоставленный материал!!!
🎉🎉🎉🎉🎉
nice...
I've seen some of those sensors can be calibrated. Have you tried that?
Generally there is no need for Calibration. As they come factory calibrated. Incase there is doubt of wrong output from sensor it can be tested on calibration tool.
Nice videos! Keep the good work! Are you planning any future videos on vsd?
Yes we are starting with carrier 30kav training course very soon.
How to check igbt York vsd chiller
What is the chiller model?
Yes .. normal useful video ... No blabols... Just data strict .. Nice vid
Very helpful, thank you
Quantity of oil 30xa 902
What is the tonage capacity of compressors?
Medel number:06TUA483SW1C
Reference oil of compressor plz
Synthetic oil sw220
@@UATechnicalSolutions thank you
Hi Sir, In a carrier 30 XA chiller, when is there a need to replace an oil level switch ( float switch), can you please explain exactly. Regards Derek
Hello. The oil level switch works ok dry contact principal. If the oil level is good in the chiller oil level switch contact should be closer. In case oil level is ok and oil level switch contact is open then replace the switch
@@UATechnicalSolutions Sir, I appreciate your prompt help. I'm dealing with a 30XA0302 carrier chiller. I can't figure out the chiller tonnage as I'm new to it
Thanks for your help
😮
❤
+++ !
can you go over understanding the prints on an AHU. How to know exactly where devices are going on the ahu by looking at the print
Sure, will upload a video soon .
What about when you get the "unable to read from selected device" error on a new sensor and nothing seems to make it read? It says it's not communication but I can turn the LEDs on and off.
Tengo el servitool pero no logro conectarme a mi chiller, puedes ayudarme?
Please make more videos of full training of trane rtac and centravac centrifugal chillers thanks.
Sure
👍
Looks like through hole type.
kzread.info/dash/bejne/ZmVtudGIoK21ecY.htmlsi=kPAxlwfPzPD4fTvz
I need help mcs 500 software how to use
Sorry, please, how can I download Tech View version 17 and be grateful to you
You can only access it if you are a Trane representative
if someone need KestrelView and Tracer TU, you can contact me.
Thanks a lot for the content
Always welcome
How to remove copper winding
How many days does it take to change chiller oil?
The simple answer is between 1 to 3 days. Here is the detailed answer. It depends on the chiller size and type. For air cooled chillers oil separator is accessible. You can just pump down the chiller and drain oil. Change oil filter and change oil in just 1 days. But if the chiller doesn’t have valve to isolate or pumping down is not possible than you have to add 2 extra days for refrigerant recovery and vacuum.
Maybe you can recover refrigerant and change the oil in the first day, changing the oil at the beginning of evacuation phase, then left the vacuum pump overnight to pickup evacuation results next morning. Used to use two 12 CFM vacuum pumps whenever possible
How can we change cards of EEV.... when not find same type. Like we change it from danfoce to sporlan
As far the valve specifications i.e Volatge Steps Hertz Milli amps Are same as the old one you dont need to change the card Secondly its not possible to install another type of card . As the rest of the cards in the chiller will not communicate with new type of card. If you are replacing the card is must be same as old
Very good explanation
Thank you.
Can you please tell me the override error in 30xA080-501 Air cooled liquid chiller
Please confirm what is the alarm code showing in the display? Or its just showing override ??
👌
2
Al-Molhaq company for HVAC solutions
En español
A chillar a otra parte
transistor is a current driven device . mosfet is voltage controlled
You can access trane techview if you are a trane tech or rep.
Where can i download techview?????
Thanks❤
Where can I download Techview?
kzread.info/dash/bejne/iqt3yaqRltSalps.htmlsi=VkSs1UjswAuENgph
Plz create the video in ism card faults and how to repair
please provide the actual name of the card and chiller model
@@UATechnicalSolutions :- carrier 19xrv chiller ISM .
Change adapter 12v can use?
yes you can as far the voltage are not more than 12v
I have a 1 HP inverter air conditioner with a faulty indoor board. Can I replace it with a universal AC control system?
Can it save chiller readings for a period of time for analysis?
Yes you can save file into your computer and view it anytime
30xa chiller what is setting MTAsetting it is FLA OR RLA.
MTA setting is for must trip amperes . In case compressor draw current morethan the mta setting it will trip the compressor Fla and rla are not controlled by MTA