  • @saahilraeen7590
    @saahilraeen759020 сағат бұрын

    Very informative video… sir pls upload a video regarding Trane chiller RTAC Communication how it’s works.

  • @manishgupta-ff4oj
    @manishgupta-ff4oj3 күн бұрын

    Thank for nicely demonstrating.

  • @hectortorres542
    @hectortorres5426 күн бұрын

    Thank you for the video

  • @sujon3130
    @sujon313015 күн бұрын

    Pleaee Mark the gas suction & Discharge point, & how does conimizer work

  • @UATechnicalSolutions
    @UATechnicalSolutions15 күн бұрын

    Thanks for your request. Click on the link for economizer function and operation. kzread.info/dash/bejne/i594l8pmldewgM4.htmlsi=IG83UbrMgWBuLvuU Share your email address for the suction and discharge point explanation

  • @IgorBond
    @IgorBond17 күн бұрын

    Большое Спасибо за предоставленный материал!

  • @UATechnicalSolutions
    @UATechnicalSolutions17 күн бұрын

    пожалуйста

  • @IgorBond
    @IgorBond22 күн бұрын

    Большое Спасибо за предоставленный материал!!!

  • @AliBekn1784
    @AliBekn178423 күн бұрын

    🎉🎉🎉🎉🎉

  • @spicky2966
    @spicky296625 күн бұрын

    nice...

  • @kevinmithnick9993
    @kevinmithnick9993Ай бұрын

    I've seen some of those sensors can be calibrated. Have you tried that?

  • @UATechnicalSolutions
    @UATechnicalSolutionsАй бұрын

    Generally there is no need for Calibration. As they come factory calibrated. Incase there is doubt of wrong output from sensor it can be tested on calibration tool.

  • @kevinmithnick9993
    @kevinmithnick9993Ай бұрын

    Nice videos! Keep the good work! Are you planning any future videos on vsd?

  • @UATechnicalSolutions
    @UATechnicalSolutionsАй бұрын

    Yes we are starting with carrier 30kav training course very soon.

  • @sonusomarajan1735
    @sonusomarajan1735Ай бұрын

    How to check igbt York vsd chiller

  • @UATechnicalSolutions
    @UATechnicalSolutionsАй бұрын

    What is the chiller model?

  • @patrikreksa1063
    @patrikreksa1063Ай бұрын

    Yes .. normal useful video ... No blabols... Just data strict .. Nice vid

  • @avithamosi2061
    @avithamosi2061Ай бұрын

    Very helpful, thank you

  • @mohsinelotfi5298
    @mohsinelotfi5298Ай бұрын

    Quantity of oil 30xa 902

  • @UATechnicalSolutions
    @UATechnicalSolutionsАй бұрын

    What is the tonage capacity of compressors?

  • @mohsinelotfi5298
    @mohsinelotfi5298Ай бұрын

    Medel number:06TUA483SW1C

  • @mohsinelotfi5298
    @mohsinelotfi5298Ай бұрын

    Reference oil of compressor plz

  • @UATechnicalSolutions
    @UATechnicalSolutionsАй бұрын

    Synthetic oil sw220

  • @mohsinelotfi5298
    @mohsinelotfi5298Ай бұрын

    @@UATechnicalSolutions thank you

  • @derekprreira3214
    @derekprreira32142 ай бұрын

    Hi Sir, In a carrier 30 XA chiller, when is there a need to replace an oil level switch ( float switch), can you please explain exactly. Regards Derek

  • @UATechnicalSolutions
    @UATechnicalSolutions2 ай бұрын

    Hello. The oil level switch works ok dry contact principal. If the oil level is good in the chiller oil level switch contact should be closer. In case oil level is ok and oil level switch contact is open then replace the switch

  • @derekprreira3214
    @derekprreira32142 ай бұрын

    @@UATechnicalSolutions Sir, I appreciate your prompt help. I'm dealing with a 30XA0302 carrier chiller. I can't figure out the chiller tonnage as I'm new to it

  • @ShakirKhan-kp9ny
    @ShakirKhan-kp9ny2 ай бұрын

    Thanks for your help

  • @user-cs6ew2nn6d
    @user-cs6ew2nn6d2 ай бұрын

    😮

  • @user-cs6ew2nn6d
    @user-cs6ew2nn6d2 ай бұрын

  • @user-cs6ew2nn6d
    @user-cs6ew2nn6d2 ай бұрын

    +++ !

  • @Walkingrelaxing
    @Walkingrelaxing2 ай бұрын

    can you go over understanding the prints on an AHU. How to know exactly where devices are going on the ahu by looking at the print

  • @UATechnicalSolutions
    @UATechnicalSolutions2 ай бұрын

    Sure, will upload a video soon .

  • @1shagg420
    @1shagg4203 ай бұрын

    What about when you get the "unable to read from selected device" error on a new sensor and nothing seems to make it read? It says it's not communication but I can turn the LEDs on and off.

  • @cazuica
    @cazuica3 ай бұрын

    Tengo el servitool pero no logro conectarme a mi chiller, puedes ayudarme?

  • @UmarKhan-mb2lm
    @UmarKhan-mb2lm3 ай бұрын

    Please make more videos of full training of trane rtac and centravac centrifugal chillers thanks.

  • @UATechnicalSolutions
    @UATechnicalSolutions3 ай бұрын

    Sure

  • @KuyaGomzTv
    @KuyaGomzTv3 ай бұрын

    👍

  • @ernieschatz3783
    @ernieschatz37833 ай бұрын

    Looks like through hole type.

  • @javeedhvactechnician7760
    @javeedhvactechnician77603 ай бұрын

    kzread.info/dash/bejne/ZmVtudGIoK21ecY.htmlsi=kPAxlwfPzPD4fTvz

  • @sonusomarajan1735
    @sonusomarajan17354 ай бұрын

    I need help mcs 500 software how to use

  • @user-ts2nd9qy1m
    @user-ts2nd9qy1m4 ай бұрын

    Sorry, please, how can I download Tech View version 17 and be grateful to you

  • @UATechnicalSolutions
    @UATechnicalSolutions3 ай бұрын

    You can only access it if you are a Trane representative

  • @user-yo8om6cv2j
    @user-yo8om6cv2j4 ай бұрын

    if someone need KestrelView and Tracer TU, you can contact me.

  • @user-ze7tg8ch4v
    @user-ze7tg8ch4v4 ай бұрын

    Thanks a lot for the content

  • @UATechnicalSolutions
    @UATechnicalSolutions4 ай бұрын

    Always welcome

  • @whatyouwant7633
    @whatyouwant76334 ай бұрын

    How to remove copper winding

  • @md.shahid4305
    @md.shahid43055 ай бұрын

    How many days does it take to change chiller oil?

  • @UATechnicalSolutions
    @UATechnicalSolutions5 ай бұрын

    The simple answer is between 1 to 3 days. Here is the detailed answer. It depends on the chiller size and type. For air cooled chillers oil separator is accessible. You can just pump down the chiller and drain oil. Change oil filter and change oil in just 1 days. But if the chiller doesn’t have valve to isolate or pumping down is not possible than you have to add 2 extra days for refrigerant recovery and vacuum.

  • @kevinmithnick9993
    @kevinmithnick9993Ай бұрын

    Maybe you can recover refrigerant and change the oil in the first day, changing the oil at the beginning of evacuation phase, then left the vacuum pump overnight to pickup evacuation results next morning. Used to use two 12 CFM vacuum pumps whenever possible

  • @user-dd6eb9bo8r
    @user-dd6eb9bo8r5 ай бұрын

    How can we change cards of EEV.... when not find same type. Like we change it from danfoce to sporlan

  • @UATechnicalSolutions
    @UATechnicalSolutions5 ай бұрын

    As far the valve specifications i.e Volatge Steps Hertz Milli amps Are same as the old one you dont need to change the card Secondly its not possible to install another type of card . As the rest of the cards in the chiller will not communicate with new type of card. If you are replacing the card is must be same as old

  • @user-dd6eb9bo8r
    @user-dd6eb9bo8r5 ай бұрын

    Very good explanation

  • @UATechnicalSolutions
    @UATechnicalSolutions5 ай бұрын

    Thank you.

  • @MeandMyShadow-hg7xd
    @MeandMyShadow-hg7xd5 ай бұрын

    Can you please tell me the override error in 30xA080-501 Air cooled liquid chiller

  • @UATechnicalSolutions
    @UATechnicalSolutions5 ай бұрын

    Please confirm what is the alarm code showing in the display? Or its just showing override ??

  • @pravinsam8258
    @pravinsam82585 ай бұрын

    👌

  • @user-jd9tm4mv9p
    @user-jd9tm4mv9p5 ай бұрын

    2

  • @AlMolhaqcom1
    @AlMolhaqcom15 ай бұрын

    Al-Molhaq company for HVAC solutions

  • @joseroa2414
    @joseroa24145 ай бұрын

    En español

  • @kevinmithnick9993
    @kevinmithnick9993Ай бұрын

    A chillar a otra parte

  • @leetucker9938
    @leetucker99386 ай бұрын

    transistor is a current driven device . mosfet is voltage controlled

  • @josellesison380
    @josellesison3806 ай бұрын

    You can access trane techview if you are a trane tech or rep.

  • @NeritanShyts
    @NeritanShyts6 ай бұрын

    Where can i download techview?????

  • @lodaalex
    @lodaalex6 ай бұрын

    Thanks❤

  • @MT-9222
    @MT-92226 ай бұрын

    Where can I download Techview?

  • @javeedhvactechnician7760
    @javeedhvactechnician77606 ай бұрын

    kzread.info/dash/bejne/iqt3yaqRltSalps.htmlsi=VkSs1UjswAuENgph

  • @sanjayverma5671
    @sanjayverma56717 ай бұрын

    Plz create the video in ism card faults and how to repair

  • @UATechnicalSolutions
    @UATechnicalSolutions7 ай бұрын

    please provide the actual name of the card and chiller model

  • @sanjayverma5671
    @sanjayverma56716 ай бұрын

    @@UATechnicalSolutions :- carrier 19xrv chiller ISM .

  • @_--_Iskandar58_--_
    @_--_Iskandar58_--_7 ай бұрын

    Change adapter 12v can use?

  • @UATechnicalSolutions
    @UATechnicalSolutions7 ай бұрын

    yes you can as far the voltage are not more than 12v

  • @kingdesmond3909
    @kingdesmond39092 ай бұрын

    I have a 1 HP inverter air conditioner with a faulty indoor board. Can I replace it with a universal AC control system?

  • @Ahmed.El-safty
    @Ahmed.El-safty7 ай бұрын

    Can it save chiller readings for a period of time for analysis?

  • @UATechnicalSolutions
    @UATechnicalSolutions7 ай бұрын

    Yes you can save file into your computer and view it anytime

  • @sureshkumar-fp8bl
    @sureshkumar-fp8bl7 ай бұрын

    30xa chiller what is setting MTAsetting it is FLA OR RLA.

  • @UATechnicalSolutions
    @UATechnicalSolutions7 ай бұрын

    MTA setting is for must trip amperes . In case compressor draw current morethan the mta setting it will trip the compressor Fla and rla are not controlled by MTA