  • @blue7334
    @blue73347 күн бұрын

    Hello i want to ask something in my device i can added 2 card and when i want to add the third one it does not work do you have any information about this could help me please ? Info > the card is working but the device doesn’t allow me to add more than 2 help please):

  • @YorkshireAutomation
    @YorkshireAutomation7 күн бұрын

    @blue7334 it has capacity of the 3rd card is not adding. Try to do a reset and add the cards again. Otherwise you may need to change the key pad

  • @mar4elo999
    @mar4elo9998 күн бұрын

    Hi, I wonder if you could help I just connected PV2 - another set of 4 solar panels, to existing 12 panels (pv1) do I need to change any settings? I have only changed settings to pv - 2 separate connections, options were given separate or paralel, I selected 2 separate. I hope my question makes sense, I am new to all this. Thanks in advance

  • @YorkshireAutomation
    @YorkshireAutomation8 күн бұрын

    @@mar4elo999 that's correct settings. So should be ok

  • @mar4elo999
    @mar4elo9998 күн бұрын

    @YorkshireAutomation It looks like the inverter has adopted and started to produce. Thanks for your reply! 🙌

  • @darrellhooper9973
    @darrellhooper997310 күн бұрын

    Very informative.... if my car charges 0030-0530, how do I get the battery to charge at the same time? It seems to empty the battery instead of charging both! Thanks

  • @YorkshireAutomation
    @YorkshireAutomation10 күн бұрын

    you need to enable the AC Charge option and set the time 0030 to 0530. this way it will simultabeously charge both car and batteries.

  • @dawoodrecitation
    @dawoodrecitation18 күн бұрын

    Hi How to disable the zone control ?

  • @YorkshireAutomation
    @YorkshireAutomation18 күн бұрын

    Just delete the specific zone in the climate panel OR if just temporarily you can just switch to manual mode

  • @lescrawford2650
    @lescrawford265020 күн бұрын

    Thank you for your help, am i right in thinking that two batteries and inverters in parallel will give my home 10kwh so we can run multiple appliances at the same time. Such as a kettle 2.8kw, 2x industrial iron's 3kw each as my wife works from home and uses a lot of energy.

  • @YorkshireAutomation
    @YorkshireAutomation20 күн бұрын

    Again it depends on the inverters/charge controllers. If they are 5kw rated then yes, in parallel they will give you 10kw

  • @lindamilton1521
    @lindamilton152122 күн бұрын

    Thanks for replying. I decided to do the obvious and switch off all batteries and my LuxPower unit for 5 minutes. It all worked perfectly after turning back on. Your video was very helpful. Thanks.

  • @lindamilton1521
    @lindamilton152125 күн бұрын

    In the last few days my pylontech batteries will only charge to 87% from the grid during my 7 hours of low price time at night and shows a red light on what i think is the master battery. (They always charged to 100% before that). I have the On-grid Cut-off set to 10% as set by my installer but the day this fault started the SOC went down to 9%. Could that have been the cause of the problem? However they will then charge to 100% later in the day when the solar panels kick in and no red light. Any suggestions for a solution? Thank you

  • @YorkshireAutomation
    @YorkshireAutomation22 күн бұрын

    i would suggest getting back in touch with your installer to take a look at the batteries. you shouldnt be getting any alarm lights at all, and this is what is probably causing the reduced charge

  • @saliaaugustine932
    @saliaaugustine93226 күн бұрын

    What if I had the image of the card in my phone, could i be able to open the door 🚪 using the image of the card on my phone?

  • @YorkshireAutomation
    @YorkshireAutomation22 күн бұрын

    no. rfid is a radio frequency

  • @saliaaugustine932
    @saliaaugustine93218 күн бұрын

    @@YorkshireAutomation Thank you dear

  • @sweetsandnuts
    @sweetsandnutsАй бұрын

    i had a power failure at Easter. Since then i can not get the battery to connect properly to the lux inverter. using a Pylontech battery I would appreciate any help

  • @sweetsandnuts
    @sweetsandnutsАй бұрын

    Thank u for the settings, i really messed mine up not knowing what to do

  • @preciousamaristelva2599
    @preciousamaristelva2599Ай бұрын

    Idol pwede din bang nag set up ng card kahit hindi mo na babaguhain ang lock code at system code?

  • @stephenmugglestone9784
    @stephenmugglestone97842 ай бұрын

    How do you set the max battery capacity to less than 100%?

  • @YorkshireAutomation
    @YorkshireAutomation2 ай бұрын

    Under charge settings, SYSTEM CHARGE SOC % - this is set to 100% - this means the solar will charge it to 100%. This is separate to the AC Charge settings

  • @pitiwatkittiwimonchai4656
    @pitiwatkittiwimonchai46562 ай бұрын

    may i ask some questions please. 0. I just saw luxpowertek inverter model SNA6000W on internet. 1. can this inverter sync electricity come from solar cell/battery and grid. (i mean use both of electricity from solar cell/battery and grid in same time. ex. house load = 6kw and inverter can divide into 3kw from solar cell/battery + 3kw from grid) 2. this inverter can schedule/program charging/discharging time right ? lastly in my country it's so fuxk shit (bad) when i want to sell electric from my own solar cell.

  • @YorkshireAutomation
    @YorkshireAutomation2 ай бұрын

    Hi i believe that all luxpowertek have the same software. the model number you have asked isnt a UK model so i cant comment on the the different regulations that you may have. Its best to ask a local installer re if the inverter is grid tied or off-grid

  • @pitiwatkittiwimonchai4656
    @pitiwatkittiwimonchai46562 ай бұрын

    @@YorkshireAutomation Thx for feedback sir.

  • @Bigglesworth-jv9iw
    @Bigglesworth-jv9iw2 ай бұрын

    Any chance of a video doing a setup that fits the Octopus Flux tariff with set ups for charge and discharge and after discharge leaving enough battery charge to get through the night.

  • @YorkshireAutomation
    @YorkshireAutomation2 ай бұрын

    octopus flux is just charging between 2am and 5am. but for discharge that varies between household to household. you would need to guage how much energy you need to take you through the night and set the STOP DISCHARGE SOC accordingly. i have talked about that in the video

  • @Bigglesworth-jv9iw
    @Bigglesworth-jv9iw2 ай бұрын

    Great video and much needed. I think your video is already out of date as under charge setting their is now a System Charge SOC Limit % - Not fully sure what this implies i.e is this 100 % charge to achieve SOC percentage?

  • @YorkshireAutomation
    @YorkshireAutomation2 ай бұрын

    yes fortunately and unfortunately... at least they are updating the software and adding features and fixing bugs!

  • @lescrawford2650
    @lescrawford265020 күн бұрын

    Hi, I have an 18.8 kw battery, what size lux inverter do I need to force charge and discharge the battery in the 3hr windows on octopus flux.tia

  • @YorkshireAutomation
    @YorkshireAutomation20 күн бұрын

    @@lescrawford2650 most of the charge/discharge rates are 3.5kw. so the only option you have is the squirrel pod option. Setup 2 in parallel and have the batteries split between the 2. This will then give 100% in 3 hrs

  • @xxXCoolJokeXxx
    @xxXCoolJokeXxx2 ай бұрын

    whats the difference between forced discharge and system discharge. my battery discharged overnight, i wanted it to remain as backup and switch to grid when the sun goes out..

  • @YorkshireAutomation
    @YorkshireAutomation2 ай бұрын

    Force discharge is when the lux will just discharge at max rate (unless reduced in settings) irrespective of the load so useful if you have export tariff. System discharge will only discharge what the house needs giving zero export. If you want to keep the batteries topped up in evening them use charge priority for those hours OR set up a charging schedule for those hours but keep %level to a low level so it doesn't use grid to charge up.

  • @FIBAROofficial
    @FIBAROofficial2 ай бұрын

    While this is an interesting video in terms of presented knowledge, we would like to officially state that this kind of access is not recommended. It can decrease security level of your system and could give unauthorized people open access to your Home Center. The cloud service works as a gatekeeper and uses data assigned to a specific cloud account. It is not the matter of how easy or difficult it would be for a person to access your system, but rather a fact that the presented solution makes it significantly more possible.

  • @YorkshireAutomation
    @YorkshireAutomation2 ай бұрын

    Hi thanks for your comments. As stated in the video there are risks associated with this but a couple of clients wanted access without cloud due to issues. so this video was made as a guide for them. i recommend that only those who know what they are doing to use this guide.

  • @storm_shadows
    @storm_shadows3 ай бұрын

    Good video Is the code still available somewhere

  • @YorkshireAutomation
    @YorkshireAutomation3 ай бұрын

    www.yorkshireautomation.uk/product-page/remotec-zrc90-lua-code is the webshop item. Just visit and download for £5!

  • @JasperWaale
    @JasperWaale4 ай бұрын

    Oh, do you have to go to each device and uncheck? I have just got a hc3 and Aroyec Gen5 power meter, and its not only listed as double the devices I have and I figure have to go to each and hide it? but see has 2 core master device why dont the " slave" follow that settings also for the events stuff ?

  • @YorkshireAutomation
    @YorkshireAutomation4 ай бұрын

    I actually don't use the energy panel but yes I would have had to uncheck each device and use the aeotec only. Also the as I have the 3 phase version I got 4 sets of devices. The 1st set is all 3 added together so I just hid them. Then the other 3 sets I kept the power only visible and hid the others

  • @JasperWaale
    @JasperWaale4 ай бұрын

    wondering how you monitor house power use

  • @YorkshireAutomation
    @YorkshireAutomation4 ай бұрын

    I have the Aeotec HEM gen5 meter. I have the 3 phase version. So 3 clamps to measure the House Consumption, Grid Import, and Solar Production. As long as you have a separate fuse box for house and solar then we can differentiate.

  • @justbrowsing7565
    @justbrowsing75654 ай бұрын

    I currently have two Pylontech US5000. I am going to add another two. What settings do I need to change in the Lux Power app to add these?

  • @YorkshireAutomation
    @YorkshireAutomation4 ай бұрын

    there are no settings in the app that need chagning. Once you have added the batteries and adjusted the dip switch settings on the master battery and slave batteries this is automatically picked up. Speak to your Pylontech supplier/installer re the dip settings

  • @justbrowsing7565
    @justbrowsing75654 ай бұрын

    @YorkshireAutomation thanks. Currently on my batteries they're both set to all be up.i assumed the new two I put to be up also? So they're all up?

  • @YorkshireAutomation
    @YorkshireAutomation4 ай бұрын

    i do a lot of greenlinx batteries and not Pylontech - theres a setting on the master to let it know how many slaves are connected and also ID of each battery. I think its on a dial with some numbers on it that you have to adjust - sorry but cant help more on that as i havent done Pylontech

  • @justbrowsing7565
    @justbrowsing75654 ай бұрын

    @YorkshireAutomation ok thank you very much I will have a read of the manual

  • @user-jk2yx5jg2u
    @user-jk2yx5jg2u4 ай бұрын

    The motion sensor is blinking red. I initialized it and uninstalled it from the home center. I tried putting it in listening mode, and it stayed solid blue without blinking. In the end, I couldn't add it again. Do you know why it behaves this way?

  • @YorkshireAutomation
    @YorkshireAutomation4 ай бұрын

    Hi you need to exclude it. So put your controller in Exclusion mode and triple click the B button that should reset the sensor. Any controller can reset the sensor. once done just add it back in.

  • @user-jk2yx5jg2u
    @user-jk2yx5jg2u4 ай бұрын

    @@YorkshireAutomation Thank you for the prompt response. I've already done that; the sensor is no longer in the home center, but it still maintains the slow red blinking.

  • @YorkshireAutomation
    @YorkshireAutomation4 ай бұрын

    possibly battery needs replacing? Also is the home centre and motion sensor in the same zwave frequency? if all is ok then more than likely the motion sensor has become faulty

  • @user-jk2yx5jg2u
    @user-jk2yx5jg2u4 ай бұрын

    @@YorkshireAutomation Thank you for responding. Changing the battery was one of the first things I did. The sensor had been working fine for a while. Most likely, the device is damaged. Thank you for your response and assistance. Do you have an email or contact number?

  • @YorkshireAutomation
    @YorkshireAutomation4 ай бұрын

    Hi. [email protected] Mobile/Whastaapp is +447946591533 thanks

  • @robindraycott7844
    @robindraycott78444 ай бұрын

    Might be better if you don't have someone shredding bags of crisps in the background..?

  • @laszlopecsy934
    @laszlopecsy9344 ай бұрын

    It seems to be cool! Thanks for your video! Could you provide the scene settings for heating and cooling a zone?

  • @YorkshireAutomation
    @YorkshireAutomation4 ай бұрын

    It's individual so it depends what you have in your system. Generally Temp sensor to measure temp A thermostat to sync to climate panel. Then check if temp is below the setpoint. When below the temp then change variable for that room. Then another scene to check all variables before turning the boiler switch on or off in case of heating or activate the AC

  • @laszlopecsy934
    @laszlopecsy9344 ай бұрын

    @@YorkshireAutomation Thanks a lot, it helps me! I have almost the same system as yours just with fewer zones (and currently without any air conditioning) :)

  • @darrencareford3003
    @darrencareford30034 ай бұрын

    Hi, trying to follow your video to achieve the same, could you clarify a few things for me? The COM connects to int1 yellow cable? NO connects to Blue GND, does it matter which Blue GND as the implant has two? Thanks in advance for any help.

  • @YorkshireAutomation
    @YorkshireAutomation4 ай бұрын

    Doesn't matter which blue as they both the same. They have supplied 2 lots so we don't have to do ourselves

  • @neilp7024
    @neilp70244 ай бұрын

    HI thanks for the video - i have just had the Lux lxp3600acs and 2 x 3.2 kw batteries by green link (home ess-lv- 3.2 k) installed the lag on solar production reading via this app is woeful and tbh i`m really dissapointed with it !! just wondering if there is a way of getting a live reading from the inverter etc via the app ....i have another system that is far better (owl) and this is pretty much live...i`d say a lag of 3 seconds ...i have used the owl system to monitor my solar for the last 7 years and i thought this app would be far superior but sadly its not...anyway once again thanks for posting this video as its far better than the ones made by lux.Oh btw i i have used the refresh button on the app and it does work but wondered if there is a way to use live?

  • @samgirt7459
    @samgirt74594 ай бұрын

    Hi - Is it possible to have a lower rate of charge when using the grid over night but maintain full charge speed during the day? I've tried amending the grid charge option but noticed my system was also limiting my solar charging during the day!

  • @YorkshireAutomation
    @YorkshireAutomation4 ай бұрын

    Yes, only adjust the %charge rate inside the AC CHarge Time area. that will then adjust only grid charging and not solar charging

  • @samgirt7459
    @samgirt74594 ай бұрын

    Ah I'm using the app and I don't have that option. It saves 'Grid charge rate' and 'AC charge level' as my options. I'll try to see if I can log into the browser

  • @samgirt7459
    @samgirt74594 ай бұрын

    I checked on the website and its actually the same setting but with a different name. When I adjust it for some reason it was still limiting my charging through the day today from the panels.

  • @YorkshireAutomation
    @YorkshireAutomation4 ай бұрын

    @@samgirt7459 Under Charge settings SYSTEM CHARGE POWER RATE (%) - Keep at 100% under the AC CHARGE thats separate

  • @samgirt7459
    @samgirt74594 ай бұрын

    @YorkshireAutomation Yeah that's what it's set to. It charges overnight at 50% rate fine, then today I noticed I was exporting half the power generation and the limit was also impacting my solar charging. I'll check again tomorrow. Maybe it was lagging a bit and I didnt give it chance to amend itself while I was testing

  • @deanharrysmith718
    @deanharrysmith7185 ай бұрын

    Great Video, I do have a quick question. I am on a Luxpower hybrid 8-10K inverter with 2 x 10Kw Hanchu Batteries, I am on Octopus Flux and with flux I have setup the batteries in the inverter config to charge them between 2am and 5am as it's really cheap. Is there a reason why when the batteries get fully charged say approx 4am the inverter does not swap over to batteries but keeps pulling current from the grid right up to 5am and then swaps onto batteries.

  • @YorkshireAutomation
    @YorkshireAutomation5 ай бұрын

    That's because you have specified to charge them from.2am to 5am and so they will remain in charge mode only. They cannot work in both modes simultaneously. If you know that they regularly get to 100% by 4am then amend them charging schedule to 2am.to 4am instead .

  • @user-shandyman
    @user-shandyman5 ай бұрын

    Thanks for the explanation. Very helpful. I currently don’t have solar but am considering this. The company that has quoted me have no knowledge of Lux inverters. I have 2 squirrel pods. To add solar to charge my batteries i understand we need to add a CT clamp on the primary Lux inverter that sees the power on the live of the PV inverter. The solar installer is thinking the CT clamp needs an Eastron SDM120CT. Is this correct?

  • @YorkshireAutomation
    @YorkshireAutomation5 ай бұрын

    Hi No it's a standard CT clamp similar to the one that you already have that is monitoring the grid. You will then only need a PV string inverter and not a hybrid inverter. If unsure give me a call for a chat on 07946 591533. Thanks

  • @Zangettsu_ZA
    @Zangettsu_ZA5 ай бұрын

    We've installed a LuxPower hybrid solar inverter in our security estate in South Africa due to our country not having electricity for 12 hours of the day from the grid. At home I have a Victron system whereby I can just set the SOC to say 40% and the system will use the battery power at night when the sun is down and discharge to that setting before the grid is allowed to be used. Should the grid be out during Loadshedding (rolling blackouts) the batteries can dip below 40%. This is simple. But I have not yet figured out how to get this to work on the LuxPower inverter. The grid was out for 2 hours tonight and the battery discharged from 100% to 95% in that time. Now the battery remains at 95% while it is using grid power. There is enough battery capacity for our estate's security systems to be up all the time on the battery, after which the battery will recharge via solar again starting in the morning. Does anyone know how to set the LuxPower inverter to operate as with my Victron described above?

  • @YorkshireAutomation
    @YorkshireAutomation5 ай бұрын

    i believe that in order to get the Lux to behave in the off-grid format needs your installer/distributor to change some settings for it to do that. As far as i know the defaut setting is as grif-tied

  • @Zangettsu_ZA
    @Zangettsu_ZA5 ай бұрын

    @@YorkshireAutomation Ah thanks. I actually managed to figure it out. The interface seems a bit different than in your videos. On our inverter's maintenance page you can now set the Charge to take place within Timers, like it used to be, or set it to a certain SOC, or in fact, a combination of both. The first evening with the new settings the batteries reached their SOC setting at around 2 am, however the grid was off between 2am and 6am. So unfortunately the battery depleted and our security to our estate went dark. I then tweaked the settings again and last night it worked. When the grid came back around 6am there was still 50% of the battery left. And shortly after the sun was out and started charging the battery. So, it seems like there was a firmware upgrade which added the SOC setpoint, which in my opinion works 100% better than timers. Especially if you have an unstable grid like us where your power can go off without any notice.

  • @user-zx4kw5lo8y
    @user-zx4kw5lo8y5 ай бұрын

    @YorkshireAutomation this was genuinely a really helpful video and much better than the manufacturers literature and efforts. Perhaps a silly question but what does "Power Backup Enable" do? Is it possible to configure the system to run the house during the power cut? Or can you only wire a socket on to the battery for smaller items to use?

  • @YorkshireAutomation
    @YorkshireAutomation5 ай бұрын

    thanks for your comments. the system can run the house when there is a power cut but it has to be connected to the EPS outoput port of the Lux. You would need an electrician to wire in and make sure it complies with the electical regulations. Thanks

  • @user-zx4kw5lo8y
    @user-zx4kw5lo8y5 ай бұрын

    I think I read it couldn't power the house unless there was a gateway or something to stop electricity going the wrong way into the grid. Does the lux Inverter work as a gateway? I suspect it doesn't and the EPS outlet will only power some sockets and can't be connected to the whole house. Nonetheless, many thanks for your help!

  • @YorkshireAutomation
    @YorkshireAutomation5 ай бұрын

    @@user-zx4kw5lo8y the eps is connected indepently from the existing house. so the circuits are wired into a consumer unit directly fed from the EPS port. it has nothing to do with the grid. When grid is active then power is bypassed thruogh charge controller and into eps. when no grid then power is supplied via batteries. at no point is there a back-feed into the grid

  • @tomasjacko9534
    @tomasjacko95346 ай бұрын

    Hello, I would like to do scene but it doesnt work as I want. I want scene in my bathroom where: Between 10:00 pm and 6:00 am is by detected motion light turned on only to 5% This works for me. But in the other times, i want it to reset settinings of brithness back to 100% because when I turned on light manually by switch, it is still only on 5%. Can you help how to reset in these other times light back to 100%?

  • @YorkshireAutomation
    @YorkshireAutomation6 ай бұрын

    Hi best to send me an email and we can book an online session

  • @tomasjacko9534
    @tomasjacko95346 ай бұрын

    Done. Please reply@@YorkshireAutomation

  • @mirk4work2
    @mirk4work26 ай бұрын

    What does S O C mean?

  • @YorkshireAutomation
    @YorkshireAutomation6 ай бұрын

    State of Charge

  • @nguyenminhvu5947
    @nguyenminhvu59477 ай бұрын

    webshop free?

  • @YorkshireAutomation
    @YorkshireAutomation7 ай бұрын

    There is nothing to buy for this. This is just free advice

  • @GracesterTime
    @GracesterTime6 ай бұрын

    Mine doesnt work , i unfortunately update to beta version and now i have been trying to update to the newer version but still doesnt work. 🥲 any idea?

  • @YorkshireAutomation
    @YorkshireAutomation6 ай бұрын

    ​@GracesterTime you will have to download the firmware manually and use the recovery process to update to latest firmware. There is a post on this on the main fibaro forums

  • @GracesterTime
    @GracesterTime6 ай бұрын

    Thank you so much! I succesfully updated the software. Now i just need to find out why all my devices loose connections. I tried to re conect but not it says “ transfered failed’” sorry i have many questions 😅 do you have any idea on how i can connect my devices back?

  • @YorkshireAutomation
    @YorkshireAutomation6 ай бұрын

    @@GracesterTime send me an email and will discuss further [email protected]

  • @Veranda4M
    @Veranda4M7 ай бұрын

    can you help me to add some devices into my hc3?

  • @YorkshireAutomation
    @YorkshireAutomation7 ай бұрын

    Hi Yes. Just contact me via email on [email protected]

  • @johnjameson4956
    @johnjameson49567 ай бұрын

    Why does this need an app? You can do it easily enough with a block scene, don't even need LUA.

  • @YorkshireAutomation
    @YorkshireAutomation7 ай бұрын

    it was a request from a client who wanted to be able to amend the temps from the phone. but in block scene as the temp is read and goes above the max temp OR if falls below the min temp the system will keep sending push notificaions to you. This QA only sends a single notification until it switches to the opposite

  • @johnjameson4956
    @johnjameson49567 ай бұрын

    Ah, fair enough. In my application the low temp warning will relate to a probable boiler failure so I'm not averse to multiple warnings.

  • @sokusziu
    @sokusziu7 ай бұрын

    Many thanks for this informative video. We have just added another 3 Pylontech batteries to our LuxPower Invertor. What do we have to do to see these on the app please?

  • @YorkshireAutomation
    @YorkshireAutomation7 ай бұрын

    They will automatically appear on the app provided they have been configured and connected correctly to your existing setup.

  • @sokusziu
    @sokusziu7 ай бұрын

    @@YorkshireAutomation Many thanks for your quick reply! It's hard to tell from the app as it doesn't show the amount of charge in kWh just W (which says 30W) and 50.0Vdc and I haven't a clue what this means!

  • @sokusziu
    @sokusziu7 ай бұрын

    Everything seems to be working ok - all lights on and no error message

  • @YorkshireAutomation
    @YorkshireAutomation7 ай бұрын

    @sokusziu have you waited for at least 5 mins for the server to update? Also has the master been set to the new number of batteries? Have the slave batteries also been set?

  • @sokusziu
    @sokusziu7 ай бұрын

    @@YorkshireAutomation yes ir's been about an hour. How do I change the master (what/where is the master? On the app?) I don't know what you mean by slave batteries, sorry!

  • @BoBrondum
    @BoBrondum8 ай бұрын

    I can highly recommend this QuickApp (QA) and the ClickSend Service that sends SMS in case of an Alarm or other trigger. However, I caution using to long an "Id". In this case “myHC3” is used and that works fine. Configuring a lengthy "Id" gave me problems. Initially I had configured the “Id” with a rather long name and did not receive any messages. I have no idea what the limit is. Note: SMS are received almost without a reference to the Prefix. For Denmark I can use 0045, +45 or no Prefix at all in front f my number and still recieve messages.

  • @mortexist
    @mortexist8 ай бұрын

    Hi, thanks for the video. I have a Lux system installed with a Lux 6000 hybrid inverter and a Greenlinkx battery. Based on the specs of the inverter it seems that it could be fitted with an automation so that if the grid power gets down the solar system can disengage the grid and continue to feed the house and function from solar and battery alone - as long as there is enough power generated or available in the batteries . However, the installer said he cannot fit it that way. Do you know if there is any after market option to make it this way?

  • @YorkshireAutomation
    @YorkshireAutomation8 ай бұрын

    He is correct. The system does have EPS mode but they will have to re-wire existing house circuits through the hybrid inverter and also make provision for an external earth rod too.

  • @mortexist
    @mortexist8 ай бұрын

    @@YorkshireAutomation Thanks. I suspected that. They don't know how to. I have an idea, but I am not an authorized electrician. Would this modification be something that you would do, or be interested to take on a contract ?

  • @YorkshireAutomation
    @YorkshireAutomation8 ай бұрын

    @@mortexist please contact me via email or call 07946591533 or [email protected]

  • @theoccupier675
    @theoccupier6758 ай бұрын

    Hi, is there a way to set the start % for charging, as during the spring and summer months my batteries will go through the night and start charging via solar in the morning. So if the battery percentage was below 40% the inverter could charge them to 70%, thanks

  • @YorkshireAutomation
    @YorkshireAutomation8 ай бұрын

    as far as i know the system can only be set to charge based on time and then it will check percentage. So you could set the charge level to 70% and set a time period for tfor the morning. This would mean taht even if it was at 69% it would charge for 1%. During that charge times you have set would mean that discharge is disabled. I think a third party integration would be needed for what you would like to do.

  • @ericshelver8390
    @ericshelver83908 ай бұрын

    The web interface I see on the Africa server differs a lot from your video. Not sure if different regions have different versions, but I can't apply settings as you have. My actual problem is that an inverter is set to begin AC charge with both SOC and TIME - to begin 55% SOC and Time 18:00 start to 06:00 end. It charges fine during the specified Time range but not when it reaches the SOC percentage during the day. It does, however stop discahrging at the 50% EOD SOC I have set. Is there an explanation as local Lux support are unable to provide answers as to why it's not beginning charge at the SOC 55% point?

  • @YorkshireAutomation
    @YorkshireAutomation8 ай бұрын

    From my understanding the SOC rate is the minimum SOC required. So if the SOC drops to below 55% it will charge up. However if it goes above then it wont charge at all. I can see from your email that the interface is different and you have different options to us here in UK. But as far as we know that we cannot set the batteries to charge/discharge at same time. its one or the other in that specific time frame.

  • @Tjeturner
    @Tjeturner8 ай бұрын

    Hi, thanks for this video it’s very useful. I wondering if you can help, My battery will only AC charge IF it has some charge left in. If it’s empty at (at 11% SOC) then it will not auto AC charge. Should I try increasing the on grid cut off SOC a touch do you think?

  • @YorkshireAutomation
    @YorkshireAutomation8 ай бұрын

    Hi It should still charge from AC if that is the settings you have set. I have mine set to 5% with Lux and Greenlinx batteries. 10% if lux and pylontech batteries. The only time it needs solar to charge up is if the battery voltage drops down. Best to ask your installer to take a look and escalate to tech support if they can't figure out

  • @lynussss
    @lynussss8 ай бұрын

    Can you pair a secondary secen controller such as the remotec zwave remote ?

  • @YorkshireAutomation
    @YorkshireAutomation8 ай бұрын

    Yes Once paired we write a scene that can send commands depending on what buttons are pressed. There should be videos on this already on my channel

  • @lynussss
    @lynussss8 ай бұрын

    @@YorkshireAutomation legend thankyou !

  • @billywheelspin
    @billywheelspin8 ай бұрын

    Is there any way to set the batteries to discharge at peak times, but not export to grid (only discharge for what the house is using)?I'm finding that the batteries are dumping out to grid and fully discharge before peak time has ended, therefore I'm still paying for peak time electricity towards the end of the peak time window.

  • @YorkshireAutomation
    @YorkshireAutomation8 ай бұрын

    The default setting is for the batteries to discharge only what the house needs. Unless you have enabled force discharge then it will just supply what you have specified in the settings.

  • @FrankHighlanders
    @FrankHighlanders9 ай бұрын

    Hi, is the AC CHARGE setting that I see at minute 13:20 the one that allows you to charge the batteries at night at a discounted rate and then use the battery during the day? So recharge from 11.30pm until 5.30am?

  • @YorkshireAutomation
    @YorkshireAutomation9 ай бұрын

    Yes mate that is the setting you use to set your schedule up. Just remember to press SET after each entry and enable it too.

  • @FrankHighlanders
    @FrankHighlanders9 ай бұрын

    ​@@YorkshireAutomation If it is possible to have another help.. what the button is for Quick Charge?

  • @YorkshireAutomation
    @YorkshireAutomation9 ай бұрын

    @FrankHighlanders quick charge is just that.. Just press and that's it. No need to go into settings and set times etc

  • @FrankHighlanders
    @FrankHighlanders9 ай бұрын

    @@YorkshireAutomation Recharge your batteries from the mains for an hour? Thank you

  • @YorkshireAutomation
    @YorkshireAutomation9 ай бұрын

    @FrankHighlanders I tested it and it's not a 1 hour timer. It just charges manually until.you stop it. It means you don't have to go into settings. I've edited original response

  • @akaGoolash
    @akaGoolash9 ай бұрын

    Can you provide a photo how you mount this IR devices? I'm asking as I have the similar problem right now with Haier devices. I'm trying to use the Aidoo Z-wave converters by they are not compatible with Haier :/

  • @YorkshireAutomation
    @YorkshireAutomation9 ай бұрын

    Hi My units are in the loft as they are centralised units, so the ZXT is in line of site with the receiver of the AC units

  • @akaGoolash
    @akaGoolash9 ай бұрын

    @@YorkshireAutomation so wher you mount ZXT to ceiling to be inline with the unit? I'm looking how to hide them not but some hanging stuff. In my setup right now it will be hard to mount them in line of site and keep them invisible for people :/

  • @YorkshireAutomation
    @YorkshireAutomation9 ай бұрын

    @@akaGoolash fortunately i can hide mine in loft space. In living areas i have placed my ZXT behind the sofa under the AC unit itself. So the ZXT and AC are line of site but the ZXT is behind sofa. Later in the year MCO Home are bringing out a new unit which is wall mountable and has a display with an IR sender. This is a nice looking unit for AC control too. Hopefully i will get one shortly and present it on my channel

  • @paulmott6197
    @paulmott61979 ай бұрын

    Very useful. Tiny error, max power for two luxpower / squirrel pods of 7.2 kW does not equate to "40 amps". More like just under 32 amps. Hence my 32a MCB they are on, won't trip. But I have throttled charge rate to 57%, as I too have 19.2 kWh, I too have intelligent octopus, 6 hours to charge in, absolutely no need to go berserk and charge at 7 kW. 4 kW charge rate is plenty actually, and a shade kinder on the batteries.

  • @YorkshireAutomation
    @YorkshireAutomation9 ай бұрын

    Yes that's what I do now. And you are correct better for the batteries

  • @lawrenceharris1819
    @lawrenceharris18199 ай бұрын

    Could I ask a general question please? We have this set up - Luxpower batteries and a controller that doesn't. Most of the time the controller is fast asleep and only grudgingly wakes up to switch to battery supply. Have you seen many examples where the controller does not control - or is ours the only one? TIA

  • @alexischrysaphis5492
    @alexischrysaphis549210 ай бұрын

    Do we need a paid monthly subscription to the VoiceMoney to work? Thank you.

  • @YorkshireAutomation
    @YorkshireAutomation10 ай бұрын

    no subscription required if you are just using it the way shown in the video

  • @nicoleheneha5282
    @nicoleheneha528211 ай бұрын

    We are moving into a warehouse that has one of these. I do not know the management code. How do I reset it not knowing the current one so that I can use it?

  • @YorkshireAutomation
    @YorkshireAutomation11 ай бұрын

    Hi There is a link at the beginning of the description to the manual. That will let you know how to reset it