Transformer Overcurrent Sizing, 750V or Less, Dry Type
In this video we discuss the overcurrent protection requirements dry type transformer rated 750V or less.
The rule referenced for this is 26-254 in the 2018 CEC.
Don't forget to check out these other transformers calculations videos:
Transformer Conductor Sizing: • Transformer Conductor ...
Transformer Overcurrent Arrangement: • Transformer Overcurren...
Transformer Overcurrent Sizing, Over 750V, Primary: • Transformer Overcurren...
Transformer Overcurrent Sizing, Over 750V, Primary and Secondary: • Transformer Overcurren...
Transformer Overcurrent Sizing, 750V or Less, Other than Dry Type: • Transformer Overcurren...
Introduction: (0:00)
The Transformer: (1:20)
Secondary Overcurrent: (2:02)
Feeder and Individual Primary Requirements: (4:38)
Individual Primary Sizing: (6:12)
This video is intended for educational purposes and should not be used as an installation guide. Consult your local safety code requirements and a qualified electrician.