Primary Secondary Pumping - The Tee Law

Primary Secondary Pumping - The Tee Law

Пікірлер: 22

  • @SoburinMuhandae
    @SoburinMuhandae6 жыл бұрын

    I am so happy I found this. You have answered ALOT of my questions concerning the closely separated Tee system.

  • @rafaelavila2316
    @rafaelavila23163 жыл бұрын

    Thanks very much for this wonderful down to earth explanation. You just made my life a bit easier.

  • @ericv.4596
    @ericv.4596 Жыл бұрын

    Awesome Tutorial. Thank you for this.

  • @arpitakar5600
    @arpitakar56002 жыл бұрын

    very sincere thanks to your effort rom india ,,, a great help

  • @eastmids10
    @eastmids102 жыл бұрын

    Legend. That's made it so simple to understand, thank you.

  • @Le001M66
    @Le001M666 жыл бұрын

    Too many videos out there geared towards engineers. I like how simple yet effective it is. Thanks

  • @markrussell9719
    @markrussell97194 жыл бұрын

    Thanks for sharing - This is a really good explanation.

  • @jackmcdonald7391
    @jackmcdonald73915 жыл бұрын

    Great video.I had 2 tech's try and explain this to me but this sunk in.

  • @l.crossjr
    @l.crossjr5 жыл бұрын

    Excellent explanation. Thanks

  • @M.Begley
    @M.Begley4 жыл бұрын

    Awesome video thank you very much ❤️‼️🇬🇧

  • @beefcurrywithrice
    @beefcurrywithrice4 жыл бұрын

    The water that flows in the common pipe is it returned water from the primary loop or the secondary loop? I don't get when the water comes out of the second tee where does it go? does it get carried away with the primary water, or does it go back into the first tee? Is it the same water circulating inside the secondary loop? If so how does it get heated?

  • @tecnoprofet
    @tecnoprofet4 жыл бұрын

    Thanks for this video .

  • @arturzych138
    @arturzych138 Жыл бұрын

    My question is regarding the scenario where you have 150 gpm in the secondary loop but 100 gpm in the primary loop with the reverse flow in the decoupler, how can that happen if the pressure in the primary loop is larger?

  • @syedahmed2947
    @syedahmed29473 жыл бұрын

    If incase the supply and return piping are at different levels and we connect the decoupler with some angle fitting will it work or cause problems.

  • @quentinludwigs
    @quentinludwigs3 жыл бұрын

    Thank you!

  • @beefcurrywithrice
    @beefcurrywithrice4 жыл бұрын

    If the primary and secondary loops are decoupled and operate independently, why would the 100 gpm of water from the primary loop all of a sudden go into the secondary loop when there is a pump on the secondary loop since the pressure drop in the common pipe is still 0 ?

  • @JMPCompany

    @JMPCompany

    4 жыл бұрын

    Thanks for the question. The pump in the secondary loop would create a drop in pressure. If the secondary pump creates enough pressure drop to flow 100 GPM thru the secondary loop then we have to have 100 GPM leaving the first T going into the secondary. Based on the T Law if we have 100 GPM going into the T then 100 GPM leaving the T going into the secondary that leaves 0 GPM flowing thru the common pipe. It all goes back to the secondary pump and the flow rate it establishes.

  • @jasonsjourney7792
    @jasonsjourney7792 Жыл бұрын

    Easy to understand from other videos

  • @Benzknees
    @Benzknees3 жыл бұрын

    Interesting. So my single pipe central heating system (two tees off single pipe to each radiator) doesn’t work. I wonder what’s been causing the radiators to heat up for the last 60 years then?

  • @JMPCompany

    @JMPCompany

    3 жыл бұрын

    Great question. If you have any pressure drop between the two tees then you can get flow into the radiator with a pump. Bell and Gossett makes monoflo tees for this type of application for single pipe systems. Info can be found at: bellgossett.com/hydronic-plumbing-accessories/flow-control-valves/copper-red-ring-monoflo-fittings/