Practically how to fill SF6 gas to Breaker

Practically how to fill SF6 gas to Breaker

Пікірлер: 39

  • @rahulnr173
    @rahulnr1733 жыл бұрын

    Thank you for sharing this video it can provide information about practical side of electrical maintainance, FYI please connect an appropriate regulator to the cylinder and properly purge the hose by opening the cylinder slowly while u connect it to the gas inlet of the breaker, so that there won't be any air and moisture mixing with the Sf6 gas that you are filling inside the breaker compartment. As per standards the moisture content for HV CBs must be less that 150 ppmv and for the GIS compartment it should be less than 500 ppmv. The purity must be greater than 97%. Also note that SF6 is one of the heavy greenhouse gas so the more we release it to atmosphere it more hazardous to environment so we should try to arrest the Leakage rather than top upping it if its heavy Leakage as early as possible.

  • @ravisharmaramachandran1038
    @ravisharmaramachandran10383 жыл бұрын

    We are running 220kv and 400kv gis in that each bay breaker we are using so is there need to fill sf6gas

  • @antonnov3765
    @antonnov37654 жыл бұрын

    Filling gas from high pressure Cylinder to the breaker without Regulator is Unsafe.

  • @bachaoxuan5093

    @bachaoxuan5093

    3 жыл бұрын

    @Antonnov, yes I agree with you. Btw, should do vacuum before filling to prevent moisture mixed in new gas.

  • @lefthanded1984
    @lefthanded19844 жыл бұрын

    what is the practical sf6 pressure need to be maintained all the time?

  • @user-gd5ne9kb2k
    @user-gd5ne9kb2k5 жыл бұрын

    Thank you, very useful information

  • @obsessedgamer6218
    @obsessedgamer6218 Жыл бұрын

    Would like to see more such videos.

  • @TECHV-tw6qp
    @TECHV-tw6qp4 жыл бұрын

    Help full... Gis

  • @funintended6923
    @funintended6923 Жыл бұрын

    With out regulator not safe to refill, full cylinder pressure will be more than the chamber pressure , there r chances for pressure relief device to explode. Also make sure chamber is vacuumed nd gas tight before filling from zero bar to the rated.

  • @ethanharrison9379
    @ethanharrison93792 жыл бұрын

    No regulator on gas bottles. Did you test the gas in those bottles first ? Did you test gas in CBs also before filling? How did you test alarms on falling? What was your procedure?

  • @simomntambo1974
    @simomntambo19743 жыл бұрын

    Thanks for the video, however during filling process I didn't not see you purging the hose pipe with SF6 gas. Chances are you also top up CB with normal air during the process of gassing.

  • @sirgriffin2413

    @sirgriffin2413

    Жыл бұрын

    Fk you, you gonna blow sf6 into the air you fool

  • @spartansinpursuitoftrails4516

    @spartansinpursuitoftrails4516

    5 ай бұрын

    Yes I agree

  • @georgebosman1933
    @georgebosman19332 жыл бұрын

    I can see why so many Units blew up in your area, What about vacuum the Unit, but before You start with that, what about vacuum the the pipe and where is the the connector regulator

  • @runbou3485
    @runbou34852 жыл бұрын

    thanksអគុណ👏

  • @itsmywindow
    @itsmywindow5 жыл бұрын

    Thank you

  • @muditbaid2310
    @muditbaid23102 жыл бұрын

    Sir SF6 charging kit & Hose kidar se buy kare???

  • @dalamchandkundlia5827
    @dalamchandkundlia582710 ай бұрын

    what is the outlet size of SF6 Gas cylinder.

  • @bachaoxuan5093
    @bachaoxuan50934 жыл бұрын

    It's acceptable if you top-up, however when filling an empty tank, you should vacuum firstly to remove moisture and make sure NO air/residual gas inside then filling. Visit our company WIKA website/KZread channel if you want to see not only professional product but also comprehensive solution for operating SF6 gas. Thanks.

  • @energytech3521

    @energytech3521

    3 жыл бұрын

    Yes! Or Visit DILO campany 😉

  • @razaulkarim6796
    @razaulkarim67964 жыл бұрын

    gas can refill breaker on condtion? or need off condtion?

  • @electricalprotection33

    @electricalprotection33

    4 жыл бұрын

    Circuit breaker either in off or on no problem

  • @Friend_Fuel

    @Friend_Fuel

    4 жыл бұрын

    It is better to open the breaker before vacuuming and gas filling.

  • @Goat.phomator666
    @Goat.phomator6664 жыл бұрын

    Your accent is very cool. Where are you from?

  • @sairamganeshram8107
    @sairamganeshram81073 жыл бұрын

    Use proper original sf6 hose No need of Teflon tape We use original sf6 gas hose

  • @sunilkumar-md7rj
    @sunilkumar-md7rj Жыл бұрын

    132 kV CGL SF6 CB remote se close nahi ho raha hai but local se close ho ja raha hai

  • @crossgaming1596
    @crossgaming15964 жыл бұрын

    Unsafe and incorrect way.

  • @kuwaitupdates631
    @kuwaitupdates6313 жыл бұрын

    Use gauge regulator and b4 filling gas remove air from house,

  • @surendrakverma555
    @surendrakverma5553 жыл бұрын

    Very good

  • @spsingh9583
    @spsingh95834 жыл бұрын

    Sar mein ek baat bol raha hun aapka Jo kar kar kam kar rahe ho aapka safety ke sath Kam nahin kar raha hai isliye video banane waqt safety ka Dhyan rakhen

  • @sureshgamit1054
    @sureshgamit10545 жыл бұрын

    Sf6 gas p trip ka ciurcit diagram bata o

  • @electricalprotection33

    @electricalprotection33

    5 жыл бұрын

    Tell me in English please I don't know Hindi

  • @tarun6444

    @tarun6444

    5 жыл бұрын

    Sf6 tripping Circuit diagram gurinchi cheppamantunnaru

  • @electricalprotection33

    @electricalprotection33

    5 жыл бұрын

    SF6 contact used for alarm and lockout purpose only, SF6 contacts used in both tripping and closing circuit, breaker already in closed condition at the time SF6 lockout occured this contact will block the tripping, if breaker already in open condition if you want to close the breaker the sf6 contact block the closing

  • @Vivek-kw2ep
    @Vivek-kw2ep2 жыл бұрын

    Y