    @faisalsardar10786 жыл бұрын

    Amazing step by Alfanar TQM team to ensure that optimum quality is delivered. Impressive work by Mr. Irfan Rashid such steps will lead towards a massive improvements in terms of quality.

  • @alahmadeemohammad1354

    @alahmadeemohammad1354

    3 жыл бұрын

    good description but The accompanying music is so annoying that you cannot focus in the explanation

  • @zaby09083
    @zaby09083 Жыл бұрын

    Nice presentation 👏

  • @TM-ist
    @TM-ist2 жыл бұрын

    @5:20 the earthing should not have been connected against gravity force. @5:25 marking should have included nuts along the same line with bolts. At the moment you cannot understand if a loosening occurs. And also, Main circuit connections should be marked with 2 seperate colored marking, for example a blue mark should be done by the person who get the torque and red from the one who controls it. @5:55 Normally closed contact of test switch to the connection of relay is being tested but, NC contact should have been opened via putting in test plug into the test switch and it should have been checked whether the wiring is performed correctly.

  • @rolitomercaderjr93
    @rolitomercaderjr933 жыл бұрын

    How to aply...My work..Is fabricate LVSG swichgear..High voltage

  • @bobcocampo
    @bobcocampo3 жыл бұрын

    Do you have cal/cm2 for Metal Sheet?

  • @MadanSingh-un9ym
    @MadanSingh-un9ym4 жыл бұрын

    Sir substation Ke Upar video banao erection commissioning 220 KV

  • @PQMiS

    @PQMiS

    4 жыл бұрын

    Madan Singh sure we will create that also