Jandy EE2500T Heat Pump Pool Heater Fault Low Ref Pressure

Тәжірибелік нұсқаулар және стиль

Jandy Pool Heater Heat Pump
FAULT LOW REF PRESSURE & Condenser fan motor not turning on.
Defective fan cap and leak on screader core high side.

Пікірлер: 14

  • @robertpenczar8930
    @robertpenczar89304 жыл бұрын

    You know doc it seems most of the time on those heat pumps and other condensers 8 out of 10 it's a capacitor, or a bare wire somewhere. Great video

  • @peterdarlington4117
    @peterdarlington41173 жыл бұрын

    Wow never new people actually bought those cap testers my supply house has had one sitting on the shelf for 7 years!

  • @richardcuello8249
    @richardcuello82493 ай бұрын

    Hi Mikey, how are you ? Can you please help me, my Jandy heater is not heating… the fan runs but the flow out is not cool … The display has not problem showing. What can be the problem ?

  • @ralkassab733
    @ralkassab7333 жыл бұрын

    I have Jandy pool HP, the compressor and the fan run about one minute and I get HIGH ref pressure. What could be the cause? water is 100% flowing thru.

  • @zakarathedragonqueen7254
    @zakarathedragonqueen72543 жыл бұрын

    i have a similar problem the fun doesn't turn on the heat pump shot off after 3 second and the message said fault high ref pressure, what could it be, btw I'm in central Florida.

  • @Hammhands
    @Hammhands3 жыл бұрын

    The "condenser" fan motor is not your condenser fan motor in a heat pump. Ypur sending your discharge from compressor to heat exchanger to heat water. Your "condenser" then becomes your evaporator. So if the fan wasn't running, low pressure on your low side.

  • @Hammhands

    @Hammhands

    3 жыл бұрын

    So the error was correct

  • @hasharagomes1976
    @hasharagomes1976 Жыл бұрын

    sir what was the gas pressure succession and discharge

  • @ericjmasters
    @ericjmasters3 жыл бұрын

    I have this same unit and I turn it on an it takes about 4 to 5 minutes to start up. Soon as it kicks on and the fan turns on it runs for about 10 seconds and throws the breaker. Any idea where I should start on trouble shooting this unit? Also my lcd screen is burned out so I can’t really read it

  • @peterdarlington4117

    @peterdarlington4117

    3 жыл бұрын

    The unit has a 5 minute delay built into the board also ohm out the compressor common to run let’s say it’s 1.5 then common to start let’s say it’s 1.3 now check start to run it should be the fist two readings added 2.8.... disclaimer my numbers are made up resistance will vary by compressor turn off the power first and if turning off the power didn’t occur to you call a professional also check all terminals to ground if you have resistance your windings are shorted to ground but generally it won’t run for ten seconds if shorted to ground it will trip the breaker instantly if shorted also could be a bad connection at the disconnect or connections in unit

  • @ericjmasters

    @ericjmasters

    3 жыл бұрын

    @@peterdarlington4117 thank you. I have a loose ground I think but I don’t no where to connect it at. I posted my comment 2 months ago and still have not fixed this issue so I will check today again with your response

  • @peterdarlington4117

    @peterdarlington4117

    3 жыл бұрын

    @@ericjmasters no worries let me know if have questions

  • @Eric-ei2kc
    @Eric-ei2kc2 жыл бұрын

    On heat pump running as heat, that fan is warming the evaporator coil. Also you're not moving cold- all refrigeration moves heat.

  • @MiguelRodriguez-jf1bd

    @MiguelRodriguez-jf1bd

    2 жыл бұрын

    I was just gonna say the same thing cant put cold into anything nor can you remove cold; you can take heat out or put heat in. But it all depends on the flow of refrigeration