Hvac training, cfm, blower adjustment, air flow, Air Before Charge, manometer, blower chart

One on one residential new construction Start up tech Training

Пікірлер: 54

  • @zoogie980
    @zoogie9802 күн бұрын

    Thanks, this is how I assumed it was done but had to double check to make sure

  • @alrivera8363
    @alrivera83633 жыл бұрын

    Wow. Some people think a/c techs charge too much but they don’t realize all of the education, training and experience the techs go through which costs money. Nobody should work for free.

  • @ljv2094

    @ljv2094

    2 жыл бұрын

    Exactly! I work in the residential side of the industry I learned over time how powerful communication is, relaying our knowledge back to our customers into simple form is key to success. That was my biggest weakness causing many rejections towards my recommendations. Explain our value to our work the less rejection we will encounter :)

  • @smokeysmith1282
    @smokeysmith12822 жыл бұрын

    Hats off to the instructor for his awesome approach at passing along his knowledge and passion for doing it right. Cheers to all of the young HVAC guys jumping up in the saddle. It’s a very rewarding career with excellent pay. Wear your safety glasses and Ninja thin rubber gloves. They’re fantastic and ya won’t get refrigerant burns when disconnecting from the system. Cheers 🥂!

  • @Almtyhalfbreed
    @Almtyhalfbreed5 ай бұрын

    Perfect training video for green techs 👏🏽👏🏽

  • @Livingcomfortinc
    @Livingcomfortinc2 жыл бұрын

    What a lucky kid you are getting one on one training

  • @danielzertuche9893
    @danielzertuche989311 ай бұрын

    Hats off, to Mr. Reed, I commend you for your knowledge and your years of being in the trade. I was just stopping by looking at videos and I realize this was a ONE STOP video and now ! I working for STRADA Services in the HVAC dept. 3 months now ! i’m hoping that you’ll come back and give us some training it’s be GREAT !!! I hope you will come back….and give some more classes looking forward for your knowledge. Daniel Z

  • @chamasdad
    @chamasdadАй бұрын

    Thank you Thank you Thank you!

  • @corruptedbrain6
    @corruptedbrain63 ай бұрын

    Thank you for sharing your knowledge with us !

  • @joeydelmarsjr.646
    @joeydelmarsjr.6463 жыл бұрын

    thank you for this video, you explained very well and gave a better understanding of static pressure im a HVAC enthusiast so im always looks for way to meet or exceed hvac performance with new and old systems.

  • @pridemechanical815
    @pridemechanical8154 жыл бұрын

    Good job with this video. You created a great learning resource my my newer techs. Thanks

  • @TWeatherford88
    @TWeatherford883 жыл бұрын

    Excellent video and explanation. I really like your choice of concise, concrete terms (should, is etc).

  • @vincentabarca
    @vincentabarca Жыл бұрын

    Thank you for the amazing information Mr.Reed !

  • @tedallen9078
    @tedallen90782 жыл бұрын

    i've been in the field 25 years. and i just watched real world charting in this video. kudoos to this fine instructor. i needed these numbers today as i was calibrating a 3 zone 3.5 ton system. the by-pass damper was installed incorrectly causing the heating cycle to interrupt due to a temperature over limit. i was called in to fix it. safety first.

  • @jfoley1968jf
    @jfoley1968jf3 жыл бұрын

    Great video!! thanks for the great information!!

  • @chuckquinn8026
    @chuckquinn80262 жыл бұрын

    Excellent easy to understand video!

  • @joeyduffy7732
    @joeyduffy77322 жыл бұрын

    I can appreciate this video. Your supply static is inconclusive because of where the port is. Also I believe your supply plenum should be a minimum of 18” and you would get a better reading. Install the static port up high towards the back of the plenum. With it being in the front bottom corner you have about 8” of cabinet before the supply discharge.

  • @aldocampi3575
    @aldocampi35753 жыл бұрын

    Awesome, explanation

  • @hvacguy11
    @hvacguy113 жыл бұрын

    Great video thanks

  • @lancerudy9934
    @lancerudy99343 жыл бұрын

    Very nice video

  • @user-fb1kr2ye4y
    @user-fb1kr2ye4y3 жыл бұрын

    Hey, question, why do you use just the tube without the pito tube for checkin return static pressure? You can use the tube also right?

  • @gankstar2000
    @gankstar20003 жыл бұрын

    Well done!!! Great teacher!!!! Jesus is Lord; God bless!!!

  • @liantoby1200

    @liantoby1200

    2 жыл бұрын

    you prolly dont care at all but does anyone know a trick to log back into an instagram account..? I somehow forgot my login password. I would love any assistance you can offer me

  • @dominickreginald5969

    @dominickreginald5969

    2 жыл бұрын

    @Lian Toby instablaster =)

  • @liantoby1200

    @liantoby1200

    2 жыл бұрын

    @Dominick Reginald I really appreciate your reply. I got to the site through google and im waiting for the hacking stuff now. I see it takes quite some time so I will get back to you later with my results.

  • @liantoby1200

    @liantoby1200

    2 жыл бұрын

    @Dominick Reginald It did the trick and I now got access to my account again. Im so happy:D Thanks so much you saved my ass !

  • @dominickreginald5969

    @dominickreginald5969

    2 жыл бұрын

    @Lian Toby happy to help =)

  • @canamericanguy7992
    @canamericanguy79923 жыл бұрын

    Informative, thank you! Now that we know the how, it would be great if you could explain the why. In your scenario here, what are the implications of running the fan on high instead of medium? Are we able to calculate some sort of loss in efficiency? And when the static pressure has remained virtually the same, why wouldn't you want more air circulation?

  • @thebaba9511

    @thebaba9511

    3 жыл бұрын

    Checking CFM over a dry coil, it makes no difference. But when the system is running it will affect your superheat and su cooling. A slow blower speed will cause your supply air to be too cold, cause condensation and buildup of all kinds of funk in your duct work.

  • @thisisyourcaptainspeaking2259

    @thisisyourcaptainspeaking2259

    3 жыл бұрын

    @@thebaba9511 Thanks! Although I'm still not entirely clear on the downside of a blower speed higher than target, would that be specifically, incorrect superheat/subcooling balance? Two (other) aspects I can think of are excess noise and incorrect condensate scavenging, where condensate might be blown off the evap coil onto other surfaces.

  • @justwork_hvac
    @justwork_hvac3 жыл бұрын

    Thanks for sharing this great video

  • @goodtimestxphotobooth985
    @goodtimestxphotobooth9853 жыл бұрын

    Question- I just had a new ac installed and the blower motor/return air section was making a weird throbbing or pulsing noise. Tech said that he had to reduce the fan speed. Does this sound correct? The noise did seem to go away but now it seems that the air supply is too slow/low and taking the house too long to cool down. Would you have any other ideas as to the strange sound? (Sounded almost as if you had an old box fan and put a piece of cardboard behind it rapidly on and off to restrict the air flow)

  • @shinekraj4944

    @shinekraj4944

    2 жыл бұрын

    Usually that means that the supply side has a restriction somewhere which is blocking all that air that's getting pushed by the blower.

  • @HVACTailGateTrainer

    @HVACTailGateTrainer

    2 жыл бұрын

    I always start with a full job link report before I try thinking about problem scenarios. If your hvac company utilizes fieldpiece job link charge and air kit and the fieldpiece joblink manometers as for a copy of the report. IF they have and use this tool to generate performance reports, get a copy, take a pic , and post it for me to look at.

  • @nessnesu6202
    @nessnesu62024 жыл бұрын

    Why would you look at outdoor unit for tonnage for airflow? Thought it would be check indoor coil capacity/tonnage then adjust airflow. Most of the time I see indoor coil either same tonnage or slightly bigger than outdoor coil.

  • @allenreed8130

    @allenreed8130

    4 жыл бұрын

    Air handlers can cover a variety of sized outdoor units sometimes. A air handler may for example be compatible for a 2 2.5 or 3 ton outdoor unit, just as an example" you must identify the tonnage of outdoor unit and give the evaporator 400 cfm per ton of the outdoor units capacity. Crap tons of units out there with incorrect air flow setups in the air handlers.

  • @ArcheryRuleZ

    @ArcheryRuleZ

    2 жыл бұрын

    Ya, the more you check , the more bad installations you see

  • @mikeblackpoetry5248
    @mikeblackpoetry52483 ай бұрын

    May I ask what camera you’re using to record your videos?

  • @HVACTailGateTrainer

    @HVACTailGateTrainer

    3 ай бұрын

    I believe this was simply a go pro5

  • @fisheye42
    @fisheye42 Жыл бұрын

    I'm new to this stuff. The Supply was positive (+0.1) and Return was negative (-0.42 at 2:54 in the vid), so adding them on the sheet would result in -0.32, right?? (not 0.52). Or should you you intentionally ignore the + and minus signs?

  • @evantrace2902

    @evantrace2902

    4 ай бұрын

    Your calculating your total static. One side is going to be pulling air (negative static) and the other side pushes air (positive static). The negative is just telling you which side so it dosent apply when you add them.

  • @fisheye42

    @fisheye42

    3 ай бұрын

    @@evantrace2902 Thanks. It’s making more sense now. TSP is total “work” (resistance) that the blower/system has to overcome. A push and a pull are still both “work,” so we add the two amounts. In other words, we ignore the pull’s minus-sign because pulling still ADDS to the workload).

  • @biblebloopers946
    @biblebloopers9462 жыл бұрын

    Can you apply this method to an ecm motor?

  • @HVACTailGateTrainer

    @HVACTailGateTrainer

    2 жыл бұрын

    X13 yes, variable speed no.

  • @RobertTuck-vo8cw
    @RobertTuck-vo8cwАй бұрын

    That looks like a static probe, not a pitot probe.

  • @ivankrushensky
    @ivankrushensky2 жыл бұрын

    We need more education like this in the US, and a lot less gender studies.........

  • @kyleperry1701
    @kyleperry17013 жыл бұрын

    only question is where did you get the 1400ish cfm from how do you know the black is 1400 cfm.

  • @kyleperry1701

    @kyleperry1701

    3 жыл бұрын

    i understand air handlers come with a blower motor that can handle tons from 1 ton to 3 tons of air / and some can can do 3 tons to 5tons . question is how do you know that airflow without using a anemometer

  • @ArcheryRuleZ

    @ArcheryRuleZ

    2 жыл бұрын

    He does show u how to read the fan capacity chart ......

  • @come_on_now
    @come_on_now3 жыл бұрын

    Static pressure bubba... before the vent/grille... that is why your supply reading was ALL OVER THE MAP. Enjoy the free education instructor.

  • @ArcheryRuleZ

    @ArcheryRuleZ

    2 жыл бұрын

    Plus, on the return test shouldn’t they make sure the probe tip was pointing towards the air coming in

  • @jcstudios5629
    @jcstudios5629 Жыл бұрын

    I’m sorry but I don’t think your static pressure readings are very accurate. First of all you just stuck the hose inside the return. Second, what type of probe was used on the supply side? Conventional wisdom says to use a 90 degree elbow probe with it facing with the airflow to get the most stable and accurate static pressure readings. The other problem is the air turbulence happening on the supply side. The rest of the demonstration is good.