Falló el Solenoide o la Válvula Expansión ?

Ғылым және технология

El cliente me había comentado que esta saltando por baja cada ves que lo resetea. Se pensó que había fuga pero encontré una falla distinta.

Пікірлер: 91

  • @DanielFernandez-fb4sb
    @DanielFernandez-fb4sb2 жыл бұрын

    Saludos desde uruguay,siempre que podemos vemos tus experiencias para aprender,seria bueno tener un profesor como vos para acá, gracia

  • @derrickenbuenosaires

    @derrickenbuenosaires

    2 жыл бұрын

    Gracias Daniel, saludos a Uruguay

  • @pabloolmedo-zb6ly
    @pabloolmedo-zb6ly5 ай бұрын

    Sos un groso Derrick!!!! Capo total!!! Gracias por compartir tu conocimiento!!!!

  • @jesusquintero2514
    @jesusquintero25142 жыл бұрын

    Nos vemos en el próximo capítulo jajaja! Éstos equipos son un cuento de nunca acabar pero eso es bueno para nosotros xq así tenemos trabajo y cada vez aprendemos algo nuevo! Saludos desde Ecuador-Venezuela!!!

  • @federicovarela1038
    @federicovarela10382 жыл бұрын

    Muy buenos tus videos Derrick, felicitaciones y seguí trayendo tus Derrickaventuras

  • @brattbautistaoscco3229
    @brattbautistaoscco32296 ай бұрын

    un maestro enserio perfecta enseñansa en el campo mucha gracias tu experiencia nos sirve a todos gracias por darnos de tu tiempo y tu sabiduria

  • @carlospalacios3420
    @carlospalacios3420 Жыл бұрын

    Excelente explicasión y un buen trabajo amigo Dios te bendiga por tus enseñanzas

  • @ricardoconil1543
    @ricardoconil15432 жыл бұрын

    Gracias .Derrick , muy bueno gracias x compartir tus conocimientos , saludos desde monte caseros corrientes

  • @joseluisdelacruz3210
    @joseluisdelacruz3210 Жыл бұрын

    Buenos días bendiciones para todos muy bueno el video excelente trabajo uste es un maestro

  • @juliosan2177
    @juliosan21772 жыл бұрын

    Muy bien Derrick , otro cliente satisfecho

  • @guillemartinez8247
    @guillemartinez8247 Жыл бұрын

    Tus videos son excelentes,te hace falta una recuperadora de gases para estos trabajos ya que el refrigerante esta muy caro;podes recuperar en un envase todo el refrigerante del sistema podes trabajar tranquilamente. Tu método de trabajo es sobre la marcha donde tu diagnóstico es muy certero se aprende un montón con tus videos y se agradece el aporte.Saludos

  • @ottoa.menendez171
    @ottoa.menendez171 Жыл бұрын

    Excelentes videos aprende mucho de todo, muchísimas gracias

  • @waltherherrera67
    @waltherherrera67 Жыл бұрын

    Excelente adelante y éxitos dios te guarde y bendiga

  • @manueldiez2929
    @manueldiez29292 жыл бұрын

    que grande Derrick !! te izo renegar el acmar !!😵 a mí tmb me pasó con una válvula con el bulbo cortado se cerraba y no entendía ni @ !! hasta que me di cuenta pasa que esas fayas no son comunes por eso es bueno lo que ases de repasar los problemas para no olvidar !!! saludos colega !!! si tenés paste algún vídeo de cómo es las reparaciones en usa !! gracias

  • @willyfrias7330
    @willyfrias73302 жыл бұрын

    Buen video instructivo derrick para aprender algo más 👍👍👍

  • @enzitoo69
    @enzitoo692 жыл бұрын

    Excelente video Derrick, gracias por compartir tus experiencias se agradece! Sigo esperando que algún día hagas otro vídeo explicativo, como fue el de válvulas de expansión pero sobre sobrecalentamiento y subenfriamiento un abrazo!

  • @tecnifriotequendama9452
    @tecnifriotequendama94522 жыл бұрын

    Muy buenos el video gracias 🙂 Derrick saludos desde Colombia 👍

  • @dragonrojo1045
    @dragonrojo10452 жыл бұрын

    Bien Derrick, siempre se aprende algo

  • @joselm653
    @joselm6532 жыл бұрын

    Perfecto amigo como siempre! Amaizing!!

  • @VictorLopez-qv1fv
    @VictorLopez-qv1fv Жыл бұрын

    Saludos camaradad #1 chingón carnalito.

  • @joseluisgonzalezlopez9696
    @joseluisgonzalezlopez96962 жыл бұрын

    exelente video y trabajo

  • @alvaropedrozo6117
    @alvaropedrozo6117 Жыл бұрын

    desdes colombia gracias amigo aprendi lo agradezco mucho por recordarme este chicharron

  • @pablopescetti5136
    @pablopescetti5136 Жыл бұрын

    Q buena explicacion deloq se leiso al eqipo y su problema...

  • @paracutirimi
    @paracutirimi2 жыл бұрын

    Buen trabajo

  • @yoberrojas5815
    @yoberrojas58153 ай бұрын

    Exelente vídeo

  • @walteralvarez8496
    @walteralvarez84962 жыл бұрын

    Hola Derrick ,como siempre dando clases y bien claras, asta el próximo video colega ,que sigas bien!!

  • @carlosdariomartinez1294
    @carlosdariomartinez1294 Жыл бұрын

    Hola amigo Derrick! Saludos de Santa Fe. Gracias por tus vídeos me sacan un montón de dudas continuamente! Quería preguntarte dónde puedo conseguir el imán para destrabar las solenoides, cómo el que vos usas, acá en el país. Gracias!

  • @user-mf2ii8ho7d
    @user-mf2ii8ho7d9 ай бұрын

    Amigo Derrick,soy un seguidor de tus videos ,que para mi son " muy didácticos.Me gustaria poder hacerte consultas.Un saludo desde Cuba.

  • @monguelo
    @monguelo2 жыл бұрын

    Buenas Derrick, gracias por tus conocimientos, ayudan mucho. Por qué pasa eso en las válvulas de expansión? Donde trabajo tengo una deshumectadora y cada año o a veces a los pocos meses toca cambiar la válvula de expansión. La marca que le pongo es danfoss. Los compresores están 24h en funcionamiento todos los días. Podría ser por estar tanto tiempo en funcionamiento? un saludo y gracias!

  • @josemateo5430
    @josemateo54308 ай бұрын

    Excelente

  • @joseortoneda1649
    @joseortoneda16492 жыл бұрын

    Gracias, gracias

  • @escobar2021
    @escobar2021 Жыл бұрын

    hola saludos desde españa

  • @fabianesparza6445
    @fabianesparza6445 Жыл бұрын

    Saludos desde México como le puedo hacer un cambio de aceite a a una máquina igual no le encuentro el tornillo de dernado

  • @Joseaguilar-pt4iq
    @Joseaguilar-pt4iq3 ай бұрын

    ERES CHINGON PERO SOLO TE CONFUNDES!!

  • @derrickenbuenosaires

    @derrickenbuenosaires

    3 ай бұрын

    Gracias Weiii !

  • @roceloi
    @roceloi2 жыл бұрын

    11:46 cables pegando en las resistencias de desescarche esperando ha hacer corto!

  • @leoderosario9150
    @leoderosario91502 жыл бұрын

    Muy bueno Saludos

  • @derrickenbuenosaires

    @derrickenbuenosaires

    2 жыл бұрын

    Gracias Leo, saludos

  • @wolgfangruidiaz2782
    @wolgfangruidiaz2782 Жыл бұрын

    Derrick saludos yo acostumbro cuando voy a recuperar una carga cierro el el tubo recibidor enciendo la unidad con mi presostato puentiado. Y antes de que llegue bacio .apago la unidad y cierro la linea de liquido .

  • @carlosandrade7091
    @carlosandrade70912 жыл бұрын

    TE extrañabamos derrick, el profesor derrick

  • @raulhoraciolecce4926
    @raulhoraciolecce4926 Жыл бұрын

    Hola derrick! Una pregunta de curioso, tú llevas una ficha de servicio por equipo intervenido por ti?

  • @IvanRRubio-cx5zz
    @IvanRRubio-cx5zz Жыл бұрын

    Hola Derrick, gusto saludarte, soy Iván Rubio de Honduras, te sigo desde ya hace más de un año y he aprendido mucho con tus videos y tutoriales. Que refrigerante me recomiendas para una unidad condensadora de un cuarto frío que actualmente utiliza R-502 ?

  • @joseluisdelacruz3210

    @joseluisdelacruz3210

    Жыл бұрын

    😅😅😅😅😅 ,

  • @mariogustavomoreno6157
    @mariogustavomoreno61572 жыл бұрын

    Maestro !!!

  • @sterlingarcher46
    @sterlingarcher462 жыл бұрын

    Primero quiero decir me disculpa para hablar inglés. Couple questions came to my head Derrick : Do you need copper flare washers in between the flare nuts and the male flare fitting on the Txv , and if you do but don't have them available then what can you do ? Nylog ? Loctite ? Do clients where you're located accept that you'd recover the charge and replace the solenoid , dryer and Txv at once , or do they only accept the bare bone minimum . And last , do you even have recovery tanks and supply houses take the freon back and recycle it , or is it just old school no recovery ? ( asking cause I know places where there isn't even logistics in place to recover freon even if you wanted to ) Muchas gracias y cheers mate 👍.

  • @derrickenbuenosaires

    @derrickenbuenosaires

    2 жыл бұрын

    Hey sterling, no problem talking in english 👍 I would say that proper installation would be to use copper or some type of nylon flare gasket on the mating surface but honestly down here I have no idea where one would even buy such an accessory since it's not commonly found. Brass against brass does seal though since I've installed the reducer before in a similar situation. I used some errecom "seal up" thread sealant as well, I prefer nylog but no nylog down here. As for recovery goes, the refrigeration supply houses don't accept recovered refrigerant to be recycled. That's why reclaiming here is practically non existent. The customer almost always has to replace the charge if a part fails where the charge can't be pumped down. There are recovery cylinders here but they are mostly owned by supermarket chains and large manufacturers where they may have 100s of kgs of refrigerant or thousands of lbs. We mostly do the minimum to get the equipment running. (at least with my clients) I would've liked to change the solenoid here because I wasn't sure where the restriction was but I'm sure the customer was grateful that I was able to diagnose correctly and not change something that did not fail even though it is old. The drier I couldn't change because the king valve wouldn't shut properly so he got to keep his older drier lol

  • @sterlingarcher46

    @sterlingarcher46

    2 жыл бұрын

    @@derrickenbuenosaires thank you very much indeed. Yeah so it's pretty much the exact same thing as the other places I was talking about . It appears that only the "developped" countries have the reclaiming process in place , it's a shame because there would be a whole lot of business to be done around it .

  • @derrickenbuenosaires

    @derrickenbuenosaires

    2 жыл бұрын

    @@sterlingarcher46 What I would really like to see down here is some kind of certification to buy and handle refrigerants. Anyone underage, untrained, whoever can walk into a supply house and buy refrigerant. It takes away jobs from the true technicians and it makes us look bad because some random will do a job for half the price, do it wrong, collect money and disappear. Then the customers become weary of the HVAC techs down here. There's no respect for the residential guys. I'm glad I don't do residential regardless lol

  • @sterlingarcher46

    @sterlingarcher46

    2 жыл бұрын

    @@derrickenbuenosaires Ah man ! 🤦‍♂️they've put that in place over here in EU it's called the F-Gas license . Without it you can't handle refrigerant, and there's a second category license that you need to buy refrigerant and then you have to annually report what and how much you've bought , used , reclaimed , recycled and so on and so forth . But then again it's only been put in place and finalised in 09 or 2010 , so not so long ago innit .

  • @educastillo3805
    @educastillo38057 ай бұрын

    excente

  • @eduardpalma6781
    @eduardpalma6781 Жыл бұрын

    Hace poco me pasó algo parecido la unidad condensadora itarcon no apagan por Pug dawn el control apaga el equipo y tiene presostatos de alta y baja tipo pila y apagan por estos controles si se baja más la presión o se sube el presostato se demora.en reponer y hay que activar las selenoides con el iman

  • @ernestovaldez495
    @ernestovaldez4952 жыл бұрын

    Primer comentario , siempre aprendiendo del maestro !!!

  • @derrickenbuenosaires

    @derrickenbuenosaires

    2 жыл бұрын

    Gracias Ernesto, un abrazo !

  • @ernestovaldez495

    @ernestovaldez495

    2 жыл бұрын

    @@derrickenbuenosaires eres un capo, no me pierdo tus videos.. excelente contenido. Gracias por responder!

  • @jndenisbergeaud3200
    @jndenisbergeaud32002 жыл бұрын

    Hello my friend how are you doing? From New Orleans

  • @cristiangonzalez1939
    @cristiangonzalez19395 ай бұрын

    Que pasa si un motor compresor de frío por alrta Sele echar aceite que con secuessia trae

  • @ivanhhss
    @ivanhhss11 ай бұрын

    Estimado ese equalizador externo debe ir conectado porque sino no trabajará la válvula correctamente

  • @manuelbenito2186
    @manuelbenito218611 ай бұрын

    Si metes un iman en la solenoide y luego cuando lo tienes la aspiración a 0 bares cierras la lleve de el compresor lo más seguro es que no tengas el problema de tirar tanto gas

  • @Oscar-zt2di
    @Oscar-zt2di Жыл бұрын

    La válvula selenoide probar en ohmios y la válvula de expansión cambiar la tobera ???

  • @pelatitorial1054
    @pelatitorial10542 жыл бұрын

    Que tal Derrick, pudiste ver la tobera y filtro de la VET? Para saber si la restricción era por falla, suciedad o humedad dentro del sistema... Lastima que no pudiste cambiar el filtro y la solenoide... buen laburo, saludos

  • @hackpreak

    @hackpreak

    Жыл бұрын

    Lo mismo pensé

  • @carolineustaquiocastro8756
    @carolineustaquiocastro875611 ай бұрын

    como saber el orificio calibrado que lleva la unidad

  • @kikebiker
    @kikebiker11 ай бұрын

    Super incómodo ese igualador externo o compensador. Es parte de cambiar una valvula

  • @carloscolina2638
    @carloscolina26382 жыл бұрын

    Saludos amigo.!! Disculpa mi ignorancia y se q no viene con el tema pero. Tengo un compresor q trabajaba con r12 pero en vista q está descontinuado el refrigerante r12 le cambié el aceite para r134a y le hice una buena limpieza a las tuberías. Fui a comprar una válvula d expansión para r134a pero no había la necesaria para 1 1/2 T. M ofrecieron una válvula para r12 y m indicaron q sirve para refrigerante r134a.! Mi pregunta es esto posible?? Sirve o no? Lo has hecho? Gracias x tu ayuda d ante mano.!

  • @derrickenbuenosaires

    @derrickenbuenosaires

    2 жыл бұрын

    Hola Carlos, si te va funcionar perfectamente bien la valvula. Cuando reemplazo r12 mayormente utilizo 437A y compro una valvula de 134A. Son todos refrigerantes de baja presion que se pueden intercambiador sin problema despues que hallas cambiado el aceite a POE. Sigue adelante amigo sin preocupacion

  • @cesarblanco7955
    @cesarblanco79552 жыл бұрын

    Que bien cuidas la herramienta, parece recién estrenada. Que importante tener mirilla en la línea de líquido y en buenas condiciones. Sino esta avería muy difícil de ver. ¿Porque no está instalado el tubo compensador de presión.?

  • @derrickenbuenosaires

    @derrickenbuenosaires

    2 жыл бұрын

    Y maso menos intento de mantenerlas limpias. Tengo que hacer una limpieza general de mis herramientas pronto. El VET original no tenia opcion de compensador. Estos evaporadores son grandes y lo deberia tener para compensar la caida de presion a la salida del evaporador

  • @luisvillasmil5496

    @luisvillasmil5496

    Жыл бұрын

    @@derrickenbuenosaires amigo Derrick una pregunta, qué sucede si a un equipo de congelación de 3hp le coloco una válvula de expansión de 3hp ? Trabaja bien, o hay q colocar una más pequeña? Y cual seria la correcta? Saludos.

  • @cristiancarrondi2460
    @cristiancarrondi2460 Жыл бұрын

    Soy de Rosario Argentina, cuando veo un equipo de esos se lo hago tirar a la basura

  • @Luis1985-
    @Luis1985- Жыл бұрын

    después del solenoide se podría poner otro filtro

  • @RobertojavierMeichtri-ig5vt
    @RobertojavierMeichtri-ig5vt Жыл бұрын

    Solo un cosejo tendrias que haver anulado el presostato para travajar con el compresor en marcha para guardar el refrijerante

  • @alejandrocaller4477
    @alejandrocaller4477 Жыл бұрын

    Esa falla se produce por la saturación del filtro, afloja la tuerca y sabrás si pasa o no.

  • @elektrotecnico
    @elektrotecnico8 ай бұрын

    hola como estas? quisiera saber como se llama el instrumento que utilizar para comprobar la bobina del selenoide en el minuto 7:12 gracias

  • @derrickenbuenosaires

    @derrickenbuenosaires

    8 ай бұрын

    "Solenoid checker" o "tester". No he encontrado alguien que lo vende aca en el mercado pero lo puedes conseguir por amazon

  • @elektrotecnico

    @elektrotecnico

    8 ай бұрын

    @@derrickenbuenosairesgracias, muy amable Derrick, saludos !!

  • @sergioflores7651
    @sergioflores76512 жыл бұрын

    Hola dereick necesitas un ayudante? Quisiera aprender más... soy d bs as.. tengo herramientas y vehículo.. j😁

  • @victoravalosjavier3826
    @victoravalosjavier38262 жыл бұрын

    Muy bueno el vídeo pero veo que nunca arrancó los ventiladores de la condensadores

  • @derrickenbuenosaires

    @derrickenbuenosaires

    2 жыл бұрын

    Gracias Victor, ese equipo es condensado por agua. Cuando empieza verano devuelta en esos dias calidos puede llegar a ciclar devuelta. Saludos !

  • @victoravalosjavier3826

    @victoravalosjavier3826

    2 жыл бұрын

    @@derrickenbuenosaires ok gracias por sus explicaciones sos el único que sube vídeos de equipo grande. Amii me encanta la refrigeración estudié me recibí y en mismo tiempo libre hago algunos trabajo. Tengo empleo pero mi sueño sería vivir de este ofició qué es tan lindo la refrigeración .Tengo trabajo fijo en una empresa. Pero algún día me gustaría vivir de este ofició qué es tan lindo la refrigeración le mandó un abrazo grande esperó que tenga mucho éxito en todo. Yo quisiera algún día vivir de este ofició y renunciar a mi trabajo.

  • @fredysantonioospina5932
    @fredysantonioospina59322 ай бұрын

    Yo cambiaría el filtro y válvula solenoide

  • @jndenisbergeaud3200
    @jndenisbergeaud32002 жыл бұрын

    Que sucede tengo una clienta que me llamo por carro que no enfría correcto ,yo chequeó todas casas están bien, lo que yo viendo fué el ventilador qué tarda 5 a 6 minutos pará arranca ,puedes me dar un idea que sucede?

  • @derrickenbuenosaires

    @derrickenbuenosaires

    2 жыл бұрын

    Es posible que en tu caso tienes un ventilador que cicla por presostato. Eso lo puedes comprobar viendo donde enciende y corta el ventilador con el manifold conectado al lado de alta. Igual deberia encenderse enseguida si hace calor, si no es porque esta muy baja con carga de refrigerante. Si el ventilador tiene una plaqueta puede ser la logica tambien pero es raro que tarde 5 mins para encenderlo. Yo iria a ver si tiene presostato para el ventilador

  • @jndenisbergeaud3200

    @jndenisbergeaud3200

    2 жыл бұрын

    Gracias mi amigo

  • @Walteracon
    @Walteracon2 жыл бұрын

    mira esos cables de la resistencia re quemados haciendo contacto

  • @derrickenbuenosaires

    @derrickenbuenosaires

    2 жыл бұрын

    Hola Walter, no me di cuenta hasta que empeze a editar el video, parece que en 13:04 los movi de donde tocaban 😂😂

  • @edgarescalona7590
    @edgarescalona759011 ай бұрын

    Que orifioc lleva esa unidada

  • @zottagustavo
    @zottagustavo2 жыл бұрын

    Maldita llave, siempre hay alguna en mal estado... Si no, era VET, filtro, y a cobrar! 😉 Chinwewencha, tenés un magnetómetro!

  • @arrionda1

    @arrionda1

    2 жыл бұрын

    Puedes tambien usar una brujula comun

  • @fabiangamarra1687

    @fabiangamarra1687

    2 жыл бұрын

    El telefono también lo podés usar

Келесі