ETAP Motor Starting Analysis (Dynamic)

ETAP Motor Starting Analysis
ETAP Dynamic Motor Starting Analysis
ETAP software
ETAP study
electrical engineering
system study

Пікірлер: 9

  • @user-cb3oq2cy5s
    @user-cb3oq2cy5s Жыл бұрын

    Very useful.. Please explain how to add motor and load parameters in ETAP library, thanks!

  • @SmartEducare

    @SmartEducare

    Жыл бұрын

    Will upload soon

  • @charinath5445
    @charinath54452 ай бұрын

    Some do Dynamic motor starting study in Transient stability module? Why not in Motor starting module?

  • @SmartEducare

    @SmartEducare

    Ай бұрын

    To check the system stability during any sudden change like switching on the large motor starting, generator etc. we need it.. However, dynamic motor starting is performed to check the voltage status and adequacy to start the largest motor in the power system..

  • @mkhoirun918
    @mkhoirun91810 ай бұрын

    One Problem for Dynamic, we shall input Moment of inertia WR2 ( kg m2). How to calculate Moment Inertia WR2 (kg-m2) in ETAP? Is there any standard to calculate WR2?. I found in IEC 60034-12, Table 4. External Moment of Inertia J ( kg m2) for each kW of motor. Is it same WR2 and J? J in IEC 60034-12. Mentioned as J=0.04P^0.9xp^2.5

  • @SmartEducare

    @SmartEducare

    10 ай бұрын

    Yes, these are same. Moment of Inertia is WR2 or mr2 i.e. mass x distance sq. Moment of Inertia (Jm) value will be provided by motor manufacturer..Jext value i.e. motor external is recommended in IEC.. Based on WR2 value and motor rotation speed, ETAP will calculate the value of H

  • @wongsabarchannel1335
    @wongsabarchannel133510 ай бұрын

    ETAP Dynamic Motor Starting Analysis, For motor used to drive pump with Low Voltage, 225 kW rated.. What Model shall be used ? LV-LS-LT (Low Voltage-Low Slip-Low Torque), then Model ID, can we use MV500HP2P? What meaning MV here?

  • @SmartEducare

    @SmartEducare

    10 ай бұрын

    You can choose according to the project specific requirements..MV (Medium Voltage)..in reality, it may be required to add motor model i.e. design class, ID etc. in ETAP library depending on voltage level, slip, torque, no. of pole... Separate video available how to add motor dynamic model in ETAP library

  • @wongsabarchannel1335

    @wongsabarchannel1335

    8 күн бұрын

    One Question again, why Dynamic and Static analysis in ETAP, kW motor always higher than motor name plate that we have set/entry in the motor data in ETAP?