Automatic Changeover Switch for Generator / ATS for Single phase Wiring / ATS System for generator

In this video I hope to explain the circuit diagrams required to Automatic Changeover Switch for Generator, ATS for Single phase Wiring, ATS System for generator.
*Generator turns on automatically when the main supply fails.
*The generator will automatically turn off when the supply is restored.
*There are two AC powered and DC powered timers.
*The circuit is configured to interlock the two contactors, thus providing greater protection.
*This is a very important circuit for a home that uses a generator.
*** Red colour wire - Live wire(L)
*** Black colour wire - Neutral wire(N)
***Main supply contactor auxiliary point 2 should be N / C (normally closed).
***You can buy such a contactor in the market or you can use auxiliary contact block. Thanks.
****Thanks for watching video please subscribe my channel.
Watch out: **electrical wiring is very dangerous**you could be shocked or killed. If you are not trained and familiar with proper, safe electrical wiring practices don't try it.
My Other Video..
Ring Circuit Wiring Diagram | Socket Outlet Ring Circuit Wiring Diagram
• Ring Circuit Wiring Di...
Transistor How to Work Animation | Bipolar Transistor (NPN/PNP) | NPN Transistor | PNP Transistor
• Transistor How to Work...
generator auto start stop circuit diagram sinhala
Security Lamp Circuit | Security Light Wiring Connection
• Security Lamp Circuit ...
Forward Reverse Starter Power and Control Circuit | 3p Motor Forward and Reverse Control Wiring
• Forward Reverse 3 Phas...
Forward Reverse Starter Power and Control Wiring | 3p Motor Forward and Reverse Control Circuit
• Forward Reverse Starte...
Direct Online Starter(DOL) | 3 phase Motor Connection | Contactor Working | DOL Starter
• DOL starter control ci...
Electrical House Wiring Diagram/Single Phase House Wiring
• Electrical House Wirin...
Water Pump Automatic and Manual Control | Float Switch Wiring Diagram | Water Motor Float Wiring
• Water Pump Automatic a...
One Light On/Off Two Places /Two Way Circuit (method 1)
• Two way switch connect...
5V DC Power Supply | How to Make USB Port | 7805 Regulator IC | 5V DC
• 5V DC Power Supply | 7...
Emergency Light Wiring for Home | Home Emergency Light Wiring with Solar Power
• Emergency Light Wiring...
Water Pump Motor Automatic and Manual Control | Float Switch Wiring Diagram
• Water Pump Motor Auto ...
Solar Panel system for home/Solar Power system with inverter
• Solar Panel Wiring | S...
Generator Connect to the Home Distribution Board | Distribution Board Wiring with portable Generator
• Video
ats panel, ats automatic transfer switch, ats control circuit diagram, ats changeover switch, Automatic Changeover Switch, ATS System, ATS Wiring Diagram, ats switch for generator, ats panel for generator, generator ats panel wiring, generator ats wiring diagram, generator ats panel, generator ats controller, generator ats connection, ats for generator, ats auto start generator, ats connection to generator, ATS Automatic transmission system.

Пікірлер: 142

  • @ELTronic3
    @ELTronic33 жыл бұрын

    ***Main supply contactor auxiliary point 2 should be N / C (normally closed). You can buy such a contactor in the market or you can use auxiliary contact block. Thanks.

  • @zainmalik7977

    @zainmalik7977

    Жыл бұрын

    Help me

  • @salahsalman5863
    @salahsalman58633 жыл бұрын

    Thank you brother

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    Thanks friend

  • @easyelectric5761
    @easyelectric57613 жыл бұрын

    Thank you sir

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    Thank you friend..😍😍

  • @abubakar8647
    @abubakar86473 жыл бұрын

    Great video

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    Thank you..

  • @pongoadriano3110
    @pongoadriano31103 жыл бұрын

    Merci

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    Ok friend

  • @mentorramadani9247
    @mentorramadani9247 Жыл бұрын

    Very Useful video no doubt, thank you for your work and your time. but how could Bobin of the Power contactors and relays 230 V be ON (Energised), wen A2 terminal is connected from outlet terminals of the Contactors, or I misunderstud the Circuit?

  • @ELTronic3

    @ELTronic3

    Жыл бұрын

    Thank you very much for your comment. Please watch this for better understanding. kzread.info/dash/bejne/pHykvKempavRnrQ.html&feature=share&EJGixIgBCJiu2KjB4oSJEQ

  • @petergodwin7920
    @petergodwin7920 Жыл бұрын

    This very good

  • @ELTronic3

    @ELTronic3

    Жыл бұрын

    Thanks.keep watching my videos.

  • @tanveerabbas8095
    @tanveerabbas80953 жыл бұрын

    Sir this very informative video God bless u but I can not understand why you use comman neutral plz explain me thanks

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    Thank you...In one case only one contactor is turned on (interlock system is used) so it is not common neutral.

  • @austinegambo2922
    @austinegambo2922 Жыл бұрын

    Good stuff

  • @ELTronic3

    @ELTronic3

    Жыл бұрын

    Thanks friend..

  • @user-qh8ve8lv1c
    @user-qh8ve8lv1c Жыл бұрын

    Thanks for the video it's good but the generator contactor won't be energized since it doesn't receive the neutral

  • @ELTronic3

    @ELTronic3

    Жыл бұрын

    Thanks your best comment my friend.I'm made a small mistake.Sorry

  • @ELTronic3

    @ELTronic3

    Жыл бұрын

    Watch this one for beter understand it. kzread.info/dash/bejne/pHykvKempavRnrQ.html

  • @teflonmd7994
    @teflonmd79943 жыл бұрын

    Great video....One question though, why did u connect the generator relay-contactor's A2 coil terminal to main power neutral line, shouldn't the A2 for the generator be connected to line two of the generator power wire

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    Both contactors in this circuit do not turn on at the same time .interlock is used for this circuit.Therefore it is correct to connect the neutral terminals together and assign them to the A2 terminals.

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    Thank you very much your comment

  • @mudassaransari8611
    @mudassaransari86113 жыл бұрын

    Sir very good But more explain by morally with practical bcs eas to understand

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    Thank you so much .. Ask if there is anything you do not understand

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Single phase ATS explain kzread.info/dash/bejne/pHykvKempavRnrQ.html

  • @suryadevaelectricals7122
    @suryadevaelectricals71223 жыл бұрын

    Good Expalaination, Please send me 3phase ATS wiring diagram.

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    Thanks...i will create a 3 phase ats systerm

  • @techkushan470
    @techkushan4702 жыл бұрын

    For how many seconds we should set ac and dc timer Give example

  • @earthenergyhex
    @earthenergyhex2 жыл бұрын

    Hi, I have a Schneider conext 4024 system with a 24V Battery System. I have a WEN 4750 Generator like in your video above. With that said, I have a relay setup, that when I lose the AC, which basically means, that her home is dead from the AC side of the Solar system, it will signal the relay to switch to the generator. The problem with that, is that I still have to manually go out and start the generator. So, what I’m Looking for is a switch that will sense the battery voltage and the loss of AC, in case of loss of Solar power, and a low voltage of the Battery system, to signal the Generator to start. Do you have any video's like that?

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Thanks your comment. There is currently no video created. I will create it.

  • @Adnan-ayoub
    @Adnan-ayoub7 ай бұрын

    ❤❤❤❤

  • @ELTronic3

    @ELTronic3

    7 ай бұрын

    Thanks friend..

  • @scottymatthews6821
    @scottymatthews68213 жыл бұрын

    good video but question is what if you wanted to simply run generator manually?

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    I will submit a video with a suitable solution for it.

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    Thank for your comment 😊

  • @kirejosifovski6648
    @kirejosifovski66482 жыл бұрын

    You take neutral kontrol after main contactor, how it will be activated

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Neutral wire should be connect to contactor coil ..

  • @user-wl2ji8bf2m
    @user-wl2ji8bf2m14 күн бұрын

    Gen stop piont how to work with N/C point in relay of contector Gen stop and start function is same, hiw to work this function? Sir please this doubt.

  • @ELTronic3

    @ELTronic3

    6 күн бұрын

    Watching care full my friend kzread.info/dash/bejne/pHykvKempavRnrQ.htmlsi=DY91VePcfBL_pQGZ Thanks.

  • @abudaoud1310
    @abudaoud13102 жыл бұрын

    sir please make 3phase ATS & auto generator diagram video

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    I will create this video immediatly.Thanks👍👍

  • @Sir_Gee
    @Sir_Gee2 жыл бұрын

    Pardon me, Shouldn't the Stop of the gen be connected to the N/O of the relay? In that way, it the completes the STOP circuit when the power returns

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Thanks your comment. 😍 Depending on the type of start stop switch on the generator we can select N / O, N / C on the relay.

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Please watch other video.. kzread.info/dash/bejne/pHykvKempavRnrQ.html

  • @user-ke2mc9qm5m

    @user-ke2mc9qm5m

    Жыл бұрын

    @@ELTronic3 my

  • @nhempanha8523
    @nhempanha85232 жыл бұрын

    I don’t know how to stop machine?when main supply coming?🙏

  • @ELTronic3

    @ELTronic3

    Жыл бұрын

    Thanks your comment.please watch my ATS video.. kzread.info/dash/bejne/pHykvKempavRnrQ.html

  • @easyelectric5761
    @easyelectric57613 жыл бұрын

    Please sir is video main main & gen indicator & auto manual rotary switch connection Karke dikhyo

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    I will create this method video

  • @mangalaguillaume3487
    @mangalaguillaume34873 ай бұрын

    merci pour le montage, comment la bobine du premier contacteur sera exciter or pour l'exciter , il faut que le timer soit fermé or il n'a pas encore son neutre pour basculer vers le contactes fermés ( 8 et 6), avec le relais aussi (8 et 6 est ouvert), il est alimenté par le neutre de la sortie or les contacteurs sont tous ouverts car leurs bobines ne sont excitées, ... le montage n'a pas encore fonctionné

  • @ELTronic3

    @ELTronic3

    3 ай бұрын

    Thanks your best comment...please watch this video for better idea kzread.info/dash/bejne/pHykvKempavRnrQ.htmlsi=k732LE3WC3bwCwbz Thanks..❤️❤️

  • @GurdeepSingh-uq4fq
    @GurdeepSingh-uq4fq2 жыл бұрын

    Sir light ane se genrator off hoga fir or DG contactor off hoga fir timer chalega last may Main contactor on hoga kya

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Thanks friend .. Please watch this video kzread.info/dash/bejne/pHykvKempavRnrQ.html

  • @tanveerabbas8095
    @tanveerabbas80953 жыл бұрын

    And another why you use relay for generator stoping use n/c point

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    You can also use the N / O point depending on the stop switch used on the generator

  • @JustaCuriousity
    @JustaCuriousity2 жыл бұрын

    Hi, should A2 be coming from either 6/L3 Main Supply or Generator? In your diagram, its coming from 5/L3? How will contactor ever be turned on?

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    a2 must be neutral for the contactor to be on.

  • @easyelectric5761
    @easyelectric57613 жыл бұрын

    Sir video thoda jaldi banate to Accha hota

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    Thank you..next video create fast

  • @jkkhan8697
    @jkkhan86972 жыл бұрын

    How its working with out Neutral U can not connect Neutral from the main power or Generator and how to stop Generator self starter wy U not use to NC point of contactor and it can run to b two timer 12vol and 220vol

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Thank your comment..I always use contactor n/c point.interrlock system very important.

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Please watch this video.. kzread.info/dash/bejne/pHykvKempavRnrQ.html

  • @tanveerabbas8095
    @tanveerabbas80953 жыл бұрын

    If you use this comman neutral I think circuit not working plz clear this

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    In one case only one contactor is turned on (interlock system is used) so it is not common neutral.

  • @user-ke2mc9qm5m
    @user-ke2mc9qm5m Жыл бұрын

    I want to see the 240 volts wiring diagram

  • @ELTronic3

    @ELTronic3

    Жыл бұрын

    The timer contactor used should be 240V.Diagram same

  • @ELTronic3

    @ELTronic3

    Жыл бұрын

    Watch this one..to better understand . kzread.info/dash/bejne/pHykvKempavRnrQ.html

  • @christophernwafor9779
    @christophernwafor97793 жыл бұрын

    How can i identity the stop and start wires of a generator?

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    Remove the wire from the start switch and off switch from the control box of the generator. Connect the wire as in this video.

  • @christophernwafor9779

    @christophernwafor9779

    3 жыл бұрын

    Pls how can i contact you to send you the images of the generator am talking about. Thanks?

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    @@christophernwafor9779 thank you.. your comment.

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    eltronic3@gmail.com

  • @christophernwafor9779

    @christophernwafor9779

    3 жыл бұрын

    Ok bro

  • @noumanahmad205
    @noumanahmad2052 жыл бұрын

    Please brief in audio how this circuit works

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Thank you friend.I will create your video.😊

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Check this out for now. kzread.info/dash/bejne/pHykvKempavRnrQ.html

  • @noumanahmad205

    @noumanahmad205

    2 жыл бұрын

    Thanks

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Ok friend .Stay with me.🤗

  • @lovealone327lovelykashiflo6
    @lovealone327lovelykashiflo62 жыл бұрын

    bahi jaan mujhy ji batain ky genrator ki jo start ke wire ja stop karny wali wire kaisy lagy gin ap ke meherbani ho gi janab ager numbr mil jaye to sab say best ha thanks

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Thanks your comment..

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    kzread.info/dash/bejne/pHykvKempavRnrQ.html

  • @raghavans5113
    @raghavans5113 Жыл бұрын

    Software name pls

  • @RajeshKumar-ol6kx
    @RajeshKumar-ol6kx2 жыл бұрын

    Sir dg automatic on off hoga kya

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Thank you friend your comment..

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Please watch this video kzread.info/dash/bejne/pHykvKempavRnrQ.html

  • @RajeshKumar-ol6kx

    @RajeshKumar-ol6kx

    2 жыл бұрын

    Stop aur start push bottn hai kya ya

  • @rehopowertv3908
    @rehopowertv39083 жыл бұрын

    Thank you so much i am glad. please can you make this circuit a PDF so i can get it printed? if i can send my mail address. thanks

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    Thank you I do not currently have the circuit diagram here. I will create it and give it to you.

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    Sorry for being late to reply😊😊

  • @ELTronic3

    @ELTronic3

    3 жыл бұрын

    eltronic3@gmail.com my email..

  • @cramesh13
    @cramesh13 Жыл бұрын

    How to get neutral to main contactor coil for operation. Without neutral contactor not hold

  • @ELTronic3

    @ELTronic3

    Жыл бұрын

    Thanks your comment.please watch this video..kzread.info/dash/bejne/pHykvKempavRnrQ.html

  • @smeysmey8540
    @smeysmey85402 жыл бұрын

    សុំសួរមួយលោកគ្រូតើប្រព័ន្ធនេះវាដេរម៉ាស៊ីនភ្លើង auto មែន

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Thanks your comment ..😍😍

  • @zainmalik7977
    @zainmalik7977 Жыл бұрын

    Sir

  • @ELTronic3

    @ELTronic3

    Жыл бұрын

    Yes...🙂

  • @ghiex1
    @ghiex12 жыл бұрын

    Wiring on A2 is wrong it will not automatically turn to normal when the mains power returns.

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Thanks your comment 😊..please watch this video. kzread.info/dash/bejne/pHykvKempavRnrQ.html

  • @hendrikjunaidi6092
    @hendrikjunaidi60922 жыл бұрын

    it will not work because A2 (-) taking from output (after contactor), should be from input (before contactor). and generator continue start, never stop.

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Thanks you for your comment.

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Please watch this video.(Single Phase ATS with explain) kzread.info/dash/bejne/pHykvKempavRnrQ.html

  • @HafeezKhan-qi7jj
    @HafeezKhan-qi7jj2 жыл бұрын

    good send me 3phase

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Thanks friend..i will create 3phase ats system 🤗

  • @BonnieSichone-lw6bx
    @BonnieSichone-lw6bx2 ай бұрын

    Use manual change over switch

  • @ELTronic3

    @ELTronic3

    Ай бұрын

    This circuit is automation circuit..you like manual switch..

  • @peterjesus816
    @peterjesus8162 жыл бұрын

    Poor explanation, when ur sharing knowledge always try to explain not to play music

  • @kingsylla5633
    @kingsylla56332 жыл бұрын

    Hello

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Hello friend ..

  • @kingsylla5633

    @kingsylla5633

    Жыл бұрын

    Every Time i look but i dont undasting i want

  • @silasdumbi9206
    @silasdumbi920610 ай бұрын

    Salut je peux avoir son schéma

  • @ELTronic3

    @ELTronic3

    10 ай бұрын

    No poblem.thanks

  • @jubayerofficialyt6579
    @jubayerofficialyt6579 Жыл бұрын

    oi vai aita koi pabo piz bolben

  • @ELTronic3

    @ELTronic3

    Жыл бұрын

    what are you saying dude....

  • @PiyushSharma-bt6mx
    @PiyushSharma-bt6mx2 жыл бұрын

    Line digram banao l

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    What line diagram...

  • @zainmalik7977
    @zainmalik7977 Жыл бұрын

    Hlo

  • @ELTronic3

    @ELTronic3

    Жыл бұрын

    Helloo friend. watch my videos always.

  • @techkushan470
    @techkushan4702 жыл бұрын

    Give me the model no. Of that contractor

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    A contactor with a current of 40A should be selected between the main contact points. Both auxiliary points of the first contactor should be N / C.

  • @Oyajihajannat
    @Oyajihajannat5 ай бұрын

    এইখানে তিনটা রিলে দরকার নেই,,, একটাই এনাপ,, যদি জানলে,,,,,,

  • @ELTronic3

    @ELTronic3

    4 ай бұрын

    Thanks friend your comment..

  • @prabathyasiru339
    @prabathyasiru3392 жыл бұрын

    මට මේකෙ ඩයිග්‍රම් එකක් ගන්න පුලුවන්ද..

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Mekat balanna..kzread.info/dash/bejne/pHykvKempavRnrQ.html Digaram eka adapu ekak ne ne.adala tamai denna wenne..

  • @TiwaAngoly
    @TiwaAngolyАй бұрын

    Stop too much music playing 2:43

  • @masoudirani2657
    @masoudirani26572 жыл бұрын

    This is Wair (N) poroblam for bobin s condactor s

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Thanks friend your comment. please watch this video kzread.info/dash/bejne/pHykvKempavRnrQ.html

  • @masoudirani2657

    @masoudirani2657

    2 жыл бұрын

    @@ELTronic3 Thanks i see

  • @TiwaAngoly

    @TiwaAngoly

    Ай бұрын

    You are right

  • @TiwaAngoly
    @TiwaAngolyАй бұрын

    Stop too much music playing

  • @mostaqueal-mehedi9370
    @mostaqueal-mehedi93702 жыл бұрын

    Poor Explanation

  • @ELTronic3

    @ELTronic3

    2 жыл бұрын

    Ok friend. kzread.info/dash/bejne/pHykvKempavRnrQ.html

  • @TiwaAngoly
    @TiwaAngolyАй бұрын

    Stop too much music playing 2:43

  • @TiwaAngoly
    @TiwaAngolyАй бұрын

    Stop too much music playing

  • @TiwaAngoly
    @TiwaAngolyАй бұрын

    Stop too much music playing 2:43

Келесі