AHU Cooling Coil Design Calculation (Step-By-Step Clear Guide)

Тәжірибелік нұсқаулар және стиль

A step-by-step guide on how to size AHU cooling coil from sensible cooling load to calculating the AHU airflow, identifying the on/off coil conditions and finding the on/off coil enthalpy for coil load calculation.

Пікірлер: 12

  • @aircondlounge
    @aircondlounge6 ай бұрын

    Before AHU cooling coil design, the sensible and latent cooling load must be determined. Anyone interested to learn how to perform cooling load calculation, check out my RTS Cooling Load Calculation Course (course.aircondlounge.com/rts-cooling-load-calculation-course). If you would like to go through this video in the future, it is quicker to read my blog post (aircondlounge.com/how-to-size-ahu-cooling-coil). Feel free to ask questions in the comment section if you have any.

  • @vanzproject9378
    @vanzproject937820 күн бұрын

    Im from indonesia , thanks sir you are amazing ,

  • @aircondlounge

    @aircondlounge

    20 күн бұрын

    It’s nice to meet you!

  • @sadeghnaderi4129
    @sadeghnaderi412913 күн бұрын

    @aircondlounge if your AHU is CAV you can add sensible heat to get total sensible heat. if AHU is VAV then you can nod add the max of each zone sensible heat together

  • @aircondlounge

    @aircondlounge

    13 күн бұрын

    For VAV AHU, you should apply a diversity factor to the total sensible heat you mean?

  • @sadeghnaderi4129

    @sadeghnaderi4129

    11 күн бұрын

    @@aircondlounge you should calculate total sensible load of all zones hourly to find the worst scenario with highest load, not just add the load of each zones together. because they can not occur at the same time to add them together

  • @aircondlounge

    @aircondlounge

    11 күн бұрын

    For load calculation yes. However, if those zones are serve by one AHU, adding the max load at each zone at different hour will lead to oversizing because when one zone is at max load, it doesn’t necessarily means the other zones are at max load as well. So, sum up the load by the same hour and choose the highest one should be the optimal approach.

  • @sadeghnaderi4129

    @sadeghnaderi4129

    11 күн бұрын

    @@aircondlounge yes thats what I mean. So you select the hour with highest load?

  • @aircondlounge

    @aircondlounge

    11 күн бұрын

    Because this video is about coil sizing, the sensible loads are just an example. In load calculation, I do calculate by hourly and pick the highest load hour.

  • @user-jw7gh5py3v
    @user-jw7gh5py3v5 ай бұрын

    Where can i get the copy for psychometric chart same as what you use in the video?

  • @aircondlounge

    @aircondlounge

    5 ай бұрын

    It is extracted from the ASHRAE Handbook. You may try google it though.

  • @user-jw7gh5py3v

    @user-jw7gh5py3v

    4 ай бұрын

    @@aircondlounge ok thanks a lot. :)