A Common PROBLEM With AirTemp Units & How I Fix It | HVAC Repairs

Фильм және анимация

- SUPPORT THE CHANNEL -
www.patreon.com/qualityhvacr?...
- Check out @TruTech Tools, LTD -
www.trutechtools.com (Use promo code “QUALITYHVAC” to save 8%)
- HVAC TACTICAL -
hvactactical.com/ (Use Promo Code "QUALITYHVAC" to save 10%)
- FOLLOW ME -
Instagram: @qualityhvacr
- BUSINESS INQUIRES -
qualityhvacrtn@gmail.com
- TOOLS I USE -
Fieldpiece SC480 Meter: www.trutechtools.com/Fieldpie...
Fieldpiece SC680 Meter: www.trutechtools.com/Fieldpie...
Fieldpiece Job Link HVACR Charge & Air Kit: www.trutechtools.com/JL3KH6?a...
Fieldpiece SM380V Digital Manifold: www.trutechtools.com/Fieldpie...
Veto ProPac Tech MCT Tool Bag: www.trutechtools.com/TECHMCT?...
Supco Magnetic Umbrella: www.trutechtools.com/Supco-Ma...
Solderweld HVAC Brazing Pack: www.trutechtools.com/HVAC-15-...
Solderweld Hot Block Putty: www.trutechtools.com/SolderWe...
Navac 2cfm Battery Operated Vacuum Pump: www.trutechtools.com/NAVAC-NP...
Cordless-Vacuum-Pump-2CFM?affid=38
Accutools BluVac Micron Gauge: www.trutechtools.com/Accutool...
Accutools TruBlu Evacuation Kit: www.trutechtools.com/Accutool...
Veto ProPac LC Tool Bag: www.trutechtools.com/Veto-Tec...
Veto ProPac MC Tool Bag: www.trutechtools.com/Veto-Pro...
Fieldpiece Job Link Pressure Probe: www.trutechtools.com/Fieldpie...
Appion 1/2" Hose: www.trutechtools.com/MH120006...
Appion 3/8" Hose: www.trutechtools.com/Appion-M...
AccuTools Core Removal Tool: www.trutechtools.com/Accutool...
Malco Sheet Metal Snips (Left Cut): www.trutechtools.com/Malco-M2...
Malco Sheet Metal Snips (Right Cut): www.trutechtools.com/Malco-M2...
Malco Sheet Metal Snips (Bulldogs): www.trutechtools.com/Malco-M2...
Malco Sheet Metal Snips: www.trutechtools.com/Malco-MC...
Malco Turbo Shear Cutter: www.trutechtools.com/Malco-TS...
Malco Sheet Metal Hole Cutter: www.trutechtools.com/Malco-HC...
Malco Flex Duct Cutter: www.trutechtools.com/Malco-FD...
Malco Panduit Gun: www.trutechtools.com/Malco-TY...
Malco Sheet Metal Hammer: www.trutechtools.com/Malco-RH...
Malco Turbo Crimper: www.trutechtools.com/Malco-C5...
Malco Sheet Metal Pipe Crimper: www.trutechtools.com/Malco-C5...
Malco Reversible Hex Driver: www.trutechtools.com/Malco-MS...
Malco 24" hand bender: www.trutechtools.com/Malco-24...
I've had several AirTemp heat pump package units with an issue in the heat mode. The unit turns on, then after a min it shuts off with no code on the circuit board. In this video I show how I fix this common problem. Hope you enjoy the video, LET'S DO SOME WORK!!
#heatpump #hvac #hvacrepair

Пікірлер: 111

  • @soloch69
    @soloch692 жыл бұрын

    Thank you for the great video I had this same problem 2weeks ago and it was the Contactor also replaced it just like you did everything went back to normal working at 100% once again thank you for the great video keep them coming stay safe out there

  • @tuningtobi
    @tuningtobi2 жыл бұрын

    Very helpful, I don't know about the problems with the 24v circuit and the relays. I always look forward to your videos, thank you.

  • @DerbyDogz
    @DerbyDogz2 жыл бұрын

    Had a York Predator Heat Pump RTU kick my butt one time via a contactor coil. Every time the simplicity board would send a 24V signal for the 2nd stage compressor it would completely blank out the board and go into a power recycle start up delay. Had several others say they've encountered similar issues with York Units & contactor coils. But good informative video!

  • @b-2466
    @b-24662 жыл бұрын

    Thanks for the tip man. Always the best content from this channel. 👌🏻

  • @gerardsullivan2337
    @gerardsullivan2337 Жыл бұрын

    Thank you for your video I had no heat last night it dropped to 29 degrees. When ohming out the coil I found a broken wire. Repaired and we were good. Thank you

  • @MariosACandRefrigeration
    @MariosACandRefrigeration2 жыл бұрын

    For what they are worth,i would replace all 3 a lot less than a call back,thanks for the info.

  • @Austin23191
    @Austin231912 жыл бұрын

    Crazy thing I had happen while at a heat PM at the start of the heating season. Trane heat pump and air handler, about 5 years old, I tested the auxiliary heat first then the heat pump via the installer test settings on a visionpro 8000. Then I tested both together and the contactor in the heat kit fried the coil out of nowhere. Thankfully the customer understood that nothing I did caused that to happen and it was a crazy fluke

  • @whitneyowen8551
    @whitneyowen85512 жыл бұрын

    Excellent content sir! Love troubleshooting!

  • @jonathanraul4086
    @jonathanraul40862 жыл бұрын

    Great job! Thanks for the info. Keep up the great work!

  • @HVACGUY
    @HVACGUY2 жыл бұрын

    Good find. But, gotta ask why do they use two contactors for 8kW?

  • @jammin345

    @jammin345

    2 жыл бұрын

    Good question. Contactor with black wires supplies 120v to one side of two heaters. Contactor with red wires supplies 120v other side of heaters to total 240v, and runs through hi limit switches.

  • @chadillac_256

    @chadillac_256

    2 жыл бұрын

    Them contactors probably are 30 amps so 8 kw is to much for one

  • @rruizproductions
    @rruizproductions2 жыл бұрын

    Nice diagnosis and fix! Thanks!

  • @RjsEpicAdventures
    @RjsEpicAdventures2 жыл бұрын

    Thanks for the great info may help for future calls

  • @enriquehvac6004
    @enriquehvac60042 жыл бұрын

    Thanks for the tip I’ll be looking out, good job 👍

  • @tunaman2200
    @tunaman22002 жыл бұрын

    Thank you sir for sharing this knowledge. Very interesting.

  • @thesilentonevictor
    @thesilentonevictor2 жыл бұрын

    Great tip Zack knowledge is important 👌

  • @richardthomas1743
    @richardthomas17432 жыл бұрын

    Great information and repair! 👍

  • @jfjhtfghgfhgf
    @jfjhtfghgfhgf2 жыл бұрын

    Been installing Rheems for over 10 years. Over the past 2 years they have been having massive issues with their contactors as well.

  • @OGHVAC
    @OGHVAC2 жыл бұрын

    Great information and video young man. I'm no longer in the field service business but appreciate the knowledge the young generation of techs are sharing. I am a stationary engineer at a LARGE data center working on CRAH, CRAC unit's and chillers/cooling towers. Same principle but much larger scale equipment. I enjoy your videos and even though I've been in the HVAC industry for 42 years, it's a joy to learn something new. Keep up the great work. 👍🏾

  • @bobbybroderick3299
    @bobbybroderick32992 жыл бұрын

    Might as well swap the evap while your at it It’s an airtemp 😁

  • @johnwalker890
    @johnwalker8902 жыл бұрын

    Good job Zack.

  • @emeryhvac1023
    @emeryhvac10232 жыл бұрын

    Good tip. Thanks for the video.

  • @canhn8574
    @canhn85742 жыл бұрын

    Easy to understand. Thank you.

  • @ryanmarshall9146
    @ryanmarshall91462 жыл бұрын

    Great video! So I see you have a topper on your truck now. Can you do a video on your truck setup sometime? I always like to how other people have there trucks setup. Thanks man

  • @per995
    @per9952 жыл бұрын

    Great job😊 Could it be that the surface for the relays placed near the heaters get warm? Added heat to coils is not a great condition if picked up from the assembly. The right sided one catch more heat? Seldom seen coil failures on relays over my years on equipments. May be change them to some better working ones? Later years I have been found of solid state types relays since they has been nice to me😬

  • @victorespana8684
    @victorespana86842 жыл бұрын

    greetings bro faithful follower of yours from your beginnings greetings from 🇪🇨

  • @BigmoRivera
    @BigmoRivera2 жыл бұрын

    Great Job Nicely Done 😉👍🏽

  • @JoseJB0
    @JoseJB02 жыл бұрын

    Very common in Trane/American Standard package heat pumps also.

  • @jrod3515
    @jrod35152 жыл бұрын

    Love the new black out trailer 👍

  • @randytorboli
    @randytorboli2 жыл бұрын

    The ECM blower motors on these systems are notorious for failing

  • @davidcruickshank2419
    @davidcruickshank24192 жыл бұрын

    I see a new cap on the truck… need to post a video of the new set up

  • @jaykemm3472
    @jaykemm34722 жыл бұрын

    Good info. Thanks

  • @moeselec
    @moeselec2 жыл бұрын

    Thanks for the tip.👍👍👍

  • @washer-dryer-ac-repairshop8643
    @washer-dryer-ac-repairshop86432 жыл бұрын

    Great job

  • @IslandbreezeMechanical
    @IslandbreezeMechanical2 жыл бұрын

    Fixed several straight cool units with the same issue. The ones I did blew the fuse.

  • @tingo210
    @tingo2102 жыл бұрын

    Good information

  • @oscarsoto8413
    @oscarsoto84132 жыл бұрын

    Thanks Boss Good Video

  • @REFERTECH4U
    @REFERTECH4U2 жыл бұрын

    Hey bud you did a video that is called I can’t believe this happened it was a package unit on the ground and you were replacing a blower motor and the housing was a plastic housing and you were using a hand held pump sprayer and you poured some viper cleaner in it.great video by the way if you don’t mind me asking where did you purchase that hand held pump sprayer it had a black and blue top on it ?.

  • @mrtryhard1996
    @mrtryhard19962 жыл бұрын

    Have you seen this in regular split systems as well or just package units with electric heat?

  • @dyung0007
    @dyung00072 жыл бұрын

    Zack have you use any flareseal in refrigeration HVAC ductless Schrader valve or mini split.

  • @douglaskahane141
    @douglaskahane1412 жыл бұрын

    Change both contractors and do not pull wires from them. Use a long nose pliers to pull wires loose.This will save a repeat call.

  • @hvacguy8362

    @hvacguy8362

    2 жыл бұрын

    Agree

  • @89dhvac

    @89dhvac

    2 жыл бұрын

    Why?

  • @jorgejr2697

    @jorgejr2697

    2 жыл бұрын

    Agree

  • @89dhvac

    @89dhvac

    2 жыл бұрын

    Why does everyone want to change both contactors when one tested good? Doesn’t this seem a little bit like wasting the customers money? And why do we need to use long nose pliers to pull wires loose? Please explain….

  • @douglaskahane141

    @douglaskahane141

    2 жыл бұрын

    @@89dhvac because both contractors are the same part number. Also, by pulling on the wires there is the chance of the wires coming out of the spade terminals. When the other contractor fails the client will have the same problem. Eliminate a call back and save the client time and money. A contractor does not cost that much.

  • @johncondron7404
    @johncondron74042 жыл бұрын

    Main Power breaker box looked a little rough,( rusty) is that for ac and everything in the house? normally most inside out the weather , ? but ha good job getting it going /

  • @sknight0391
    @sknight03912 жыл бұрын

    Ever get the feeling China is doing this to us on purpose? Contactors have been around for decades and there's never been this high of a failure rate that we're seeing right now in the industry. Most of it seems to be with the contactors on the heat kits. Trane has had major issues. Rheem has been affected and now Airtemp. Carrier was having a lot of problems with their contactors on the outdoor units. China is out to get us...one cheap part at a time. 😎👍

  • @Heavy_metal_rulez

    @Heavy_metal_rulez

    2 жыл бұрын

    I do believe your 100% right about china doing this on purpose. Its all part of the globalist agenda

  • @DanO181919

    @DanO181919

    2 жыл бұрын

    Made in China…. Enough said. 🤦‍♂️

  • @ApartmentMaintenance

    @ApartmentMaintenance

    2 жыл бұрын

    👍

  • @chrisb1899

    @chrisb1899

    2 жыл бұрын

    Yay, I had several Carrier AC compressor contractors short and destroy a Nest and Ecobee stats.

  • @sknight0391

    @sknight0391

    2 жыл бұрын

    @@chrisb1899 Hey "shorty" it's your birthday. Hey shorty blow the Nest up. 😁👌

  • @MarioMunoz-yz6we
    @MarioMunoz-yz6we2 ай бұрын

    Hey man. Do those run off of just this system or do they also come with the coil and the tank inside. We have one smiling but a little older and noticed we don't have the tank or e coil where I thought it would be

  • @hvacjay3201
    @hvacjay32012 жыл бұрын

    Wow 1st 👍🏻 love the videos. As always great work.

  • @quintend1465
    @quintend14652 жыл бұрын

    I have been having issues with contractor on Airtemp equipment in general

  • @harrellfamilyfun
    @harrellfamilyfun2 жыл бұрын

    Keeps us busy🙂

  • @brandonspangler38
    @brandonspangler382 жыл бұрын

    Every package heat pump air temp I've had problems with is the back left low fitting to condenser coil ruptures . Same place everytime. I'll never sell their products.

  • @neildam7677
    @neildam7677 Жыл бұрын

    Package units on the side of a house are hilarious to me.

  • @matthewjones541
    @matthewjones5413 ай бұрын

    Does this apply on air temp heat pump systems with electric furnace in its Mobil homes

  • @utubepro7742
    @utubepro77422 жыл бұрын

    Sometimes the voltage tap should be changed too?

  • @maracservices
    @maracservices2 жыл бұрын

    Can’t say iv ever seen a residential Packaged unit in Australia. Are they common in the US? Nice video as always 👍🏻

  • @OGHVAC

    @OGHVAC

    2 жыл бұрын

    @Mitch Attwood, package unit's either heatpump or gaspaks are very common in the USA. Depends on the brick and mortar build of the home or commercial structure. Some have natural gas piped to them, some do not. In my 42 year's being in the HVAC trade in America, I've seen hundreds of package unit's.

  • @maracservices

    @maracservices

    2 жыл бұрын

    @@OGHVAC thanks mate. I watch so many HVAC vids from the USA and was genuinely surprised how many Air Conditioner / Gas Furnaces there are over there as opposed to just a reverse cycle Air Conditioner. Very interesting watching how other countries do things . 👍🏻 thanks

  • @jimmurphy7849
    @jimmurphy7849 Жыл бұрын

    what kind of tool bag do you use.

  • @1jckinnick
    @1jckinnick6 ай бұрын

    Would this cause it to not reach the set temp on the thermost mine never gets to the set degree

  • @ufartface
    @ufartface2 жыл бұрын

    do you know the difference between heater coil and heat pump? please let us know

  • @carystone7168
    @carystone71682 жыл бұрын

    I live in DFW, Texas. Residential package units are very uncommon in this area. Why are package units so common in Nashville?

  • @WGwarrior20
    @WGwarrior209 ай бұрын

    If you get Error 02 and SC. On heat and cool, could the contactor of the heater pack can cause the issues. Error 02 keep tripping after reseting the control board. Won't let the unit call for cool or heat.

  • @dyershvac5884

    @dyershvac5884

    9 ай бұрын

    I have ran into this on literally 6 or 7 units. An Error code 02 will show and the SC as well. Definitely a shortage somewhere. These units are notorious for this issue

  • @profuse007
    @profuse0072 жыл бұрын

    8K electric heat strip as a secondary heat added. isn't that too much heat or that the HP is not very effective?

  • @jammin345

    @jammin345

    2 жыл бұрын

    8kw heating strips supplies 27K btus which matches the heat pump heating capacity. The heating strips not only provide supplemental heat, but it also acts as back up if the heat pump (compressor) were to fail.

  • @waterfuel
    @waterfuel Жыл бұрын

    My Powermate 3400W generator won't turn on my NEW gas furnace! It did run the old oil furnace. When utility power to house came back on, the furnace started. The generator sockets have 3rd ground hole The ground is already connected to neutral side. The power out at end of 3 prong extension cord was 60cycle AC 117volts. What's wrong? The male plug has poor ground. The socket on furnace has loose connection for plug. Is the new gas furnace in lockout mode? Service sheet says no power.Does the new Airtemp gas furnace have a timed off period before allowing main circuit board to turn on? No response from contractor. He has the plague.

  • @keithehrman5490
    @keithehrman54902 жыл бұрын

    Why are you checking g and commen. Check r and c.for system low voltage.

  • @tanjeetsahota7434
    @tanjeetsahota74342 жыл бұрын

    Update on The Trailer !!!! Thing looks nasty

  • @stephwaylonwells3218
    @stephwaylonwells32182 жыл бұрын

    👍

  • @robertj.2319
    @robertj.23192 жыл бұрын

    When you sell and install low end equipment you get low end results!

  • @jorgeespinoza4002
    @jorgeespinoza40022 жыл бұрын

    God is Good! 🙏🏼❤️

  • @rabokarabekian409

    @rabokarabekian409

    10 ай бұрын

    witch one? all of em?

  • @chadillac_256
    @chadillac_2562 жыл бұрын

    You never quit learning I work on air temp and installed a bunch of them. Air temp don’t make contactors but air temp is bottom of the equipment line imo there workmanship is subpar at best

  • @genclark9214

    @genclark9214

    Жыл бұрын

    Is Goodman better?

  • @chadillac_256

    @chadillac_256

    Жыл бұрын

    @@genclark9214 Goodman workmanship and case is better but no there junk too get you a Bryant or American standard is my pick

  • @chadillac_256

    @chadillac_256

    Жыл бұрын

    @@genclark9214 all you gotta do is look at the brazed joints that’ll tell you a lot about a company right there I don’t know who airtemp and nordyne is getting to build these units but they are junk point blank and that micro channel is no good I’ve changed so many of them coils out I can’t count ‘em also changed a couple condenser coils out 1 was so out of square I couldn’t even get it back in the case junk!!

  • @phoenixhvac-r828
    @phoenixhvac-r8282 жыл бұрын

    Disappointed you didn't check control voltage after replacing contactor since that was your first troubleshooting indicator, other than that good stuff

  • @geraldborne94

    @geraldborne94

    6 ай бұрын

    Yes he did it read 14.5 volts

  • @phoenixhvac-r828

    @phoenixhvac-r828

    6 ай бұрын

    At no time in this video did he measure 14.5 volts, you are incorrect.

  • @realestateservicessaleshea99
    @realestateservicessaleshea992 жыл бұрын

    Thanks for the information. Thanks again for the videos. 🥃🥃🍺🍺🍺⛳🥃 Stay safe. Retired (werk'n)keyboard super tech. Wear your safety glasses!

  • @Christer885
    @Christer8852 жыл бұрын

    😊👍🌹

  • @PlowenYourMommy
    @PlowenYourMommy Жыл бұрын

    The best way to repair Air Temp systems. steps: 1) Uninstall the Air Temp hvac system. 2) Haul the uninstalled Air Temp system to the local dump. 3) Install another brand of hvac system (ie Carrier, Trane etc); anything other than a piece of sh*t Air Temp hvac system.

  • @picklerix6162
    @picklerix61622 жыл бұрын

    The coil is getting hot and melting the shellac on the coil windings, causing the windings to short out. Bad design.

  • @dewittarchibald7191
    @dewittarchibald71912 жыл бұрын

    Please stop wiggling those crimp connectors to remove them! Use a pair of needle nose to remove them. You can damage the wiring in the crimp by wiggling them.

  • @raymondperez8182
    @raymondperez8182 Жыл бұрын

    Why do need such a high resistance? Shouldn’t it be low resistance? New tech trying to comprehend the ohm side of things ?

  • @benjaminjeffries681
    @benjaminjeffries6812 жыл бұрын

    Airtemp got a manufacturing problem with the quality of their switchgear. Why does new American tech look like it was designed in the 80s? Definitely no fujitsu or daikin tech in there.

  • @steveturcotte7435
    @steveturcotte74352 жыл бұрын

    just as bad as the POS capacitors and copper there selling us nowadays

  • @ianicus123
    @ianicus1232 жыл бұрын

    Cheap cheap cheeeeeeap contactors.

  • @1shagg420
    @1shagg4202 жыл бұрын

    AirTemp is total garbage. Too bad the crap Trane replaced it with is also garbage! Come on Trane, you need to at least try to make something decent quality like Champion in the economy line.

  • @hvacguy8362
    @hvacguy83622 жыл бұрын

    Nortek global bought them out. Their units are all cheap parts and all seem to have major issues with them down here in florida.